Lenze 00387068 EZN3A0500H007 3-Phase Mains Choke 50A 0.7mH

New 
1 available for direct collection
Refurbished   
10+ available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: EZN3 Series | Series: EZN3

The Lenze 00387068, type EZN3A0500H007, is a 3-phase mains choke from the EZN3 Series engineered for power conditioning in industrial drive systems. Designed to operate in standard 3-phase AC power networks up to 480 V AC, this line reactor provides a continuous current handling capacity of 50 A with a nominal inductance of 0.7 mH per phase. Built in an IP00 open-frame enclosure for panel or cabinet mounting, the component filters harmonic distortion and suppresses voltage spikes generated by variable frequency drives and servo controllers. By inserting precise inductive reactance upstream of the drive rectifier, it protects internal DC bus capacitors and reduces electrical stress across factory automation, packaging, material handling, and automotive manufacturing machinery.

Integrating a replacement mains choke into an existing machine installation requires verifying the physical wiring connections and electrical ratings. As a passive inductive component, the unit does not require parameter setup, software loading, or firmware alignment when swapped into a system. Line phase conductors must be secured directly to the terminal connections according to the system power distribution layout. When replacing a damaged unit, confirming that the current rating of 50 A and inductance of 0.7 mH match the original specification ensures proper harmonic filtering and drive protection. Maintenance personnel can source a tested replacement unit through ABC Industrial Parts to restore stable supply power to downstream inverters without altering control software.

Diagnostic evaluation of the EZN3A0500H007 focuses on physical and electrical inspection of the magnetic windings and terminal points. In the event of drive power faults or thermal overload, first-line checks include examining the choke for thermal discoloration, insulation degradation, or mechanical stress. Quantitative testing is performed by measuring phase-to-phase winding inductance using an LCR meter to verify that values remain consistent with the 0.7 mH specification across all three phases. Because internal winding short-circuits or structural insulation breakdowns cannot be repaired in the field, swapping out a compromised choke for a tested replacement from ABC Industrial Parts is the standard path to preventing further line transients and ensuring long-term drive operation.

Technical Specifications

ManufacturerLenze
Part Number00387068
Model / TypeEZN3A0500H007
Product FamilyEZN3 Series
Component Type3-Phase Mains Choke
Rated Current50 A
Inductance0.7 mH
Maximum Supply Voltage480 V AC
Number of Phases3
Protection RatingIP00

Diagnostics and Status Indication

Diagnostic procedures for the Lenze 00387068 line reactor rely on direct electrical measurement and visual inspection. Because the unit is a passive inductive device, diagnostic checks focus on evaluating the physical condition of the core windings and verifying phase-balanced inductance.

Troubleshooting should begin by inspecting the open-frame IP00 structure for signs of thermal stress, discoloration, or physical winding damage. Electrical health is verified by taking LCR meter inductance measurements across each phase to confirm balanced readings near the nominal 0.7 mH specification.

Replacement and Spare Part Considerations

When installing a replacement Lenze 00387068 EZN3A0500H007 mains choke, maintenance engineers must ensure the replacement matches the continuous current rating of 50 A and nominal inductance of 0.7 mH. Installing an incorrectly rated choke can lead to inadequate harmonic mitigation or excess voltage drop under load.

Because the IP00 open-frame construction provides no internal ingress protection against dust or moisture, the unit must be installed within a suitable control cabinet. Proper electrical isolation and terminal torque specifications must be observed during wiring to maintain long-term reliability and prevent thermal hotspots at the line terminals.

Frequently Asked Questions

What is the primary function of the Lenze 00387068 mains choke?

The Lenze 00387068 (EZN3A0500H007) is a 3-phase line reactor that filters mains current harmonics and suppresses voltage transients, protecting frequency inverters and extending the service life of internal DC bus capacitors.

What are the electrical ratings for the EZN3A0500H007?

The line reactor is rated for a continuous operating current of 50 A, a nominal inductance of 0.7 mH per phase, and supply voltages up to 480 V AC in 3-phase industrial power systems.

Is software configuration required when replacing a Lenze 00387068?

No, as a passive 3-phase inductive component, it requires no software configuration, firmware transfers, or parameter adjustments during installation.

How can the Lenze 00387068 be tested during maintenance?

Technicians can visually inspect the unit for thermal discoloration or mechanical damage to the windings and use an LCR meter to measure phase-to-phase inductance against the nominal 0.7 mH specification.

What protection rating does the Lenze 00387068 choke have?

It features an IP00 open-frame design, requiring installation inside a protected electrical enclosure or control cabinet.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.