Lenze E82EV251_2C200 8200 Vector Frequency Inverter

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze E82EV251_2C200 is a compact 0.25 kW (0.34 HP) frequency inverter from the 8200 Vector series, engineered for precise variable speed control of asynchronous AC motors. Operating from a single-phase or three-phase supply voltage range of 180 V AC to 264 V AC, this IP20-rated cabinet drive delivers a continuous rated output current of 1.7 A and a maximum output current of 2.5 A. Control method options include sensorless vector control, standard V/f characteristic control, and torque control across an output frequency range from 0 Hz to 480 Hz. Designed without an integrated EMC filter, this specific chassis unit is intended for installation in control cabinets where external mains filtering is already provided.
Featuring a modular system architecture, the drive power unit operates alongside snap-in control interface modules and optional fieldbus adapters. Swapping a unit or commissioning a spare spare component requires transferring the front-mounted control module—such as an E82ZAFSC Standard I/O interface, an E82ZAFPC PROFIBUS-DP adapter, or an E82ZAFCC CANopen module—and transferring the drive parameters. Configuration data is structured under Lenze standardized C-parameter codes and can be rapidly duplicated using the removable memory unit, an E82ZBC keypad module, or Global Drive Control (GDC) PC software. Technicians preparing a spare unit can rely on ABC Industrial Parts to source tested drive hardware and assist with parameter extraction or interface module verification.
Local drive status is indicated by front-panel status LEDs that report power readiness, operating state, warnings, and active TRIP conditions. Internal software continuously monitors operating limits, logging fault events into the C0168 fault history buffer, which can be read using an attached keypad or PC setup tool. Typical trip causes include overcurrent on acceleration (OC1), DC bus overvoltage (OU), or DC bus undervoltage (LU). If the drive displays hardware codes such as H10 or H11, indicating an internal board or processor fault, field repairs are not possible; exchanging the faulty inverter with a fully tested unit through ABC Industrial Parts ensures a rapid return to production.
Technical Specifications
| Manufacturer | Lenze |
| Part Number | E82EV251_2C200 |
| Model / Type | 8200 Vector Frequency Inverter |
| Rated Power | 0.25 kW |
| Supply Voltage Range | 180 - 264 V AC |
| Output Voltage | 0 - 230 V AC |
| Rated Output Current | 1.7 A |
| Maximum Output Current | 2.5 A |
| Output Frequency Range | 0 - 480 Hz |
| Switching Frequency | 8 kHz |
| Control Method | Sensorless vector control, V/f characteristic control, torque control |
| Overload Capacity | 150% for 60 seconds |
| Enclosure Rating | IP20 |
| Mounting Type | Cabinet / DIN Rail / Panel Mount |
| EMC Suppression | Without integrated EMC filter |
Programming and Configuration
The E82EV251_2C200 uses the standardized Lenze C-parameter matrix to manage motor parameters, acceleration profiles, control methods, and fieldbus mappings. Parameters such as acceleration time (C0012), deceleration time (C0013), and maximum frequency (C0011) allow precise tuning for specific mechanical loads. The drive supports a 150% overload capacity for up to 60 seconds, which is configured and monitored via internal thermal motor models (C0075 and C0076).
Parameter management and drive commissioning can be executed via the plug-in E82ZBC keypad module or through Lenze Global Drive Control (GDC) software on a PC. When replacing an existing inverter, the pluggable memory chip allows direct parameter cloning between units without re-entering parameters manually. If a parameter set becomes corrupted or inconsistent, resetting the drive to factory default settings via C0002 enables a clean re-commissioning process.
Communication and System Integration
Integration into fieldbus networks and automated control systems is accomplished using plug-in function and communication modules attached to the front Automation Interface (AIF) slot. The drive hardware is compatible with standard modules including the E82ZAFSC Standard I/O module for hardwired terminal control, the E82ZAFPC module for PROFIBUS-DP, and the E82ZAFCC module for CANopen system bus integration. Additional network options such as Modbus RTU and EtherCAT are also supported through appropriate snap-in interfaces.
When configured on a network, status word inspection and control commands are exchanged continuously across the fieldbus interface. Proper physical installation requires securing the function module into the AIF slot to prevent contact issues. On CANopen and System Bus installations, verifying bus cable connections, baud rate alignment, and correct termination resistor placement is required to prevent communication timeouts.
Diagnostics and Status Indication
The drive features two status LEDs on the front panel that provide real-time visual feedback on operating state and active trip conditions. A green LED indicates power status and operational readiness, turning solid green when the inverter is enabled and running. A red LED indicates warning states or active TRIP faults, illuminating solid red during an active inverter fault and flashing when a start inhibit or warning condition is present.
In addition to LED indications, detailed fault diagnostics can be extracted from the C0168 fault history buffer using the E82ZBC keypad or GDC engineering software. The system monitors parameters such as heatsink temperature, motor overload conditions, DC bus voltages, and fieldbus communication integrity to maintain operational safety.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Red LED | Red - Solid / Flashing | TRIP active / Fault state. Solid red indicates inverter fault; flashing indicates warning or start inhibit. |
| Green LED | Green - Solid / Flashing | Operation / Ready. Solid green indicates inverter is enabled and operating; flashing indicates power on / ready state. |
Replacement and Spare Part Considerations
When replacing a failed E82EV251_2C200 inverter, ensure that the part number matches the required chassis configuration. The '200' suffix indicates that this unit does not contain an integrated EMC filter. Installing a unit without an EMC filter in an installation designed for integrated filtering may result in electromagnetic interference unless external mains filters are present.
