Lenze E82EV402_4C 8200 Vector Frequency Inverter 4 kW / 5.5 HP

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze E82EV402_4C is a 4.0 kW (5.5 HP) frequency inverter from the 8200 vector series, designed for speed and torque regulation of standard three-phase asynchronous motors. Operating on a three-phase AC supply from 320 V AC to 528 V AC across 45 to 65 Hz, this IP20-rated variable frequency drive delivers a rated output current of 9.5 A at 400 V AC and can support short-term peak overloads up to 14.3 A for 60 seconds. The drive provides an output frequency range from 0 to 480 Hz using linear V/f, square-law V/f, or Sensorless Vector Control (SLVC) modes, making it suitable for dynamic industrial equipment including material handling conveyors, industrial pumps, fans, and packaging systems.
To integrate into existing control systems, the base unit features a modular design with a dedicated slot for plug-in function modules (FIF), accommodating options such as Standard I/O (E82ZAFSC), CANopen (E82ZAFCC), or PROFIBUS DP (E82ZAFPC). Integrated DC bus terminals support dynamic braking chopper connection and energy sharing across shared DC links. Commissioning a replacement unit requires restoring the parameter configuration, as up to four internal parameter sets can be stored on the drive. Parameter transfer is performed using either the Keypad XT E82ZBC operator panel or Global Drive Control (GDC) PC software. ABC Industrial Parts can support maintenance teams with parameter extraction and replacement drive preparation to minimize machinery downtime.
Comprehensive visual and system diagnostics assist in rapid fault identification on the factory floor. A dual-color Ready / Fault LED on the front face reflects real-time status, distinguishing between drive enable, inhibit, warning, and fault states. Detailed operating data and a fault history buffer can be accessed via parameter C0183 and parameter C0161. When confronting persistent overcurrent or hardware memory errors, internal driver or component failures cannot be serviced in the field; installing a fully tested replacement drive through ABC Industrial Parts provides an effective solution to restore production.
Technical Specifications
| Manufacturer | Lenze |
| Part Number | E82EV402_4C |
| Model / Type | 8200 vector 4 kW |
| Component Type | Frequency Inverter |
| Rated Power (kW) | 4.0 kW |
| Rated Power (HP) | 5.5 hp |
| Supply Voltage Range | 320 - 528 V AC |
| Mains Frequency | 45 - 65 Hz |
| Rated Output Current | 9.5 A |
| Maximum Output Current (60s) | 14.3 A |
| Output Frequency Range | 0 - 480 Hz |
| Switching Frequency | 8 kHz |
| Control Method | Sensorless Vector Control (SLVC), V/f linear, V/f square-law |
| Power Loss | 150 W |
| Protection Rating | IP20 |
Programming and Configuration
The Lenze E82EV402_4C frequency inverter utilizes parameter-based management supporting up to four independent internal parameter sets. This feature allows different operating profiles to be saved directly on the drive and switched during machine setup. Software configuration is conducted through Lenze Global Drive Control (GDC) software version 4.x or higher, connected via appropriate communication adapters.
For direct manual parameter adjustment and status monitoring, the optional Keypad XT E82ZBC operator module plugs directly into the drive interface. Parameter cloning can be performed using the Keypad XT or GDC software to read out existing settings from a functioning or donor unit and download them to a replacement drive. Restoring factory settings can be performed by setting parameter C0002 to 1 followed by a power cycle.
Communication and System Integration
System integration for the E82EV402_4C is achieved via interchangeable plug-in function modules (FIF) installed into the drive's dedicated front expansion slot. Network options include standard I/O modules (E82ZAFSC), CANopen interface modules (E82ZAFCC), PROFIBUS DP interface modules (E82ZAFPC), DeviceNet modules (E82ZAFDC), and INTERBUS modules (E82ZAFIC).
In addition to fieldbus interface slots, the unit includes integrated DC bus terminals (+UG, -UG). These connections allow multiple drives to share a common DC link for regenerative energy balancing or connection to external dynamic braking choppers and resistors during high-inertia braking operations.
Diagnostics and Status Indication
Diagnostic evaluation on the drive is supported through hardware status indication and software monitoring tools. Parameter C0183 displays the current operational state in real time, while parameter C0161 maintains a historic fault memory buffer for recording previous trip events and troubleshooting intermittent issues.
A dual-color LED on the front panel provides direct status feedback without requiring external diagnostics software. The combination of green and red illumination states signals operational readiness, active enable, system warnings, or active trip faults.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Ready / Fault LED | Green / Red - Green flashing: Drive ready/inhibit | Green solid: Drive enabled/operating | Red flashing: Warning active | Red solid: Fault/TRIP active | Indicates overall operating status, readiness, warnings, or fault conditions |
Replacement and Spare Part Considerations
When replacing an existing Lenze E82EV402_4C drive, verify that the physical function module (e.g., E82ZAFSC, E82ZAFCC, or E82ZAFPC) is transferred from the old drive or equipped identically on the replacement unit. Ensure node addresses, DIP switches, and bus termination resistors on the function module match the original installation.
