Lenze E82EV222_4B 8200 Vector Frequency Inverter 2.2kW

New 
On request
Refurbished   
8 available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: 8200 Vector | Series: 8200 Vector

The Lenze E82EV222_4B is a 2.2 kW (3 HP) frequency inverter from the 8200 Vector series, engineered for precise speed and torque regulation of three-phase AC induction motors in industrial machinery. Operating from a 3-phase supply voltage range of 320 to 550 V AC, this drive delivers a continuous output current of 5.6 A at 400 V AC and 4.8 A at 480 V AC, with a maximum overload capacity of 8.4 A supporting up to 150% output current for 60 seconds. The drive features a modular physical structure that separates the main cabinet-mounted power unit from attachable control terminals and fieldbus function modules. Supported motor control methods include high-dynamic sensorless vector control, linear V/f, quadratic V/f, and direct torque control across an output frequency range of 0 to 480 Hz with an 8 kHz switching frequency.

Integrating a replacement unit into an existing cabinet requires matching the installed function module and transferring application parameters. The E82EV222_4B base unit supports pluggable interface modules including the E82ZAFSC Standard I/O module, E82ZAFAC Application I/O module, E82ZAFCC CANopen module, and E82ZAFPC PROFIBUS-DP module, alongside support for DeviceNet, INTERBUS, and AS-Interface networks. Commissioning and parameter configuration are managed using Lenze Global Drive Control (GDC) software or the pluggable E82ZBC Keypad XT unit. Non-volatile internal EEPROM storage holds up to four complete, independent parameter sets, allowing convenient offline backup, cloned parameter duplication, or fast restoration when replacing a failed drive in the field. ABC Industrial Parts can assist with parameter extraction, module transfer, and supply of replacement units to keep production lines running smoothly.

Diagnostic information is provided via a front-mounted dual-color Red/Green Operating State LED and a fault memory log accessible through the optional E82ZBC Keypad XT, which logs the last four TRIP events with error codes and timestamps. A blinking green LED indicates normal operation with the drive enabled, solid green signals that the drive is ready or inhibited, blinking red signifies an active warning or trip condition, and solid red indicates an unrecoverable internal hardware or power stage fault. Common TRIP codes include OC1 through OC5 for overcurrent and motor thermal overload, OU and LU for DC bus link voltage monitoring, and OH series codes for motor or heatsink overtemperature. While errors such as CE1 option module communication failure or EEPROM fault P01 can often be resolved by reseating modules or reloading factory defaults, hardware errors like internal heatsink sensor faults H10 and H11 require board-level service or drive replacement. ABC Industrial Parts provides tested exchange units and professional repair services when internal hardware faults occur.

Technical Specifications

ManufacturerLenze
Part numberE82EV222_4B
Model / Type8200 Vector E82EV222_4B
Product family8200 Vector
Component typeFrequency Inverter
Rated power (400V)2.2 kW
Rated power (480V)3 HP
Supply voltage range320 - 550 V AC
Continuous output current (400V)5.6 A
Continuous output current (480V)4.8 A
Peak overload output current8.4 A
Output frequency range0 - 480 Hz
Switching frequency8 kHz
Control methodSensorless Vector Control / V/f linear / V/f quadratic / Torque Control

Programming and Configuration

Engineering and parameter management for the Lenze E82EV222_4B drive are executed using Lenze Global Drive Control (GDC) software or the E82ZBC Keypad XT pluggable control module. The inverter incorporates non-volatile internal EEPROM storage capable of holding up to four complete, independent parameter sets. This multi-set storage capability allows operators to maintain alternative operational profiles for different products or machine operating modes directly within the drive memory.

During drive replacement or commissioning, parameter sets stored in the EEPROM can be cloned and uploaded via GDC software or copied directly using the Keypad XT module. When swapping out a damaged inverter, restoring the saved parameter set to the replacement unit preserves calibrated motor characteristics, acceleration and deceleration ramps (parameters C0012 and C0013), motor rated current limits (C0016), and assigned digital input functions without requiring manual re-commissioning.

