Lenze 13057309 EMF2133IB PROFIBUS-DP Communication Module

New 
On request
Refurbished   
2 available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: 8200 vector / 9300 Series | Series: 8200 vector / 9300 Series

The Lenze 13057309 EMF2133IB is a PROFIBUS-DP fieldbus communication module designed for Lenze 8200 vector frequency inverters and Lenze 9300 series servo drives. Functioning as a DP-V0 slave interface card, this plug-in module enables direct integration of host drives into centralized PLC architectures. Network connection is made through a standard 9-pin Sub-D female RS-485 port. Built-in galvanic isolation protects host drive electronics from ground loops and severe electrical interference across industrial applications such as packaging, material handling, automotive, textile, and printing lines.

Commissioning a replacement unit requires aligning the hardware address configuration with the existing fieldbus layout. The EMF2133IB features onboard DIP switches S1 and S2 to assign network station addresses from 1 to 126, while offering automatic baud rate detection across transmission speeds ranging from 9.6 kbit/s up to 12 Mbit/s. Network integration and parameter access are managed using standard GSD files alongside Lenze Global Drive Control (GDC) software, with drive parameter sets backed up in the non-volatile EEPROM memory of the host drive. Prior to installing or removing a module, power to the host drive must be completely isolated. ABC Industrial Parts provides tested replacement units to support rapid deployment during drive system maintenance.

Visual status monitoring is handled via dedicated STAT and BUS LEDs located on the front cover. A solid green STAT LED confirms operational supply power and healthy module functionality, whereas an unlit STAT LED signals a missing power supply or internal module failure. The red BUS LED illuminates solid during active baud rate searches or fieldbus communication errors, turning off during regular cyclic data exchange. Built-in diagnostic fault codes CE0 through CE3 help differentiate between physical RS-485 cabling problems, master PLC interruption, and internal interface failures. If re-seating the card and power cycling fails to clear internal board faults, sourcing a tested exchange unit through ABC Industrial Parts ensures a reliable path back to production.

Technical Specifications

ManufacturerLenze
Part Number13057309
Model/TypeEMF2133IB
Component TypeCommunication Module
Compatible Drive FamiliesLenze 8200 vector, Lenze 9300 Series
Communication ProtocolPROFIBUS-DP (DP-V0 Slave)
Physical LayerRS-485
Connector Type9-Pin Sub-D Female
Minimum Baud Rate9.6 kbit/s
Maximum Baud Rate12 Mbit/s
Baud Rate AdjustmentAutomatic
Bus Address Range1 - 126 (DIP switch selectable)
Galvanic IsolationIntegrated

Programming and Configuration

Hardware node addressing for the Lenze 13057309 EMF2133IB is set directly on the card using dual onboard DIP switches S1 and S2. This allows technicians to select network station addresses within the 1 to 126 range without connecting external software tools during initial hardware setup.

System engineering and parameter management are supported using standard GSD files in combination with Lenze Global Drive Control (GDC) software. Network setup and drive control parameters are saved directly in the non-volatile EEPROM memory of the host drive controller, ensuring configuration data remains safe during system maintenance.

Communication and System Integration

The EMF2133IB acts as a high-speed PROFIBUS-DP slave interface supporting DP-V0 cyclic data exchange over standard RS-485 network layouts. Interfacing with higher-level masters such as Siemens S7 PLC controllers or centralized automation systems, the card transfers process commands and feedback signals efficiently.

Physical connection is established via a standard 9-pin Sub-D female RS-485 connector. The module automatically matches the transmission speed of the network across a wide operating bandwidth from 9.6 kbit/s to 12 Mbit/s. Built-in galvanic isolation protects internal drive circuits against stray potential differences and electrical interference across fieldbus segments.

Diagnostics and Status Indication

Real-time diagnostic analysis is available via front-panel LED indicators STAT and BUS. Detailed error conditions and cyclic parameter states can also be monitored through system bus diagnostic parameters in host drive controllers or via Lenze Global Drive Control (GDC) software.

Status LED Indicators

LEDColor/StatusMeaning
STATGreen - Solid / OffSolid green indicates normal operation and supply power present. Off indicates no power or internal module failure requiring unit replacement.
BUSRed - Solid / OffSolid red indicates PROFIBUS communication error or active baud rate search. Off indicates normal cyclic data exchange.

Replacement and Spare Part Considerations

When swapping out a faulty communication module, verify that the host drive is completely powered down before removing or inserting the card to avoid pin damage or electrical discharge. Ensure the module is firmly seated into its card slot before restoring power.

Always verify that the onboard DIP switches S1 and S2 on the replacement EMF2133IB match the station address configuration of the unit being replaced. Because parameter settings reside in the host drive's EEPROM, replacing the communication card alone generally does not require re-parameterizing the main drive.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
CE0Communication Error 0 (BUS OFF)PROFIBUS DP watchdog time elapsed or physical bus connection lost.Damaged fieldbus cable, improper bus termination, disconnected connector, master PLC stopped or incorrect bus address.Check physical cable connections, check bus termination resistors at segment ends, verify PLC master state, verify module address DIP switch configuration.
CE1Communication Error 1 (Module Interface Error)Process data transfer failure between the communication module and host drive controller.Module loose in slot, bent interface pins, severe electrical noise interference, internal board fault.Power off drive, re-seat EMF2133IB module firmly into host slot. If fault persists, replace the communication module (internal hardware failure).
CE2Communication Error 2 (Parameter Channel Timeout)Time-out during parameter access over PROFIBUS parameter channel.Invalid parameter request from master, excessive bus cycle time, network overload.Check PLC parameter access program, verify requested parameter index exists in host drive parameter database.
CE3Communication Error 3 (Module Initialization Error)Communication module failed internal self-test or initialization with host controller.Firmware incompatibility between drive and module, damaged module internal components.Internal hardware fault or firmware issue. Re-seat module and power cycle. Replace communication module if condition persists.

Frequently Asked Questions

How is the PROFIBUS station address configured on the EMF2133IB module?

The station address is configured using onboard DIP switches S1 and S2 located directly on the module, allowing address assignment from 1 to 126 without requiring software tools.

Does the EMF2133IB module require manual baud rate selection?

No, the module features automatic baud rate detection, matching transmission speeds from 9.6 kbit/s up to 12 Mbit/s based on the active PROFIBUS master.

Which Lenze drive series are compatible with the EMF2133IB card?

The EMF2133IB communication card is compatible with Lenze 8200 vector frequency inverters and Lenze 9300 series servo drives.

What do the STAT and BUS LEDs indicate on the front panel?

The green STAT LED indicates supply power and operational health (off indicates no power or module failure). The red BUS LED indicates a bus communication error or baud rate search when lit solid, and remains off during normal data exchange.

What steps should be taken if a CE1 interface fault occurs?

Isolate power to the host drive and re-seat the EMF2133IB module firmly in its expansion slot to eliminate loose contact or pin issues. If the fault persists after restoring power, the module has an internal hardware failure and must be replaced.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.