Lenze E84AVSCE2234VB0 8400 Stateline C 22 kW Frequency Inverter

New 
On request
Refurbished   
On request
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: 8400 Inverters | Series: 8400 Stateline C

The Lenze E84AVSCE2234VB0 is a 22 kW frequency inverter from the 8400 Stateline C series designed for precise speed and torque control of three-phase AC motors across automated processing lines, material handling systems, pumps, and fans. Designed for cabinet installation with an IP20 protection rating, this drive operates on a 3-phase supply voltage of 400 V or 500 V AC (operating across a 320 V to 550 V AC supply range) and delivers a rated output current of 47 A at 400 V or 37.6 A at 500 V. Output frequencies range from 0 to 599 Hz with selectable motor control methods, including linear or square-law V/f characteristic control, Sensorless Vector Control (SLVC), and Servo VFC with encoder feedback. Built-in Safe Torque Off (STO) functional safety technology permits reliable safety circuit integration directly within the inverter, eliminating the need for redundant external motor contactors.

For machine control integration, the drive is equipped with 8 digital inputs, 4 digital outputs, 2 analog inputs, and 2 analog outputs alongside an onboard CANopen system bus interface. An integrated fieldbus option slot supports optional communication modules including PROFINET (E84AYCER), PROFIBUS-DP (E84AYCPM), EtherCAT (E84AYCET), and EtherNet/IP (E84AYCEO). Commissioning and replacing a drive in service is streamlined through Lenze's pluggable Memory Module architecture, which stores complete parameter configurations directly on a removable chip for rapid transfer without requiring a PC or engineering software. Parameterization and manual control can also be conducted using the Keypad X400 (EZAEBK1001), a USB Diagnostic Adapter (EWM8400BASE), or Lenze EASY Starter and EASY Engineer software frameworks. ABC Industrial Parts can assist maintenance teams with pre-configured replacement units or parameter transfer support.

Real-time drive status is indicated on the front panel by four status LEDs: DRIVE READY, DRIVE ERROR, CAN RUN, and CAN ERR. Advanced troubleshooting and historical error logs are accessible through the Keypad X400 or via EASY Starter software. When commissioning or diagnosing operational issues, technicians should first verify three-phase line voltage, output motor cabling, earth isolation, and 24 V logic signals on the STO safety inputs. Diagnostic codes address operational conditions such as DC-bus overvoltage, motor overtemperature, or mains supply dips, whereas internal power section failure or ASIC self-test errors indicate hardware-level degradation. When internal hardware defects prevent normal drive operation, ABC Industrial Parts offers tested exchange units and professional repair services to minimize production downtime.

Technical Specifications

ManufacturerLenze
Part NumberE84AVSCE2234VB0
Model / Type8400 Stateline C
Component TypeFrequency Inverter
Rated Power22 kW
Supply Voltage3x 400 / 500 V AC
Supply Voltage Range320 - 550 V AC
Rated Output Current (400V)47 A
Rated Output Current (500V)37.6 A
Output Frequency Range0 - 599 Hz
Switching Frequency4 kHz
Control MethodV/f, SLVC, Servo VFC
Digital Inputs / Outputs8 Inputs / 4 Outputs
Analog Inputs / Outputs2 Inputs / 2 Outputs
Ingress Protection RatingIP20
Functional SafetySafe Torque Off (STO)

Programming and Configuration

Parameter settings and operational configurations for the Lenze E84AVSCE2234VB0 are managed through the Lenze EASY Starter or EASY Engineer software suites. Direct PC connections are established via the USB Diagnostic Adapter (EWM8400BASE) or through an installed fieldbus network module. These software environments allow technicians to configure motor nameplate data, acceleration and deceleration ramps, switching frequencies (rated at 4 kHz), input/output function mapping, and control algorithms ranging from simple V/f curves to advanced Servo VFC vector control.

The inverter utilizes a pluggable Lenze Memory Module as its central hardware parameter storage medium. All drive parameters and operational profiles reside directly on this removable non-volatile chip. During device replacement, the Memory Module can be physically moved from a non-functioning drive into a replacement unit, enabling full parameter restoration without requiring software tools, PC connections, or re-commissioning work. Local adjustments and real-time parameter editing can also be performed directly at the machine using the optional Keypad X400 (EZAEBK1001).

Communication and System Integration

The Lenze E84AVSCE2234VB0 features an onboard CANopen system bus interface for networking drives within CAN-based control architectures. The native CANopen connectivity supports real-time velocity control, control commands, parameter adjustment, and cyclic feedback polling between distributed frequency inverters and a master PLC.

To accommodate broader fieldbus architectures, the drive includes a dedicated option slot on the front control section. Pluggable communication modules allow direct integration into PROFINET (E84AYCER), PROFIBUS-DP (E84AYCPM), EtherCAT (E84AYCET), and EtherNet/IP (E84AYCEO) networks. This modular expansion capability allows the drive to integrate easily into diverse industrial control systems, including material handling, automotive manufacturing, and process control applications.

Diagnostics and Status Indication

Front panel status LEDs provide visual indication of drive operational state and system bus status. The DRIVE READY LED illuminates solid green when main power is applied and the inverter is prepared for enable commands, while the DRIVE ERROR LED lights solid or flashes red when an operational fault occurs. Communication status across the onboard system bus is displayed via the green CAN RUN LED and red CAN ERR LED.

