Lenze 00384004 EVF8202-E 8200 Vector Frequency Inverter
Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze 00384004 EVF8202-E is a compact, control-cabinet-mounted frequency inverter within the Lenze 8200 vector series. Built for speed and torque regulation of three-phase AC induction motors, this 0.75 kW drive operates on a 230 V AC nominal supply voltage across a permissive range of 180 V to 264 V AC. It delivers a continuous output current of 4 A with an 8 kHz switching frequency and an adjustable output frequency range from 0 Hz to 480 Hz. Control methods include linear or quadratic V/f characteristics for standard centrifugal pump and fan applications, as well as sensorless vector control for demanding high-torque machinery.
Connecting and commissioning a replacement EVF8202-E drive requires attention to network interfaces and parameter configurations. The device features an integrated Automation Interface (AIF) slot designed for modular fieldbus cards, including CANopen (E82ZAFC), PROFIBUS-DP (E82ZAFDP), and LECOM RS-232/RS-485 interfaces. A spare drive requires transferring parameter files stored in the non-volatile internal EEPROM, which holds up to four switchable parameter sets. Parameter transfer and drive configuration are managed via Lenze Global Drive Control (GDC) software or the portable XT Keypad (E82ZBC). Reinstalling the original AIF module and reloading saved drive profiles ensures complete operational compatibility. Technical specialists at ABC Industrial Parts can assist with parameter extraction from donor hardware or preparing a replacement unit for immediate service.
Real-time operational feedback is provided through dual LED indicators on the front faceplate and accessible diagnostic parameters. A solid green LED signals that the inverter is enabled and running, whereas a blinking green LED indicates an active controller inhibit or mains connection without drive enablement. A solid red LED points to an active TRIP condition that disables power output, while a blinking red LED warns of an active threshold alert. Fault history is stored in parameter C0168, with active operational status available in parameters C0183 and C0161. Initial checks should confirm line supply voltage, cable connections, and heatsink thermal conditions. Persistent errors, such as hardware faults H05, power stage failures H10, or unresolvable OC1 short circuits, indicate non-serviceable internal component failure. In these instances, procuring a tested replacement or utilizing repair services through ABC Industrial Parts provides a rapid path back to production.
Technical Specifications
| Rated Power | 0.75 kW |
| Supply Voltage | 230 V AC |
| Supply Voltage Range | 180 - 264 V AC |
| Output Voltage | 230 V AC |
| Rated Output Current | 4 A |
| Output Frequency Range | 0 - 480 Hz |
| Switching Frequency | 8 kHz |
| Control Method | Sensorless Vector Control / V/f Characteristic |
| Mounting Type | Control Cabinet Built-in |
Programming and Configuration
Engineering and parameter adjustment for the Lenze EVF8202-E frequency inverter are conducted using Lenze Global Drive Control (GDC) software connected via a serial interface, or locally using the plug-in XT Keypad (E82ZBC). Drive settings are retained inside internal non-volatile EEPROM memory, which holds up to four independent, switchable parameter sets. These parameter sets permit rapid changeover of operating parameters for different products without requiring continuous downloading from a master controller.
When commissioning a replacement unit, parameter data must be reloaded from a saved GDC project file or cloned from an existing drive using the XT Keypad. Essential settings include motor nameplate parameters, selection of V/f curve or sensorless vector control mode, acceleration and deceleration ramp times (parameters C0012 and C0013), and fieldbus network parameters. Proper alignment of these configurations ensures correct motor acceleration performance and activates protective functions such as I2t motor thermal monitoring.
Communication and System Integration
The Lenze EVF8202-E drive integrates into automated control environments via a plug-in Automation Interface (AIF) slot. This interface accepts expansion modules designed for various fieldbus and serial standards, enabling real-time control and remote monitoring from central programmable logic controllers.
Compatible plug-in options include the E82ZAFC System Bus module for CANopen networks, the E82ZAFDP module for PROFIBUS-DP, and LECOM RS-232 or RS-485 serial communication interfaces. When replacing an existing drive, removing the functional AIF card from the original unit and seating it into the replacement inverter preserves hardware physical interfaces, though bus node addressing and parameters must be verified upon installation.
Diagnostics and Status Indication
Visual status diagnostics on the EVF8202-E are provided by two faceplate LEDs indicating operational readiness and trip conditions. Parameter readouts C0183 and C0161 display real-time operating states and control status directly via connected software or keypad displays.
The inverter logs recent diagnostic events in parameter C0168, which serves as a fault history buffer. Detailed status menus, actual operating values, and historical trip logs can be navigated using the text interface on the XT Keypad (E82ZBC) or through the diagnostic monitor within Global Drive Control (GDC) software.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Green LED (Ready / Operation) | Green - Solid / Blinking | ON: Inverter enabled and ready for operation; BLINKING: Controller inhibit active (IMP block) or mains supply connected without drive enable. |
| Red LED (Trip / Fault) | Red - Solid / Blinking | ON: Fault/TRIP active, drive output disabled; BLINKING: Warning condition active. |
Replacement and Spare Part Considerations
Replacing a failed unit with a spare Lenze 00384004 (EVF8202-E) requires verifying electrical and physical specifications. The replacement inverter must match the 0.75 kW power rating and 230 V AC operating voltage to fit within existing cabinet space and wire directly to existing supply circuits.