Because a new or spare drive contains default factory parameters, running the drive without transferring the application parameters can result in improper control or fieldbus errors. Parameter sets should be cloned using the Keypad XT E82ZBC or GDC software v4.x+. When upgrading control panels to current technology, the Lenze i550 cabinet inverter (model i550-C4.0/400-3) represents the official migration path.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Overcurrent during acceleration | Output current exceeded overcurrent threshold during motor acceleration | Acceleration time set too short; Short circuit in motor cable; Ground fault in motor or wiring; Incorrect motor parameterization | Check motor wiring and insulation; Increase acceleration time (C0012); Verify motor data settings; If fault persists with disconnected motor, internal hardware driver failure requires unit repair |
| OC2 | Overcurrent during deceleration | Output current exceeded threshold during motor braking/deceleration | Deceleration time set too short; High load inertia without braking resistor | Increase deceleration time (C0013); Install brake chopper / braking resistor; Check motor cable |
| OC5 | Overcurrent during constant speed | Output current exceeded overcurrent limit during steady state operation | Sudden load impulse; Mechanical jam or blockage; Motor overload | Check mechanical load for blockage; Check motor sizing and V/f boost setting |
| OU | Overvoltage DC link | DC bus voltage exceeded upper limit threshold (~770 V DC) | Excessive regenerative energy from motor during deceleration; Mains voltage input too high; Deceleration time too short | Extend deceleration time (C0013); Enable voltage controller (Vmax controller); Connect dynamic braking module/resistor; Check mains supply voltage |
| LU | Undervoltage DC link | DC bus voltage fell below lower limit threshold (~370 V DC) | Mains supply voltage too low; Phase failure in AC mains power supply; Mains voltage dip; Power interruption | Check mains voltage across all 3 phases; Check mains fuses and supply wiring |
| OH | Heatsink overtemperature | Heatsink temperature exceeded permissible maximum operating limit (>85°C) | Cooling fan failed or clogged; Excessive ambient temperature; Insufficient cabinet ventilation / airflow clearance; Continuous high load | Clean heatsink cooling fins; Ensure ambient temperature <45°C; Check fan operation; Ensure minimum mounting clearances top/bottom |
| OH4 | Motor thermal overload (I2t) | Calculated thermal load of motor exceeded limit | Motor operated at low speed under high torque for long period without forced ventilation; Continuous load above rated current | Allow motor to cool down; Check motor load; Use external forced-cooling fan on motor if operating at low speeds |
| OH7 | Motor temperature sensor TRIP | Motor PTC / thermal contact evaluation triggered | Motor thermal switch tripped due to overheating | Check motor cooling, ventilation, and operating load; Inspect PTC sensor wiring to function module terminals |
| CE0 | Communication failure | Communication interruption on System Bus (CAN) or fieldbus interface module | Bus cable disconnected; Cable shielding/grounding issue; Fieldbus master stopped or timed out; Wrong node address or baud rate | Check fieldbus cable connections and line termination resistors; Verify baud rate and station address settings in parameter list |
| EE0 | EEPROM memory fault | Internal parameter memory read/write error | Data corruption in non-volatile memory due to power interruption during write operation; Hardware memory failure | Reload factory default parameters (C0002 = 1); Power cycle unit; Internal board failure requires service/repair if error recurs |
| H10 | Heatsink temperature sensor fault | Internal temperature sensor defect or broken circuit | Internal temperature measurement sensor hardware damaged | Internal hardware fault — requires returning the unit for repair |
| P03 | Mains phase failure | Failure detected in one of the input AC mains phases | Blown supply fuse; Loose wire connection on AC input side | Inspect line fuses and input terminals L1, L2, L3 |
| NMAX | Speed threshold exceeded | Motor speed exceeded max configured speed threshold | Overhauling load; Incorrect motor control tuning | Check load and speed limit settings in parameters |
Frequently Asked Questions
What software is needed to configure the Lenze E82EV402_4C?
The drive is configured using Lenze Global Drive Control (GDC) PC software version 4.x or higher, or directly using the optional Keypad XT E82ZBC display module.
How do I transfer parameters from a failed drive to a spare unit?
Parameters can be copied using the Keypad XT E82ZBC operator panel by reading out the parameter set from the original drive and writing it to the spare. Alternatively, parameters can be saved and uploaded using Global Drive Control (GDC) software.
Which fieldbus communication options are supported?
Communication interfaces are determined by the installed plug-in function module (FIF). Supported modules include Standard I/O (E82ZAFSC), CANopen (E82ZAFCC), PROFIBUS DP (E82ZAFPC), DeviceNet (E82ZAFDC), and INTERBUS (E82ZAFIC).
What does a solid red status LED indicate on the front panel?
A solid red LED indicates an active TRIP fault condition. The specific error code causing the trip can be read via parameter C0161 fault history or using the Keypad XT module.
What modern drive serves as a direct upgrade path for the E82EV402_4C?
The recommended modern successor for control cabinet redesigns is the Lenze i550 cabinet inverter model i550-C4.0/400-3.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.
Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.