Siemens 6SL3210-1KE17-5AF1 SINAMICS G120C PN Frequency Inverter 3.0kW
Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Siemens 6SL3210-1KE17-5AF1 is a compact frequency inverter within the SINAMICS G120C family, engineered for variable speed control of three-phase AC motors in industrial machinery. Built in a space-saving FSA frame size with dimensions of 196 x 73 x 203 mm, this unit unifies the power electronics and control system in a single IP20-rated enclosure. Operating on a 3AC 380 V to 480 V mains supply at 47 to 63 Hz, the inverter provides dual power ratings of 3.0 kW for low overload and 2.2 kW for high overload requirements. It features an integrated Class A EMC line filter to satisfy electromagnetic compatibility requirements and operates at a low sound pressure level of 52 dB with a 97% operational efficiency.
For network integration and drive control, the unit comes equipped with dual RJ45 ports supporting PROFINET IO and EtherNet/IP communications, allowing direct integration with SIMATIC S7-1200 and S7-1500 controllers. Physical I/O terminals feature 6 digital inputs, 2 digital outputs, 1 analog input, 1 analog output, and an external 24 V DC control supply input. Putting a spare inverter into service requires transferring drive parameters and network device names from the existing setup. Configuration data can be loaded using TIA Portal Startdrive, STARTER engineering software, a plug-in BOP-2 or IOP-2 operator panel, or cloned directly using a SINAMICS SD memory card. When replacing a failed unit, expert support from ABC Industrial Parts can assist in verifying configuration alignment and backing up drive parameters prior to installation.
Front panel visual diagnostics are provided by dedicated status LEDs labeled RDY, BF, and SAFE, which indicate unit readiness, fieldbus communication state, and Safe Torque Off activity. Integrated functional safety is standard via Safe Torque Off (STO) according to IEC 61800-5-2. Active faults and system status can also be queried online via PROFINET or through the diagnostic buffer of a connected BOP-2 or IOP-2 display panel. If power delivery issues or internal control errors persist after verifying input supply voltage, wiring connections, and fieldbus communication integrity, internal hardware component failures may be present. Because internal circuit failures are not field-serviceable, acquiring a tested exchange unit or utilizing rapid repair services from ABC Industrial Parts provides a direct route to restoring production.
Technical Specifications
| Manufacturer | Siemens |
| Part Number | 6SL3210-1KE17-5AF1 |
| Model / Type | Sinamics G120C PN |
| Product Family | SINAMICS G120C |
| Component Type | Frequency Inverter |
| Rated Power (Low Overload) | 3.0 kW |
| Rated Power (High Overload) | 2.2 kW |
| Supply Voltage Range | 380 - 480 V AC |
| Supply Frequency | 47 - 63 Hz |
| Output Current (Low Overload) | 7.3 A |
| Output Current (High Overload) | 5.6 A |
| Power Loss | 101 W |
| Efficiency | 97 % |
| Power Factor | 0.70 - 0.85 |
| Switching Frequency | 4 kHz |
| Digital Inputs | 6 |
| Digital Outputs | 2 |
| Analog Inputs | 1 |
| Analog Outputs | 1 |
| External Control Supply | 24 V DC |
| Frame Size | FSA |
| Dimensions (H x W x D) | 196 x 73 x 203 mm |
| IP Rating | IP20 / UL Open Type |
| Integrated Line Filter | Class A |
| Sound Pressure Level | 52 dB |
| Supported Protocols | PROFINET, EtherNet/IP |
Programming and Configuration
Parameterization and commissioning of the Siemens 6SL3210-1KE17-5AF1 frequency inverter are carried out using Siemens engineering tools, including TIA Portal Startdrive and STARTER software over a PROFINET Ethernet connection. Drive parameters can also be configured locally at the panel using optional plug-in operator terminals, such as the BOP-2 (Basic Operator Panel) or IOP-2 (Intelligent Operator Panel).