Because frequency inverters store machine-specific settings in internal memory, a spare drive must be parameterized prior to operation. Transferring saved parameter sets via Global Drive Control (GDC) software or cloning them with an XT Keypad ensures ramp times, I/O terminal functions, and fieldbus parameters match original operational conditions. The plug-in AIF module must also be transferred from the existing unit to maintain network integration.
Although the Lenze 8200 vector series is phased out—with the Lenze i550 cabinet frequency inverter identified as its official modern successor line—sourcing an exact replacement EVF8202-E eliminates the need for cabinet rewiring or control software modification.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Short circuit / Earth fault | Short circuit at output terminals or earth fault in motor circuit. | Short circuit in motor or motor cables, motor cable too long, ground leak in motor line, internal power stage fault. | Check motor and output cables for short circuits or insulation resistance to earth. If fault occurs with motor disconnected, internal power stage failure — return unit for repair. |
| OC2 | Overcurrent during acceleration | Motor current exceeded limit during acceleration phase. | Acceleration time configured too short, incorrect motor parameters, mechanical blockage/overload. | Increase acceleration time (parameter C0012), check motor rating and load. |
| OC3 | Overcurrent during deceleration | Motor current exceeded limit during braking phase. | Deceleration time configured too short. | Increase deceleration time (parameter C0013) or connect braking resistor. |
| OC4 | Overcurrent at constant load | Motor current exceeded overload threshold during steady operation. | Abrupt load change, motor stalled, drive undersized for application. | Inspect mechanical system for jams, check motor parameters and sizing. |
| OU | DC-bus overvoltage | Intermediate circuit voltage exceeded upper limit (>400 V DC for 230 V unit). | Excessive regenerative energy during deceleration, mains supply voltage too high. | Extend deceleration time, fit braking module / braking resistor, check supply voltage. |
| LU | DC-bus undervoltage | Intermediate circuit DC bus voltage dropped below threshold. | Supply mains voltage too low, supply power phase loss, mains failure. | Check mains voltage and line supply fuses/wiring. |
| OH | Heatsink overtemperature | Inverter heatsink temperature exceeded maximum threshold (>90 °C). | Inadequate cooling, dirty heatsink fins, fan fault, ambient temperature too high. | Clean heatsink, improve cabinet ventilation, lower switching frequency or reduce continuous load. |
| OH4 | Motor thermal overload (I2t) | Motor calculated thermal overload based on I2t monitoring. | Continuous low-speed operation under heavy load, incorrect motor thermal parameter settings. | Check motor load, check motor I2t parameter configuration. |
| OH8 | Motor thermistor overtemperature | Motor PTC thermistor trip condition detected. | Motor overheating, defective thermistor sensor, broken sensor wire. | Check motor temperature, verify PTC thermistor wiring and connection. |
| CE0 | AIF communication error | Communication fault between drive board and function module in AIF slot. | Loose module, fieldbus timeout, defective function module or plug contact. | Check fieldbus cabling and master, reseat plug-in module in AIF slot. |
| PEr | Parameter set error | Parameter data corruption detected during power-up or parameter load. | Power failure during parameter write, internal EEPROM fault. | Load factory default settings and re-download parameter file. If error persists, internal memory hardware fault — return unit for repair. |
| H05 | Internal hardware fault | Internal control board self-test failed. | Board hardware component failure. | Internal hardware failure — return unit for repair or replace inverter. |
| H10 | Internal power stage fault | Power section electronic fault detected during startup check. | Damaged gate driver or internal sensing circuit failure. | Internal hardware failure — return unit for repair or replace inverter. |
Frequently Asked Questions
What software is used to program the Lenze EVF8202-E frequency inverter?
The Lenze EVF8202-E is configured using Lenze Global Drive Control (GDC) software or locally using the portable XT Keypad (E82ZBC). Parameters are stored internally in non-volatile EEPROM across up to four parameter sets.
How do I transfer parameter settings to a replacement EVF8202-E drive?
Parameters can be transferred by uploading the saved file from Global Drive Control (GDC) software or by transferring parameter data stored in an XT Keypad (E82ZBC) into the replacement unit.
What does an OC1 fault code indicate on the EVF8202-E inverter?
An OC1 fault indicates an output short circuit or earth fault in the motor circuit. If the fault persists when the motor cable is disconnected from the drive, an internal power stage failure has occurred and the unit must be returned for repair.
Which fieldbus modules can be used with the EVF8202-E drive?
The drive features an Automation Interface (AIF) slot supporting plug-in modules such as CANopen (E82ZAFC), PROFIBUS-DP (E82ZAFDP), and LECOM RS-232/RS-485 interfaces.
What is the official modern successor to the Lenze 8200 vector series?
The Lenze 8200 vector series is phased out, and the Lenze i550 cabinet frequency inverter series serves as its modern successor for new installations.
What do the faceplate status LEDs indicate on the EVF8202-E?
A solid green LED indicates normal operation and drive enablement, while a blinking green LED indicates controller inhibit or power applied without enable. A solid red LED indicates an active TRIP fault, and a blinking red LED signals an active warning condition.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.