Lenze 00384008 EVF8212-E – 8200 Vector 1.5kW Frequency Inverter
Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze 00384008 (Model EVF8212-E) is a 1.5 kW (2 HP) frequency inverter belonging to the 8200 Vector product family. Operating on a 3-phase supply range of 320 V AC to 550 V AC, this AC drive delivers a continuous output current of 3.9 A at 400 V AC and 3.3 A at 480 V AC, with a maximum 60-second overload capacity of 5.9 A (150%). Built in a compact IP20 enclosure for panel mounting inside control cabinets, the unit regulates motor speed across an output frequency range of 0 to 480 Hz. Supported control modes include linear V/f, quadratic V/f, sensorless vector control, and closed-loop vector control, making it suitable for material handling equipment, industrial fans, pumps, and packaging machinery.
Integrating a replacement drive into an existing system requires matching both the primary drive hardware and its installed control interfaces. The EVF8212-E features a modular structure that accepts pluggable function modules for standard control I/O or fieldbus communications, including CANopen, PROFIBUS-DP, DeviceNet, and INTERBUS. Drive configuration and parameter monitoring can be performed via the Lenze E82ZBC XT Keypad or Lenze Global Drive Control (GDC) PC software. Non-volatile internal EEPROM memory can store up to four complete parameter sets, facilitating configuration transfers to replacement hardware. When replacing a failed unit where parameter extraction from a faulty board is needed, ABC Industrial Parts can support configuration recovery and parameter transfer to ensure proper commissioning.
Diagnostic monitoring is provided directly on the front panel via LED status indicators and accessible status parameters. A green LED signals operational readiness and enable states, while a red LED indicates active trip faults or reset procedures. The drive maintains a TRIP memory buffer storing historical fault codes alongside real-time operating metrics like DC bus voltage, motor current, and heatsink temperature. Common operational issues often relate to external conditions such as line voltage drops, motor wiring defects, or fieldbus interruptions. For non-serviceable internal power stage faults, sensor defects, or persistent memory corruptions, sourcing a tested exchange unit from ABC Industrial Parts offers a fast path back to full production.
Technical Specifications
| Manufacturer | Lenze |
| Part Number | 00384008 |
| Model / Type | EVF8212-E |
| Product Family | 8200 Vector |
| Component Type | Frequency Inverter |
| Rated Power (400V) | 1.5 kW |
| Rated Power (480V) | 2 hp |
| Supply Voltage Range | 320 - 550 V AC |
| Rated Mains Current (400V) | 5.0 A |
| Rated Mains Current (480V) | 4.3 A |
| Continuous Output Current (400V) | 3.9 A |
| Continuous Output Current (480V) | 3.3 A |
| Maximum Output Current (60s) | 5.9 A |
| Output Frequency Range | 0 - 480 Hz |
| Default Switching Frequency | 8 kHz |
| Control Modes | V/f linear, V/f quadratic, sensorless vector control, closed-loop vector control |
| Protection Rating | IP20 |
Programming and Configuration
Parameter setup for the Lenze 00384008 EVF8212-E drive is executed using Lenze Global Drive Control (GDC) PC software or the optional E82ZBC XT Keypad module. Engineering software gives access to all motor parameters, V/f profile adjustments, vector control tuning, switching frequencies, acceleration and deceleration ramps, and digital or analog terminal assignments.
The inverter contains internal non-volatile EEPROM storage designed to maintain up to four distinct parameter sets simultaneously. This multi-parameter architecture enables operators to switch between different operational setups or back up operational settings directly onboard. Saved configuration files can be uploaded using GDC software or copied via the XT Keypad, allowing simple parameter restoration to replacement units.
Communication and System Integration
The EVF8212-E drive features an adaptable interface bay accepting various pluggable function and communication modules. Standard point-to-point control interface is provided through modules like the Lenze E82ZAFSC Standard I/O module. Higher-level automation integration is established through fieldbus modules such as the E82ZAFCC CANopen module, as well as optional hardware interfaces for PROFIBUS-DP, DeviceNet, and INTERBUS networks.
