Lenze EVF8222-E 8200 Vector 22kW Frequency Inverter

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze EVF8222-E is a 22 kW frequency inverter belonging to the 8200 vector series, engineered to deliver speed and torque regulation for 3-phase AC asynchronous motors in industrial automation systems. Operating across an input supply voltage range of 320 to 528 V AC at 45 to 65 Hz, this panel-mount drive delivers up to 47 A continuous output current and supports peak transient currents up to 70.5 A for 60 seconds. Motor control capabilities include programmable linear or quadratic V/f characteristics as well as dynamic open-loop sensorless vector control, supplying output frequencies from 0 to 480 Hz at a default 4 kHz switching frequency. Power dissipation during rated operation reaches 620 W, and built-in brake chopper terminals (+UG, -UG) allow direct connection of an external braking resistor to manage regenerative energy during fast deceleration cycles.
System connectivity relies on an integrated Function Module Interface (FIF) slot, which accepts plug-in fieldbus and expanded I/O modules to integrate the drive into broader machine controls. Commissioning a replacement unit requires transferring parameter profiles and matching fieldbus communication settings before operation. The drive contains four internal parameter sets stored within non-volatile EEPROM memory. Parameter configuration can be saved and loaded using the optional Lenze XT Keypad (E82ZBB001) or transferred via a computer connection running Lenze Global Drive Control (GDC) software. Technical guidance from ABC Industrial Parts can assist maintenance teams in verifying spare unit compatibility and preparing parameter configurations prior to installation.
Real-time operational monitoring is supported by two front-panel LED indicators: a green Ready/Operation LED indicating supply power and drive enable state, and a red Fault/TRIP LED indicating active warning or shutdown conditions. Diagnostics are expanded using the XT Keypad display to view active TRIP codes and status flags (IMP, STP, OK, TRIP) or by reviewing GDC software parameters C0183 and fault log memory C0161. Onboard non-volatile fault memory logs the last four TRIP conditions in parameters C0161 through C0164. When persistent internal faults or memory corruptions arise that cannot be cleared through field adjustments, a tested exchange unit or professional repair through ABC Industrial Parts provides a rapid path to restoring machine operation.
Technical Specifications
| Manufacturer | Lenze |
| Part Number | EVF8222-E |
| Model / Type | EVF8222-E |
| Product Family | 8200 vector |
| Component Type | Frequency Inverter |
| Rated Power | 22 kW |
| Nominal Supply Voltage | 400 V AC |
| Supply Voltage Range | 320 - 528 V AC |
| Supply Frequency | 45 - 65 Hz |
| Rated Output Current | 47 A |
| Maximum Output Current (60s) | 70.5 A |
| Output Voltage Range | 0 - 400 V AC |
| Output Frequency Range | 0 - 480 Hz |
| Default Switching Frequency | 4 kHz |
| Power Dissipation | 620 W |
| Control Method | V/f Characteristic, Sensorless Vector Control |
| Interface Slot | FIF Slot (Function Module Interface) |
Programming and Configuration
Drive configuration for the Lenze EVF8222-E frequency inverter is managed via the optional Lenze XT Keypad (E82ZBB001) or through Lenze Global Drive Control (GDC) software connected via a PC adapter interface. The basic inverter architecture incorporates four complete onboard parameter sets maintained within internal non-volatile EEPROM memory, allowing flexible drive adaptation across varying plant operating conditions.
During commissioning or replacement, essential parameters including motor rated current (C0087), acceleration ramp time (C0012), V/f boost settings, and carrier switching frequency must be calibrated to match the connected motor and mechanical load. When utilizing the XT Keypad, active parameter sets can be uploaded from an existing drive and transferred to a replacement unit. Alternatively, GDC software enables offline file creation, back-up parameter set archiving, and direct upload/download operations.
Communication and System Integration
System integration is achieved through the modular Function Module Interface (FIF) slot located on the front of the basic unit. This interface slot accommodates plug-in communication options, including the Lenze Standard I/O module (E82ZAFSC), Application I/O module (E82ZAFAC), PROFIBUS-DP module (E82ZAFPC), and CANopen module (E82ZAFCC), as well as DeviceNet, INTERBUS, and LECOM serial communication interfaces.
