Lenze E82EV152_4B 8200 Vector Frequency Inverter 1.5 kW

New 
On request
Refurbished   
6 available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: 8200 Vector | Series: 8200 Vector

The Lenze E82EV152_4B is a 1.5 kW variable frequency inverter from the 8200 Vector series, engineered for precise speed and torque control of three-phase AC motors. Operating on a three-phase AC supply voltage ranging from 320 V to 528 V at 45 to 65 Hz, this compact IP20 unit delivers a continuous output current of 3.9 A at an 8 kHz switching frequency with an output frequency range of 0 to 480 Hz. Control flexibility is provided through linear V/f, quadratic V/f, and Sensorless Vector Control (SLVC) modes, complemented by an integrated Class A/B EMC filter to minimize electromagnetic interference without requiring external filtering components in control cabinets.

Integrating a replacement E82EV152_4B into a machine requires swapping the existing modular control interface into the replacement base unit. The inverter utilizes a modular slot architecture supporting pluggable function modules—such as the E82ZAFSC, E82ZAFA, E82ZAFPC, or E82ZAFAC—or an XT Keypad (E82ZBC). These modules provide terminal connections and interface options for CANopen, PROFIBUS-DP, InterBus, and LECOM networks. Commissioning a replacement unit involves transferring saved parameter profiles; the drive contains four internal non-volatile parameter sets that can be duplicated using the XT Keypad copy function or Lenze Global Drive Control (GDC) software. Technical teams at ABC Industrial Parts can assist in sourcing functional replacement hardware to restore existing machine configurations.

Diagnostic conditions are visually indicated via front-panel status LEDs and tracked in an internal fault history buffer that logs trip events and operating parameters. A solid red LED indicates an active fault or drive error, while the green LED blinks to signify drive ready or inhibit states and remains solid when the drive is enabled and running. Initial field troubleshooting should include checking line supply stability, motor insulation, output wiring, and the seating of the plugged function module. When severe internal trips occur, such as persistent EEPROM memory corruptions (EEr) that resist parameter resets, internal hardware failure is indicated, making a tested replacement or repair unit from ABC Industrial Parts the most practical path to minimize line downtime.

Technical Specifications

ManufacturerLenze
Part NumberE82EV152_4B
Model / TypeE82EV152_4B
Product Family8200 Vector
Component TypeFrequency Inverter
Supply Voltage320 - 528 V AC
Mains Frequency45 - 65 Hz
Rated Power Output1.5 kW
Continuous Output Current3.9 A
Output Frequency Range0 - 480 Hz
Switching Frequency8 kHz
Overload Capacity180% rated current for 60s
Control MethodSensorless Vector Control (SLVC), V/f linear, V/f quadratic
Protection RatingIP20
EMC FilterIntegrated Class A/B Interference Filter

Programming and Configuration

The Lenze E82EV152_4B frequency inverter features parameter handling capabilities designed for quick setup and backup maintenance. It houses four non-volatile parameter sets directly within internal memory, allowing distinct operational configurations to be stored locally. Parameters can be modified, saved, and backed up using Lenze Global Drive Control (GDC) software connected via a suitable interface or directly through the optional plug-and-play XT Keypad (E82ZBC).

During commissioning or maintenance, parameter sets can be copied from one unit to another using the XT Keypad memory transfer capability, avoiding manual entry of drive parameters. Key timing and dynamic settings—such as acceleration time (C0012) and deceleration time (C0013)—allow tuning of acceleration ramp rates and regenerative braking dynamics. In cases where parameters become corrupted or require a clean baseline setup, restoring factory defaults is executed by setting parameter C0002 to 1.

Communication and System Integration

System integration for the Lenze 8200 Vector series relies on a modular function slot design on the front of the inverter. The base unit E82EV152_4B does not embed permanent control terminals on its main power chassis; instead, it interfaces with external control networks and terminal wiring via pluggable function modules. Compatible function modules include standard and application I/O boards such as the E82ZAFSC, E82ZAFA, E82ZAFPC, and E82ZAFAC.

Depending on the specific module installed in the function slot, the inverter can operate on various industrial fieldbus communication protocols, including CANopen, PROFIBUS-DP, InterBus, and LECOM serial interfaces. This modular approach allows the drive to be integrated into centralized PLC architectures or localized I/O configurations. Ensuring proper module seating, correct bus cable shielding, and accurate bus termination settings is necessary for stable fieldbus communication.

Diagnostics and Status Indication

Visual diagnostic indications on the E82EV152_4B are provided by dedicated status LEDs located on the front panel. A continuous green LED indicates that the drive is enabled and actively running, while a blinking green LED signals a ready or drive inhibit state. An active fault condition is indicated by a solid red LED.