Fieldbus modules interface directly with the main control board to transmit control commands, monitor operational status, and adjust speed setpoints remotely. Address selection switches and network communication settings are stored directly within the drive parameters or hardware rotary selectors, requiring verified bus termination and correct baud rate matching during network commissioning.
Diagnostics and Status Indication
System state monitoring on the Lenze EVF8212-E is managed using front status LEDs, the E82ZBC XT Keypad LCD display, or live monitoring variables within Lenze Global Drive Control (GDC) software. An internal TRIP memory buffer records fault histories, allowing maintenance personnel to inspect fault events and evaluate operational status parameters such as motor current, voltage, and DC bus voltage stored under code index C005x.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Red LED (TRIP / Fault) | Red - Solid or Flashing | Flashes or lights continuously when a fault trip condition occurs. Blinking codes indicate fault state or active fault reset. |
| Green LED (RUN / Ready) | Green - Solid or Flashing | On: Drive operational / enabled. Flashing: Controller inhibit active or operating in standby state. |
Replacement and Spare Part Considerations
When replacing a Lenze 00384008 EVF8212-E drive, verify that the replacement match the required hardware power rating (1.5 kW / 400 V). Pluggable function or fieldbus communication modules from the original unit must be physically transferred to the replacement drive. If a module type differs from what the drive configuration expects, fault code P13 will be triggered until acknowledged via keypad or software.
Parameter sets transferred to the replacement inverter must correspond strictly to the drive hardware size and firmware version. Attempting to load a parameter file designed for a different power class triggers fault code P12. Following parameter restoration, recheck fieldbus node addresses, motor parameters, and safety circuit interlocks before returning the machine to production. For long-term lifecycle planning, the Lenze i550 cabinet inverter series serves as the manufacturer's recommended modernization path.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Overcurrent during acceleration | Output current exceeds threshold during drive acceleration phase. | Short circuit in motor winding or cable; Acceleration time set too short; Motor cable too long; Incorrect motor parameters. | Check motor and motor wiring for short circuits or ground faults; Increase acceleration time (C0012); Verify motor parameter settings. |
| OC2 | Overcurrent during deceleration | Output current exceeds current threshold during braking or deceleration phase. | Deceleration time set too short; Short circuit in motor/cable. | Increase deceleration time (C0013); Check motor and output wiring. |
| OC3 | Overcurrent at steady state | Output current exceeds threshold during constant speed operation. | Sudden load impulse; Short circuit at inverter output; Earth fault. | Check load mechanics; Check motor and cable insulation. |
| OC4 | Motor earth fault | Earth/ground fault detected on output motor phases. | Motor winding isolation breakdown; Motor cable shorted to earth; Excessive cable capacitance. | Check motor insulation resistance with megohmmeter; Check motor cable for ground connection or damage. |
| OC5 | Continuous overload / I2t trip | Drive operating above continuous output current limit for too long (I2t integration threshold exceeded). | Motor overload; Drive undersized for mechanical load; Stalled motor. | Reduce motor load; Check machine mechanics for blockage/binding; Verify drive current rating. |
| OU | Overvoltage on DC bus | DC bus link voltage exceeded upper threshold (approx. 770-800 V DC). | Excessive regenerative energy from motor during deceleration; Deceleration ramp too short; Missing or defective brake resistor; Mains supply voltage too high. | Increase deceleration time; Connect external braking resistor and verify brake chopper configuration; Check AC mains voltage. |
| LU | Undervoltage on DC bus | DC bus link voltage dropped below lower operation threshold. | Mains supply voltage drop or failure; Phase failure on supply line; Mains contactor dropped out. | Check supply line voltage and input fuses; Verify incoming mains phase connections. |