For fieldbus network integration, network communication status is monitored via parameter C0150. Integration into CAN system bus topologies requires precise verification of node addresses, transmission baud rates, and system bus line termination using 120-ohm resistors to eliminate communication timeouts (code CE0) or internal module interface disruption (code CE1).
Diagnostics and Status Indication
The Lenze EVF8222-E inverter incorporates localized LED indicators, keypad display status flags, and software monitoring tools for real-time status indication. Two front-mounted LEDs provide instant visual feedback regarding operational readiness and fault conditions.
Detailed status monitoring is accessible using the optional XT Keypad LCD, which displays active TRIP codes alongside operational flags including IMP (pulses inhibited), STP (stop active), OK (drive ready), and TRIP (fault condition). In software-driven diagnostics, Lenze Global Drive Control (GDC) evaluates real-time operating parameters such as parameter C0183, while internal EEPROM fault memory logs the four most recent TRIP fault codes in parameters C0161 through C0164.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Fault / TRIP | Red - Illuminated or Flashing | Active TRIP fault or warning condition present |
| Ready / Operation | Green - Illuminated or Flashing | Power supplied and inverter ready; flashing indicates normal enabled operation |
Replacement and Spare Part Considerations
When replacing an existing unit with a spare Lenze EVF8222-E frequency inverter, verifying voltage ratings (320-528 V AC) and current capacity (47 A) is required to ensure physical and electrical drop-in compatibility. Before placing a spare unit into operation, the original FIF expansion module (such as PROFIBUS E82ZAFPC or CANopen E82ZAFCC) must be uninstalled from the failed drive and securely seated into the FIF slot of the replacement basic unit.
A replacement drive does not function as a direct plug-and-run module without proper parameter configuration. Active parameter profiles must be downloaded to the spare inverter using either an XT Keypad or Lenze Global Drive Control software. When internal electronic faults prevent standard parameter transfers, specialized component-level data recovery from internal EEPROM memory can assist in extracting stored parameter sets from defective units.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Short circuit / Earth fault | Overcurrent during acceleration or continuous operation caused by short circuit at output terminals, earth fault, or motor winding damage. | Short circuit in motor cable; earth fault in motor; acceleration time set too short; motor defective. | Check motor cable for short circuits and insulation resistance to ground; check motor parameter configuration; extend acceleration time. |
| OC2 | Earth fault | Ground fault detected on inverter output terminals U, V, W. | Ground fault in motor leads or motor winding; excessive cable capacitance on long motor lines. | Check wiring insulation to earth; check motor windings; install motor filter/choke if cable length exceeds specification. |
| OC5 | Overcurrent during acceleration | Current limit exceeded during acceleration phase. | Acceleration time (C0012) set too short; high initial breakaway load; incorrect motor parameters. | Increase acceleration time; check V/f boost setting or vector control parameter setup; verify motor data. |
| OU | Overvoltage in DC bus | DC bus voltage exceeded upper limit threshold (approx. 770 V DC for 400 V units). | Excessive regenerative energy during deceleration; deceleration time set too short; brake chopper or brake resistor not connected or defective. | Increase deceleration time; install or verify external braking resistor; check brake chopper settings. |
| LU | Undervoltage in DC bus | DC bus voltage fell below lower limit threshold. | Mains supply voltage too low; phase loss on mains supply; supply voltage transient dip. | Check mains input voltage L1, L2, L3; check supply fuses and contactors. |
| OH | Heatsink overtemperature | Inverter power stage heatsink temperature exceeded maximum threshold (approx. 85-90 °C). | Ambient temperature too high; enclosure fan failed or ventilation blocked; sustained continuous overload. | Clean heatsink cooling fins; verify cooling fan operation; improve cabinet ventilation; reduce carrier/switching frequency. |