In addition to LED indicators, full diagnostic status, internal variable values, and error logs are accessible through the Keypad X400 display module or via Lenze EASY Starter software using the USB Diagnostic Adapter (EWM8400BASE). Real-time diagnostic monitoring enables maintenance personnel to check DC-bus voltage levels, heatsink temperature, motor loading (I2t calculation), and Safe Torque Off (STO) input logic status during operation.

Status LED Indicators

LEDColor/StatusMeaning
DRIVE READYGreen - SolidInverter is powered and ready for operation
DRIVE ERRORRed - Solid / FlashingInverter fault or error state detected
CAN RUNGreen - Solid / FlashingCANopen system bus active state
CAN ERRRed - Solid / FlashingCANopen communication error detected

Replacement and Spare Part Considerations

When selecting a replacement for a failed Lenze E84AVSCE2234VB0 inverter, ensure that the part number and power rating (22 kW, 400/500 V AC) match the existing unit exactly. Matching model specifications guarantees identical physical dimensions for cabinet mounting, correct terminal block sizing for power wiring, and full compatibility with installed option modules.

To transfer parameters to a new drive, extract the pluggable Lenze Memory Module from the defective unit and insert it securely into the replacement drive prior to powering up. If the original memory module is undamaged, the replacement inverter will start up with identical motor settings, digital/analog I/O configurations, and fieldbus communication parameters. If the memory module is missing or corrupt, parameter sets must be reloaded using Lenze EASY Starter and a USB Diagnostic Adapter (EWM8400BASE).

Before resuming machine operation, verify that 24 V logic signals are properly applied to the Safe Torque Off (STO) inputs. If optional communication modules (such as PROFINET or PROFIBUS-DP) are used, transfer the module to the replacement drive and verify network address settings to restore communication with the main machine controller.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
0x00110002Power section fault (OC1 / Short circuit)Short circuit or ground fault at inverter output terminals U, V, W.Short circuit in motor cable, motor winding fault, excessive ramp times.Check motor and wiring for short circuit / ground fault. Check acceleration/deceleration ramp parameters. If fault persists with motor disconnected, internal power section failure is present — return unit for repair.
0x00110003Earth fault (Ground fault)Ground leakage current detected at output phase.Insulation failure in motor cable or motor, output line capacitance too high.Measure insulation resistance of motor and cables. Inspect output wiring.
0x00110010DC-bus overvoltage (OU)DC bus voltage exceeded upper threshold level.Regenerative energy from motor during deceleration; deceleration time set too short; brake chopper non-functional or brake resistor missing/damaged.Increase deceleration time; check external brake resistor and brake chopper configuration; verify line voltage.
0x00110020DC-bus undervoltage (LU)DC bus voltage dropped below minimum threshold during operation.Mains supply failure, supply voltage phase loss, supply voltage dip.Check mains voltage and supply line connections. Inspect fuses.
0x00110030Inverter overtendency / overtemperature (OH)Heatsink temperature of inverter exceeded maximum limit.Insufficient cooling airflow, dirty heatsink, cabinet temperature too high, fan failure.Clean heatsink, ensure adequate panel ventilation, verify internal fan operation.
0x00110040Motor overtemperature (OH4 / I2t)Calculated motor thermal load (I2t) exceeded trip threshold or motor PTC thermal contact opened.Motor overload, mechanical block, motor sensor trip (PTC / thermal contact), incorrect motor settings.Check motor load, check motor thermal sensor connections, verify motor current limit settings.
0x00110050Internal hardware faultInternal control board or ASIC failure detected during internal self-test.Internal hardware defect or component failure.Internal hardware failure — power cycle device. If fault persists, the unit is not field-serviceable; replace unit or return for repair.
0x00110060Memory Module errorMemory Module missing, corrupt, or incompatible.Memory Module not plugged in securely, memory module defective, parameter set corrupt.Ensure Memory Module is firmly seated. Replace memory module or rewrite parameter set via EASY Starter.
0x00110070Safe Torque Off (STO) active / faultSafety state active or inconsistency detected on STO channel inputs.Safety circuit tripped, STO input channels out of sync, emergency stop active.Verify STO input signals (24V logic), check safety circuit and wiring.

Frequently Asked Questions

How do I transfer parameters to a replacement Lenze E84AVSCE2234VB0 drive?

Parameter transfer is accomplished by swapping the pluggable Lenze Memory Module from the original drive directly into the replacement unit. Alternatively, parameters can be backed up and downloaded using Lenze EASY Starter software via a USB Diagnostic Adapter (EWM8400BASE) or Keypad X400.

What safety functionality is integrated into the E84AVSCE2234VB0 frequency inverter?

The drive includes integrated Safe Torque Off (STO) functional safety technology, which allows the motor torque to be safely disabled in compliance with industrial safety standards without requiring external electromechanical contactors.

Which fieldbus communication protocols are supported?

The drive includes an onboard CANopen system bus interface. Optional communication modules inserted into the front option slot provide support for PROFINET (E84AYCER), PROFIBUS-DP (E84AYCPM), EtherCAT (E84AYCET), or EtherNet/IP (E84AYCEO).

What motor control modes can be configured on this inverter?

The E84AVSCE2234VB0 supports linear and square-law V/f characteristic control, Sensorless Vector Control (SLVC), and Servo VFC vector control with encoder feedback.

What action should be taken if fault code 0x00110050 occurs?

Fault code 0x00110050 indicates an internal hardware failure detected during self-test routines. First, power cycle the inverter. If the fault persists, internal control board or component damage is present, requiring the unit to be replaced or sent for repair.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.