| OH | Heatsink overtemperature | Heatsink temperature exceeds maximum allowed operating limit (approx. 90°C). | Ambient temperature too high; Cooling fan defective or clogged; Inadequate cabinet ventilation; Continuous high load / low switching frequency derating. | Improve cooling airflow; Clean cooling fins and check fan operation; Reduce switching frequency or load. |
| OH4 | Motor overtemperature (PTC) | Motor temperature sensor connected to T1/T2 terminals triggered trip. | Motor overloaded; Inadequate motor cooling; Defective PTC sensor or open sensor line. | Allow motor to cool down; Check motor load and ventilation; Verify sensor connections at T1/T2. |
| OH7 | Heatsink temperature sensor fault | Internal temperature sensor line open or defective. | Internal temperature sensor wire open or damaged; Internal control board hardware defect. | Internal hardware fault — requires board repair or unit replacement. |
| OH8 | Inside temperature trip | Internal enclosure temperature inside inverter too high. | Cabinet ambient temperature too high; Internal drive fan failure. | Check enclosure cooling and ambient operating conditions. |
| CE0 | Communication error / Time-out | Communication failure or message timeout on fieldbus module. | Interrupted fieldbus cable; Bus master stopped or disconnected; Incorrect baud rate or slave address. | Check bus cable connections and termination resistors; Verify master controller status and configuration. |
| EE0 | EEPROM system error during startup | Internal non-volatile parameter memory read error on power-up. | Corrupted non-volatile memory; Internal power supply brownout during save process. | Re-initialize drive to factory default settings (C0002). If error persists, internal control board hardware fault — return unit for repair. |
| EE1 | EEPROM checksum parameter fault | Parameter checksum mismatch in EEPROM memory. | Parameter transfer interrupted or memory corrupted. | Reload factory defaults or re-download parameter set via software/keypad. |
| EEr | External TRIP trip | TRIP signal triggered via digital input assigned to external trip function. | External fault monitoring sensor/contact activated. | Check external circuit connected to configured TRIP digital input. |
| H05 | Internal power section fault | Hardware fault detected in internal power gate driver or board control hardware. | Internal component failure; Power section damaged. | Internal hardware fault — unit is not field-serviceable, replace inverter or send for repair. |
| LP1 | Motor phase failure | One of the three motor output phases U, V, or W is interrupted. | Broken cable wire; Loose motor terminal connection; Motor contactor open. | Check motor cables, output contactors, and terminal block connections. |
| P12 | Parameter set error | Incompatible parameter set loaded into inverter. | Parameter set from a different drive rating or firmware loaded. | Verify parameter file matches drive power rating and firmware version. |
| P13 | Function module changed fault | Pluggable function module was replaced or removed while drive configuration expected another module type. | Function module missing or changed. | Re-install correct function module or acknowledge configuration change via keypad/GDC. |
Frequently Asked Questions
Which programming software is used to configure the Lenze EVF8212-E drive?
The Lenze EVF8212-E frequency inverter is configured using Lenze Global Drive Control (GDC) PC software or locally using the pluggable E82ZBC XT Keypad.
How are parameters restored to a replacement EVF8212-E unit?
Parameters stored in the drive non-volatile EEPROM can be backed up and restored using Lenze GDC software or transferred directly between drives using the pluggable E82ZBC XT Keypad module.
What does fault code OU indicate on the Lenze 00384008 drive?
Fault code OU indicates an overvoltage condition on the DC bus link (exceeding approx. 770-800 V DC). Common causes include short deceleration ramps, regenerative energy from decelerating heavy loads, missing braking resistors, or excessive AC mains supply voltage.
Why does fault code P13 occur after replacing a communication module?
Fault code P13 indicates that the pluggable function or fieldbus module was replaced or removed while the drive configuration expected a different module type. The change must be acknowledged via the keypad or GDC software, or the original module reinstalled.
What is the recommended modern replacement for the Lenze 8200 Vector series?
The Lenze i550 cabinet inverter series is recommended by the manufacturer as the long-term successor for the legacy 8200 Vector product line.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.