| OH4 | Motor overload (I2t thermal motor monitoring) | Calculated thermal overload of motor reached tripping threshold. | Continuous motor operation at low speed under high load without forced cooling; incorrect motor rated current parameter (C0087). | Check motor loading; verify parameter C0087 matches motor nameplate current; fit separate forced cooling fan on motor if operating continuously at low speed. |
| OH7 | Motor PTC / Thermal contact trip | Motor temperature sensor connected to input terminals T1/T2 triggered overtemperature trip. | Motor overheated; PTC thermistor circuit open; sensor cable disconnected. | Allow motor to cool down; check motor cooling and load; verify thermistor resistance and wiring. |
| CE0 | Communication error - System bus (CAN) | Interruption or timeout in CAN system bus communication. | CAN bus cable broken or shorted; missing bus termination resistor; baud rate mismatch; node address conflict. | Check CAN bus wiring and shielding; check termination resistors (120 Ohm); verify node addresses and baud rates. |
| CE1 | Communication error - Function module (FIF) | Loss of communication between inverter basic unit and plug-in function module in FIF slot. | Function module loose or improperly seated in slot; internal hardware error in module or basic unit. | Power down unit, remove and reseat function module securely; replace module if problem persists; if module replacement does not resolve, internal hardware fault — return unit for repair. |
| EER | EEPROM memory error | Data corruption detected in internal non-volatile EEPROM memory during startup or parameter saving. | Power interruption during parameter saving; memory cell failure. | Reload factory default settings (C0002 = 91); download backup parameter set; if fault recurs continuously, internal memory failure — return unit for repair. |
| H05 | Internal hardware fault | Self-test detected failure in internal microcontroller, power supply board, or gate drive circuit. | Internal component failure; power board fault. | Cycle mains input power; if error persists, internal non-field-serviceable hardware failure — replace unit or return for repair. |
| LP1 | Mains phase failure | One phase missing from incoming 3-phase AC mains supply. | Blown input fuse; loose mains supply connection; severe mains voltage imbalance. | Check all 3 input phases L1, L2, L3 at input terminals with multimeter; check supply contactor and line fuses. |
| NMAX | Maximum speed exceeded | Actual motor speed exceeded maximum allowable limit threshold. | Unstable vector control loop tuning; external mechanical driving load; incorrect encoder configuration. | Check speed controller parameters; check mechanical load for overhauling condition; check feedback device. |
| P12 | I2t load fault on braking resistor | Thermal overload threshold calculated for external braking resistor reached. | Braking duty cycle too high; resistor power rating undersized. | Increase deceleration ramp time; fit higher wattage braking resistor matching drive specs. |
Frequently Asked Questions
What tools are required to configure parameters on the Lenze EVF8222-E inverter?
Parameter configuration requires either an optional Lenze XT Keypad (E82ZBB001) attached directly to the unit or a PC running Lenze Global Drive Control (GDC) software connected via an adapter interface.
Can a replacement EVF8222-E drive run without parameter programming?
No, a replacement unit must be loaded with the parameter settings from the original drive—including motor current parameters, acceleration ramps, and fieldbus profiles—before it can operate in a machine.
How are fieldbus modules attached to the EVF8222-E drive?
Fieldbus adapters, such as PROFIBUS-DP (E82ZAFPC) or CANopen (E82ZAFCC), plug directly into the Function Module Interface (FIF) expansion slot located on the front panel of the drive.
What do the front-panel status LEDs indicate on the EVF8222-E?
The green Ready/Operation LED indicates incoming mains power and inverter readiness (flashing when operational), while the red Fault/TRIP LED illuminates or flashes when an active fault or warning trip is present.
How does the inverter store parameter sets and fault history?
The drive stores up to four parameter profiles in non-volatile onboard EEPROM memory, while parameters C0161 through C0164 store a history of the last four TRIP fault codes.
What should be done if an H05 fault code is displayed?
An H05 code indicates an internal hardware failure in the power board, gate drive, or microcontroller. Power to the unit should be cycled; if the error persists, the fault is internal and non-field-serviceable, requiring drive repair or replacement.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.