Siemens 6ES5095-8MA01 S5-95U PLC CPU Module

New 
On request
Refurbished   
10+ available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: SIMATIC S5

The Siemens 6ES5095-8MA01 is an S5-95U PLC CPU module from the SIMATIC S5 product family. This compact controller operates from a 24 V DC supply and combines 16 digital inputs, 16 digital outputs and 8 analog inputs in one unit. Four digital inputs support interrupt-capable operation, while the digital outputs provide 24 V DC switching at up to 0.5 A per channel. The CPU is designed for maintaining established Siemens S5 automation systems with integrated I/O and SIMATIC S5-100U expansion capability.

Replacement commissioning is carried out through the integrated 15-pin Sub-D PG interface, which uses a TTY/current-loop connection for programming, commissioning and diagnostics. Siemens STEP 5 is used to maintain the PLC program and transfer it through the PG interface. Programs can be held in internal RAM with battery backup, while optional EPROM or EEPROM memory modules provide additional program storage and transfer options. When preparing a spare, check the installed CPU designation, I/O requirements, memory configuration, PG cable arrangement and connection to the SIMATIC S5-100U I/O bus.

The 6ES5095-8MA01 supports service diagnostics through STEP 5, including access to DB1 system parameters and analysis of the error stack. For a failed CPU, connect the programming device through the 15-pin TTY/PG interface, check the stored program and system parameters, and review the error stack before returning the replacement to service. This Siemens S5-95U CPU is discontinued, making a correctly matched repair or tested exchange unit relevant for restoring existing machinery and legacy automation equipment.

Technical Specifications

ManufacturerSiemens
Part number6ES5095-8MA01
Model/typeS5-95U
Product familySIMATIC S5
Component typePLC CPU module
Lifecycle statusDiscontinued
Supply voltage24 V DC
Digital inputs16 channels
Interrupt-capable inputs4 channels
Digital outputs16 channels
Digital output voltage24 V DC
Digital output current0.5 A per channel
Analog inputs8 channels
Programming interfacePG interface, 15-pin Sub-D TTY/current-loop
Interface functionProgramming, commissioning, and diagnostics
Expansion busSIMATIC S5-100U I/O bus
Engineering softwareSTEP 5
Diagnostic accessDB1 system parameters and error stack analysis via STEP 5
Program storageInternal RAM with battery backup; optional EPROM or EEPROM memory module

Programming and Configuration

Siemens STEP 5 is the engineering environment for programming, commissioning and servicing the S5-95U CPU. Program upload and download are performed through the integrated 15-pin Sub-D PG interface using a TTY/current-loop connection.

The PLC program can be maintained in internal RAM with battery backup. Optional EPROM or EEPROM memory modules provide additional storage and transfer options when preparing or replacing a CPU. During spare-unit commissioning, transfer the required program and check the DB1 system parameters through STEP 5 before returning the controller to operation.

Communication and System Integration

The 15-pin Sub-D PG interface provides the connection for programming, commissioning and diagnostics. It uses a TTY/current-loop connection for communication with the programming device.

The CPU connects to SIMATIC S5-100U I/O expansion modules through the SIMATIC S5-100U I/O bus. Compatibility checks should therefore include the installed expansion architecture as well as the CPU part number and integrated I/O requirements.

Diagnostics and Status Indication

Service diagnostics for the Siemens S5-95U are performed with STEP 5 through the 15-pin TTY/PG interface. The diagnostic functions include access to DB1 system parameters and analysis of the PLC error stack.

For troubleshooting, connect the programming device, review the error stack and inspect the DB1 system parameters. Program upload and download through the PG interface support restoration of the controller configuration when replacing a failed CPU.

Replacement and Spare Part Considerations

The Siemens 6ES5095-8MA01 is a discontinued S5-95U CPU module for existing SIMATIC S5 installations. Before selecting a replacement, match the complete part number and confirm the required 24 V DC supply, integrated I/O arrangement, memory configuration and SIMATIC S5-100U expansion connections.

Commissioning a spare may require the existing STEP 5 program, DB1 system parameters and the appropriate PG cable arrangement. Check whether the installation uses internal RAM with battery backup or an optional EPROM or EEPROM memory module, then transfer the required program through the 15-pin TTY/PG interface and review the error stack before operation.

Frequently Asked Questions

What is the Siemens 6ES5095-8MA01?

The 6ES5095-8MA01 is an S5-95U PLC CPU module from the Siemens SIMATIC S5 product family. It includes 16 digital inputs, 16 digital outputs and 8 analog inputs.

What supply voltage does the S5-95U CPU use?

The Siemens 6ES5095-8MA01 operates from a 24 V DC supply.

Which software is used to program and diagnose this PLC CPU?

Siemens STEP 5 is used for programming, commissioning and diagnostics. It provides access to DB1 system parameters and error-stack analysis.

How is the 6ES5095-8MA01 connected to a programming device?

Programming, commissioning and diagnostics use the integrated 15-pin Sub-D PG interface with a TTY/current-loop connection.

Can the S5-95U be expanded with additional I/O?

The CPU supports SIMATIC S5-100U I/O expansion modules through the SIMATIC S5-100U I/O bus.

What should be checked when replacing a failed 6ES5095-8MA01?

Match the complete part number and check the 24 V DC supply, integrated I/O, memory configuration, PG cable arrangement, STEP 5 program, DB1 system parameters and S5-100U expansion connections before commissioning the spare.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Siemens.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.