Communication and System Integration

The Lenze 8200 Vector series employs a flexible modular interface design where communication and control terminals are separated from the main power stage. Fieldbus and I/O integration is achieved by mounting optional function modules directly onto the front interface connector slot of the E82EV222_4B base unit. Available option modules include the E82ZAFSC Standard I/O module for conventional analog and digital wiring, and the E82ZAFAC Application I/O module for expanded input/output operations.

Industrial fieldbus network integration is supported through specialized communication option modules including the E82ZAFCC CANopen System Bus Module and the E82ZAFPC PROFIBUS-DP Communication Module, as well as modules for DeviceNet, INTERBUS, and AS-Interface networks. These communication options allow upper-level PLCs to command drive speed references, execute start/stop controls, and continuously retrieve operational process data and diagnostic status parameters over standard bus lines.

Diagnostics and Status Indication

Visual status monitoring on the E82EV222_4B is provided by a front-panel dual-color Red/Green Operating State LED. A flashing green light indicates normal enabled operation, while solid green indicates that the drive is powered and in a ready or inhibited state. A flashing red light indicates an active warning or TRIP condition, and a solid red light points to an unrecoverable internal hardware or power stage fault.

Detailed diagnostic analysis is supported through the pluggable E82ZBC Keypad XT or via Global Drive Control (GDC) software. The Keypad XT unit provides access to an internal fault memory log that stores the last four TRIP events along with exact fault codes and timestamps. Real-time operational variables, temperature readings, and fieldbus communication states can also be monitored continuously through GDC parameter channels.

Status LED Indicators

LEDColor/StatusMeaning
Operating State LED (Red/Green)Red/Green - Blinking Green / Solid Green / Blinking Red / Solid RedGreen blinking = Inverter enabled, operating normally; Green solid = Inverter ready / inhibited; Red blinking = Warning / Fault active; Red solid = Internal hardware / power stage fault.

Replacement and Spare Part Considerations

When replacing an E82EV222_4B frequency inverter, maintenance teams must confirm that both the main power base unit and the front option module match the existing machine configuration. Because the 8200 Vector family utilizes a separable power and module architecture, the existing function module (such as E82ZAFSC, E82ZAFAC, E82ZAFCC, or E82ZAFPC) can typically be unclipped and transferred to the replacement power unit, provided the replacement drive matches the 2.2 kW (3 HP) 320-550 V AC specification.