For detailed diagnostic analysis, the inverter maintains an internal fault history buffer that logs recent trip codes alongside drive status flags. Real-time parameter monitoring and error code evaluation can be performed remotely using Global Drive Control (GDC) software or locally via the XT Keypad (E82ZBC).

Status LED Indicators

LEDColor/StatusMeaning
Red LEDRed - SolidFault active / drive error condition
Green LEDGreen - Blinking or SolidBlinking = ready/inhibit, continuous = drive enabled/running

Replacement and Spare Part Considerations

When replacing a failed Lenze E82EV152_4B inverter, maintenance personnel must retain the pluggable function module attached to the front slot of the original unit. Because the base power chassis does not include control terminal blocks, transferring the original function module (or installing an equivalent unit) to the replacement drive is mandatory to re-establish control wiring and network communication connections.

Before putting a replacement unit into service, parameter alignment is required. Parameter sets saved on the original drive or stored in GDC software must be loaded onto the new unit, or copied directly using the XT Keypad (E82ZBC). Verify that parameter settings match the motor nameplate and machine requirements, including ramp times and control modes. Note that the 8200 Vector series has reached end-of-life status, and system modernization paths typically involve migrating to the Lenze i550 cabinet frequency inverter platform.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
OC1Short CircuitShort circuit on motor phase outputShort circuit in motor cable or motor winding, excessive capacitive ground currentCheck motor cable and motor insulation; verify drive output stage.
OC2Earth FaultGround fault on motor output sideGround fault in motor leads, motor insulation failureInspect motor cables and motor for ground faults.
OC5I x t OverloadContinuous overload during acceleration or steady operationExcessive mechanical load, motor size undersized, acceleration time set too shortReduce load, increase acceleration time (C0012), verify motor sizing.
OUOvervoltage DC BusIntermediate DC bus voltage exceeded maximum limitGeneratoric operation (deceleration too fast), mains supply voltage too highExtend deceleration time (C0013), fit external braking resistor or brake chopper.
LUUndervoltage DC BusIntermediate DC bus voltage dropped below minimum thresholdMains supply failure, supply voltage drop, phase lossCheck mains voltage, line fuses, line connection.
OHHeatsink OvertemperatureHeatsink temperature exceeds thermal limitInadequate cooling air supply, fan failed/blocked, ambient temperature too highClean heatsink fins, ensure adequate cabinet ventilation, check fan function.
OH4Motor Overtemperature (PTC)Motor temperature sensor / PTC triggered tripMotor thermal overload, low motor speed under high load without forced coolingAllow motor to cool down, check motor load and cooling.
Ce0Communication Failure / Module ErrorCommunication fault between inverter and function module / fieldbus optionFunction module loose or defective, fieldbus timeout, baud rate mismatchCheck module seating, verify fieldbus cabling and termination.
EErEEPROM FaultInternal EEPROM checksum error / parameter data corruptedPower failure during parameter save operation, internal memory hardware faultReload factory default settings (C0002=1). If error persists, internal hardware fault — return unit for repair.
P13Parameter ErrorInvalid parameter configuration or conflicting valuesInconsistent parameter settings enteredCheck setting parameters or reset parameter set to defaults.

Frequently Asked Questions

How do I back up or transfer parameters on the Lenze E82EV152_4B?

Parameter sets can be backed up and transferred using the Lenze Global Drive Control (GDC) software or by utilizing the parameter copy function of the plug-and-play XT Keypad (E82ZBC). The inverter holds up to four non-volatile parameter sets in internal memory.

Do I need to keep the function module when replacing an E82EV152_4B drive?

Yes, the control terminals and fieldbus interfaces are located on the removable function module (such as E82ZAFSC, E82ZAFA, E82ZAFPC, or E82ZAFAC). You must remove the module from the existing drive and plug it into the replacement unit to maintain wiring connections.

What do the red and green status LEDs on the drive indicate?

A solid red LED indicates an active drive fault or error. A continuous green LED indicates that the drive is enabled and running, while a blinking green LED signals that the drive is ready or in an inhibit state.

How do I clear an EEr EEPROM fault code?

An EEr fault indicates memory data corruption. You can attempt to clear it by resetting parameter C0002 to 1 to restore factory default settings. If the error persists after resetting, an internal memory hardware failure is present and the drive requires repair or replacement.

What fieldbus communication options are supported by the E82EV152_4B?

The drive supports CANopen, PROFIBUS-DP, InterBus, and LECOM serial interfaces depending on which pluggable function module is installed in the front function slot.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.