Before applying power to the replacement drive, swap the function or fieldbus interface module (e.g., E82ZAFSC, E82ZAFPC, or E82ZAFCC) from the original unit onto the new power stage. Parameter settings must then be loaded via the plug-in memory chip or uploaded using the E82ZBC keypad module or GDC software to ensure correct motor parameters, operational limits, and fieldbus node addresses.
For long-term modernization planning or complete system overhauls, Lenze i510 and i550 cabinet inverter series serve as official successor lines for legacy 8200 vector installations. However, direct drop-in replacement with an identical E82EV251_2C200 remains the fastest method to restore operation without panel modification or wiring redesign.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Short circuit / Overcurrent during acceleration | Short circuit or earth fault on motor side; motor cable too long; acceleration time too short. | Motor cable short circuit or ground fault; motor winding defect; rapid acceleration setting. | Check motor and wiring for short circuits and ground faults; increase acceleration time C0012; check motor power rating. |
| OC2 | Overcurrent during deceleration | Overcurrent during braking or deceleration ramp. | Deceleration ramp C0013 set too short; braking resistor absent or misconfigured. | Increase deceleration time C0013; install or inspect external braking module/resistor. |
| OC5 | Overcurrent at constant speed | Overcurrent occurred during steady state operation. | Sudden load impulse; mechanical motor block/jam; drive overloaded. | Check mechanical load and motor; check drive sizing for application. |
| OU | DC bus overvoltage | Intermediate circuit voltage exceeded upper threshold level. | Mains supply voltage too high; motor operating in generator mode with deceleration time too short. | Check mains supply voltage; extend deceleration time; connect braking module/resistor. |
| LU | DC bus undervoltage | Intermediate circuit voltage dropped below minimum threshold level. | Mains supply voltage too low; mains phase failure; power line dip. | Check mains voltage; check fuses and supply connection lines. |
| OH | Heatsink overtemperature | Inverter heatsink temperature exceeded maximum permissible limit. | Ambient temperature too high; cooling fan defective or obstructed; heatsink dirty. | Improve enclosure ventilation; clean heatsink cooling fins; verify fan operation. |
| OH4 | Motor overtemperature (PTC / Thermistor) | Motor temperature sensor connected to T1/T2 terminals triggered thermal trip. | Motor overloaded; motor cooling blocked; thermal sensor tripped. | Allow motor to cool; check mechanical load and motor ventilation. |
| OH7 | Motor thermal overload (I2t calculation) | Calculated motor thermal load model exceeded 100%. | Continuous operation at low speed with high load current. | Reduce motor load; check motor thermal time constant C0075 / C0076 settings; consider forced cooling fan on motor. |
| LP1 | Mains phase failure | Phase failure detected on input mains AC supply. | Missing supply phase or high voltage asymmetry on mains input. | Check input fuses, supply wiring, and mains symmetry. |
| Pr1 | Parameter set fault | Parameter data in non-volatile memory corrupted or inconsistent. | Power failure during parameter store process; memory fault. | Re-load factory settings (C0002) and re-commission inverter; reload parameter backup. |
| EEr | External error | External trip signal activated via configured digital input terminal. | External fault monitoring sensor or safety circuit tripped. | Inspect external devices wired to TRIP input terminal. |
| CE0 | Communication error (System Bus / CAN) | Communication interruption or timeout on System Bus interface. | Bus cable disconnected, incorrect baud rate, missing bus termination resistor. | Check bus cable connection, termination switches, master controller status. |
| CE1 | Automation module communication fault | Communication failure between inverter power unit and inserted function module. | Function module loose, poor contact, or internal interface error. | Internal hardware or connection fault — re-seat function module; replace module if fault persists. |
| CE2 | Communication error (AIF / Fieldbus) | Communication timeout on Automation Interface (AIF) module (PROFIBUS, CANopen, etc.). | PLC stopped, fieldbus cable damaged, node address conflict. | Verify fieldbus master status, check cable connections and node configurations. |
| H10 | Internal hardware fault | Internal power board or control board hardware error detected during self-test. | Internal component failure. | Internal hardware failure — return unit for repair or replace inverter unit. |
| H11 | Internal control board error | Internal microcontroller / memory hardware defect. | Internal board component failure. | Internal hardware failure — return unit for repair or replace unit. |
| NMAX | Overspeed fault | Motor actual speed exceeded maximum limit (C0011 + tolerance). | Uncontrolled load overspeed or incorrect encoder feedback / motor parameter settings. | Check motor settings C0011, check mechanical load, verify encoder signal if used. |
| P13 | Inverter load trip (I x t) | Inverter power stage thermal limit exceeded continuous capacity. | High current demand sustained above continuous power rating. | Reduce drive load; increase inverter capacity if application demands continuous overload. |
Frequently Asked Questions
Does the Lenze E82EV251_2C200 have an integrated EMC filter?
No. The '200' suffix in E82EV251_2C200 designates a model without an integrated EMC filter. It is intended for applications utilizing external mains filters.
How are parameters transferred to a new replacement unit?
Parameters can be transferred by moving the removable memory unit to the new drive, using the plug-in E82ZBC keypad module to copy settings, or loading a parameter backup via Lenze Global Drive Control (GDC) software.
Which interface modules are compatible with this drive?
The drive accepts various plug-in modules via its Automation Interface (AIF), including the E82ZAFSC Standard I/O module, E82ZAFPC PROFIBUS-DP module, E82ZAFCC CANopen module, and the E82ZBC keypad.
What should I check if the drive displays an H10 or H11 fault code?
Fault codes H10 and H11 indicate internal hardware or control board failures. These errors cannot be resolved through field servicing or parameter resets, and the unit must be repaired or replaced.
What modern Lenze drive series can be used to migrate away from the 8200 Vector series?
The Lenze i510 and i550 cabinet inverter series are the designated successor product lines for migrating legacy 8200 series installations.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.