Although the Lenze 8200 Vector series has reached phase-out status and is officially succeeded by the Lenze i550 cabinet drive family (such as part number i55AE222F0000000S), the E82EV222_4B remains the direct drop-in replacement for existing control panels. Retaining saved parameter sets via Keypad XT or GDC software ensures rapid restoration without requiring panel re-wiring, fieldbus re-addressing, or PLC control software modifications.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
OC1Short circuit / Earth faultShort circuit at the motor terminals or earth fault in the motor cableShort circuit in motor winding or motor cable; ground fault; excessive capacitive cable charging currentsCheck motor cable and motor windings for short circuit or low insulation resistance; verify motor cable length limits.
OC2Overcurrent during accelerationOutput current threshold exceeded during motor acceleration phaseAcceleration time set too short; motor mechanically stalled or overloaded; incorrect motor parameter settingsIncrease acceleration time (C0012); check motor sizing and mechanical load for binding.
OC3Overcurrent at constant speedOutput current threshold exceeded during steady-state operationSudden load surge; motor stall; sudden mechanical jammingInspect mechanical system for sudden load changes or mechanical obstruction.
OC4Overcurrent during decelerationOutput current threshold exceeded during ramp-down / brakingDeceleration time set too short; high load inertiaIncrease deceleration time (C0013) or install brake module / resistor.
OC5I x t motor overloadMotor thermal overload accumulator threshold exceededContinuous operation above rated current; motor thermal time constant exceededReduce motor load; check duty cycle and cooling; verify C0016 motor rated current parameter setting.
OUOvervoltage in DC bus circuitDC bus link voltage exceeded upper threshold limitRegenerative energy during deceleration too high; main supply voltage too highIncrease deceleration time (C0013); fit brake module / braking resistor; check AC mains voltage.
LUUndervoltage in DC bus circuitDC bus link voltage dropped below lower threshold limitMains supply voltage too low; main AC supply interruption; phase failureCheck incoming AC power line, supply fuses, and wiring.
OHHeatsink overtemperatureDrive power stage heatsink temperature exceeded maximum safety threshold (>90°C)Insufficient cooling airflow; ambient temperature too high; cooling fan failure; heatsink cloggedClean heatsink cooling fins; verify cooling fan operation; improve cabinet ventilation.
OH4Motor overtemperatureMotor PTC thermistor or thermal contact sensor triggeredMotor thermal overload; insufficient motor self-cooling at low operational speedsAllow motor to cool down; reduce mechanical load; check forced cooling fan on motor.
OH7Drive internal overtemperatureTemperature inside inverter control board enclosure exceeded limitAmbient cabinet temperature too highImprove cooling inside control cabinet.
OH8Motor temperature sensor break / short circuitFault detected in motor thermal sensor measurement circuitOpen circuit or shorted wire on PTC sensor terminals T1/T2Check PTC wiring and sensor connections.
CE0Communication error - Process DataTime-out error receiving fieldbus process data objectsFieldbus cable broken or disconnected; master PLC stopped communicatingCheck fieldbus cable connections, termination resistors, and master station state.
CE1Communication error - Automation ModuleLoss of communication between inverter basic unit and installed option moduleFunction or communication module improperly seated or defectiveTurn off power, unseat and firmly reinsert option module. If fault persists, replace option module.
EErExternal TRIP faultExternal fault condition triggered via digital input programmed for External TRIP functionExternal safety relay, limit switch, or user interlocking openedCheck external fault condition on assigned digital input signal.
H10Heatsink temperature sensor short circuitInternal temperature sensor failureInternal hardware failure on power stage or control boardInternal board-level failure — return unit for factory service or replace inverter.
H11Heatsink temperature sensor open circuitInternal temperature sensor open circuit failureInternal hardware failure on board-level circuitInternal hardware failure — return unit for factory service or replace inverter.
NMAXMaximum speed exceededMotor actual speed exceeded maximum limit set in C0032Overhauling load driving motor faster than programmed speed limit; motor vector control instabilityCheck load mechanics; adjust speed controller parameters or overspeed thresholds.
P01Parameter EEPROM faultInternal non-volatile EEPROM read/write memory checksum faultPower failure during parameter write sequence; corrupted memory blockLoad factory defaults (C0002 = 1) and re-parameterize. If error recurs, replace inverter.

Frequently Asked Questions

What is the rated power and voltage range for the Lenze E82EV222_4B drive?

The Lenze E82EV222_4B has a rated power output of 2.2 kW (3 HP) and operates across a 3-phase AC supply voltage range of 320 to 550 V AC. It provides continuous output currents of 5.6 A at 400 V AC and 4.8 A at 480 V AC.

Which software and modules are used to configure the E82EV222_4B?

Configuration is performed using Lenze Global Drive Control (GDC) software or the pluggable E82ZBC Keypad XT module. Up to four complete parameter sets can be stored in the drive's internal non-volatile EEPROM.

How do I transfer parameters from a failed drive to a replacement unit?

Parameters can be saved and cloned using the E82ZBC Keypad XT module or backed up to a computer using GDC software. Uploading the saved file to the replacement drive restores acceleration ramps, motor data, and digital I/O assignments.

What communication options are supported on the 8200 Vector series?

The E82EV222_4B supports pluggable communication modules including CANopen (E82ZAFCC) and PROFIBUS-DP (E82ZAFPC), as well as modules for DeviceNet, INTERBUS, and AS-Interface networks.

What does a solid red Operating State LED indicate on the inverter?

A solid red LED indicates an internal hardware or power stage fault. Unlike transient warnings or fault trips, internal board-level failures require factory service or unit replacement.

What is the recommended replacement series if migrating away from the 8200 Vector family?

The recommended replacement family for the 8200 Vector series is the Lenze i550 cabinet drive series, specifically part number i55AE222F0000000S for 2.2 kW applications.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.