To streamline drive swapping and routine backup, the inverter features a slot for a SINAMICS SD memory card. Parameter sets can be stored on the SD card and automatically restored upon powering up a replacement drive, eliminating manual parameter entry. Correct parameter configuration ensures proper motor data adaptation, I/O mapping for the onboard 6 digital inputs, 2 digital outputs, and analog I/O, as well as proper configuration of the integrated Safe Torque Off (STO) safety function.
Communication and System Integration
The 6SL3210-1KE17-5AF1 inverter incorporates integrated dual-port PROFINET IO and EtherNet/IP fieldbus communication via standard RJ45 connectors. This dual-port architecture supports line and ring network topologies, facilitating seamless fieldbus cabling across distributed automation architectures without requiring external network switches.
Optimized for integration with SIMATIC S7-1200 and S7-1500 programmable logic controllers, the drive transmits cyclic process data such as speed setpoints, actual frequency, operating current, and fault status bits. System integration in TIA Portal enables unified engineering, simplified network address assignment, and central diagnostic monitoring across the entire control system.
Diagnostics and Status Indication
Real-time diagnostic feedback on the 6SL3210-1KE17-5AF1 is provided through local status LEDs on the unit's front face, operator panels, and online software tools. Front panel LEDs offer immediate visual feedback on operational readiness, bus traffic state, and safety function activation. Online diagnostics can be performed through TIA Portal Startdrive or STARTER over the fieldbus connection.
When utilizing an optional BOP-2 or IOP-2 display panel, maintenance personnel can access the inverter's fault code memory buffer to read active alarms and historic fault logs. This direct readout simplifies troubleshooting in the field without requiring a connected programming PC.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| RDY | Green/Red - Solid / Flashing | Green = ready for operation; Red = active fault condition; Flashing = commissioning or firmware update |
| BF | Red - Off / Solid / Flashing | Off = bus communication normal; Red / Flashing Red = PROFINET / EtherNet/IP bus error or loss of master connection |
| SAFE | Yellow - Solid / Off | Yellow = Safe Torque Off (STO) active; Off = STO inactive |
Replacement and Spare Part Considerations
When replacing an existing 6SL3210-1KE17-5AF1 frequency inverter, the replacement unit must match the physical frame size FSA and power specifications of 3.0 kW (low overload) / 2.2 kW (high overload) operating on a 380 V to 480 V 3 AC mains line. Verification of the integrated Class A line filter and PROFINET communication interface is necessary to ensure mechanical and electrical drop-in compatibility within the control cabinet.
Before putting the replacement inverter into service, parameter data must be transferred from the original unit using a SINAMICS SD memory card, an operator panel (BOP-2/IOP-2), or via TIA Portal Startdrive. The PROFINET device name and IP address must be assigned to match the original controller configuration to re-establish fieldbus communication. Additionally, safety signals and wiring connected to the integrated Safe Torque Off (STO) inputs must be functionally tested prior to restoring full operational drive enable.
Frequently Asked Questions
What software is used to commission the Siemens 6SL3210-1KE17-5AF1?
Commissioning and parameter configuration can be performed using TIA Portal Startdrive software or STARTER engineering tools over PROFINET. Alternatively, basic parameter setup can be completed using a plug-in BOP-2 or IOP-2 operator panel.
How do I transfer parameters to a replacement inverter?
Parameters can be cloned by backing up the parameter set to a SINAMICS SD memory card or operator panel (BOP-2/IOP-2) from the original drive and restoring it onto the replacement unit. Parameters can also be uploaded and downloaded via TIA Portal Startdrive.
What safety functions are built into this drive?
The drive includes integrated Safe Torque Off (STO) functionality conforming to IEC 61800-5-2 standards, allowing safety-related drive power shutdown without needing external contactors.
What communication protocols does the 6SL3210-1KE17-5AF1 support?
This unit includes dual RJ45 ports supporting PROFINET IO and EtherNet/IP fieldbus communication for integration with SIMATIC PLCs and third-party networks.
What does a red BF LED indicate on the front panel?
A solid or flashing red BF (Bus Fault) LED indicates a communication error on the PROFINET or EtherNet/IP network, such as a disconnected bus cable, incorrect network configuration, or loss of communication with the master PLC controller.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.
Disclaimer:
We are not an authorised distributor of Siemens.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.