Lenze E82EV302_4C200 8200 Vector 3.0 kW Frequency Inverter

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze E82EV302_4C200 is a 3.0 kW frequency inverter from the 8200 Vector series, designed for variable speed control of standard three-phase AC induction motors. Operating from a 3-phase supply of 400 V AC to 480 V AC across a permissible voltage range of 320 V AC to 528 V AC, this inverter generates an adjustable output voltage up to mains level with an output frequency range of 0 Hz to 480 Hz. It delivers a rated current of 7.3 A at 400 V and 6.1 A at 480 V AC with a default switching frequency of 8 kHz. Built as a variant without an integrated EMC filter, this unit is intended for installation in control cabinets equipped with central or external filter arrangements.
System connectivity and control integration are managed via a front-mounted function module slot that accepts standard I/O (E82ZAFSC), application I/O (E82ZAFAC), or fieldbus interfaces such as CANopen (E82ZAFCC) and PROFIBUS-DP (E82ZAFPC). Putting a spare drive into operation requires transferring motor parameters and application settings stored in the internal EEPROM. Fast drive swapping is supported through the optional plug-in memory module (E82ZMS001), allowing direct parameter transfer without connecting a PC. Inverters can also be configured using an E82ZBC keypad or Lenze Global Drive Control (GDC) software, with technical support available from ABC Industrial Parts for parameter extractions and configuration backups.
Diagnostic evaluation is handled through onboard red and green status LEDs, as well as status displays on the optional E82ZBC keypad. Technicians can analyze active trips using the status word monitor (C0150) or review saved events in the GDC software fault history log (C0168). Common drive trips include overcurrent conditions (OC1, OC2, OC3), DC bus overvoltage (OU), and communication timeouts (CE0, CE1). Initial field checks should cover mains input stability, motor cable insulation, thermal PTC sensor wiring across terminals T1 and T2, and module seating. Internal electronic failures (H05) or persistent parameter errors (Pr) are not field-serviceable, making a tested replacement drive from ABC Industrial Parts the most reliable path to minimizing machine downtime.
Technical Specifications
| Rated Power | 3.0 kW |
| Supply Voltage | 3x 400 / 480 V AC |
| Supply Voltage Range | 320 - 528 V AC |
| Rated Current (400V) | 7.3 A |
| Output Current (480V) | 6.1 A |
| Output Voltage Range | 0 - Mains Voltage V AC |
| Output Frequency Range | 0 - 480 Hz |
| Default Switching Frequency | 8 kHz |
| Control Method | V/f Characteristic Control, Sensorless Vector Control, Torque Control |
Programming and Configuration
The Lenze E82EV302_4C200 utilizes non-volatile internal EEPROM memory capable of retaining two complete parameter sets. Drive commissioning and parameter adjustments can be performed using the optional E82ZBC plug-in keypad module or via a PC using Lenze Global Drive Control (GDC) software. Control parameters govern motor control modes, ramp times, thermal limits, digital input assignments, and fieldbus communication settings.
For maintenance operations, the drive supports the Lenze E82ZMS001 plug-in memory module. This module allows direct hardware cloning of saved parameter sets from one inverter to another without needing a laptop or software interface. When replacing a failed unit, swapping the memory module into the replacement drive automatically restores all machine-specific operational parameters.
Parameter management includes dedicated codes such as C0002 for restoring factory defaults, C0012 and C0013 for adjusting acceleration and deceleration times, C0018 for switching frequency adjustments, and C0075 for motor thermal model settings.
Communication and System Integration
System integration for the E82EV302_4C200 is built around a modular architecture featuring an integrated front slot for function, I/O, and fieldbus modules. Depending on application requirements, users can attach standard I/O modules (E82ZAFSC) or application I/O modules (E82ZAFAC) for local terminal control.
For network and fieldbus environments, the drive accepts various communication modules including CANopen (E82ZAFCC), PROFIBUS-DP (E82ZAFPC), DeviceNet, and INTERBUS. These modules enable real-time control, status monitoring, and parameter adjustment directly from higher-level PLCs or plant control networks.
The drive also includes dedicated onboard terminals T1 and T2 for direct connection of PTC thermistor sensors embedded in the motor windings, enabling integrated motor thermal monitoring independently of fieldbus communication.
Diagnostics and Status Indication
Visual status monitoring is provided on the front panel via dual red and green LEDs. These LEDs indicate operational readiness, active drive enable status, warning conditions, and active fault trips.
Detailed trip diagnosis and operational status monitoring can be accessed through the E82ZBC keypad display or via Global Drive Control (GDC) software. Key diagnostic parameters include parameter C0150 for real-time status word monitoring and code C0168, which maintains a history log of recent fault codes.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Status LEDs | Red / Green - Solid / Flashing | Displays inverter operating status and active fault conditions |
Replacement and Spare Part Considerations
When selecting a replacement drive for the Lenze E82EV302_4C200, pay attention to the exact model suffix. The designation '200' indicates that this model does not feature an integrated EMC filter. Installing a replacement variant with an integrated filter in an environment designed for external filtering may cause compatibility issues or improper line grounding setups.
To complete a rapid drive exchange, transfer the plug-in memory module (E82ZMS001) or plug-in fieldbus module (such as E82ZAFCC or E82ZAFPC) from the original unit to the replacement inverter. Ensure the fieldbus module is firmly seated in slot 1 before restoring system power.
If the memory module is damaged or unreadable, parameters must be reloaded from a software backup via Lenze Global Drive Control (GDC) or re-entered manually using the E82ZBC keypad module. Following parameter loading, execute an operational check of motor rotation, thermal protection settings (C0075), and network communications.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Short circuit / Earth fault | Short circuit or ground fault at output during acceleration phase | Short circuit in motor cable or motor winding, ground fault, acceleration time set too short | Check motor cable and motor insulation, verify motor wiring, increase acceleration time (C0012). If fault occurs without motor connected, internal drive short circuit requiring factory repair. |
| OC2 | Overcurrent during deceleration | Output current overload during deceleration / braking phase | Deceleration time set too short, dynamic braking overload | Increase deceleration time (C0013) or connect braking module / brake resistor. |
| OC3 | Overcurrent at constant speed / load | Output current exceeded instantaneous trip limit during steady-state operation | Sudden load impulse, motor overload, mechanical obstruction, wrong V/f setting | Check motor load and mechanical drive components, verify motor parameter settings in drive. |
| OC5 | I x t Inverter Overload | Inverter continuous overload limit exceeded (I2t overload monitoring triggered) | Drive operated above rated output current for extended duration | Reduce motor load, select larger frequency inverter capacity. |
| OU | Overvoltage DC bus | DC bus voltage exceeded maximum allowable threshold | Excessive regenerative power fed back from motor during deceleration, deceleration time too short, supply mains voltage too high | Increase deceleration time (C0013), fit braking chopper / resistor, check mains supply voltage. |
| LU | Undervoltage DC bus | DC bus voltage fell below lower trip limit | Mains supply failure, supply voltage drop, phase failure in mains feed | Check AC supply voltage, inspect fuses and mains contactors. |
| OH | Heatsink Overtemperature | Inverter heatsink temperature exceeded allowable operating limit (> 85 °C / 90 °C) | Ambient temperature too high, inadequate cooling, clogged heatsink/fan fault, switching frequency too high | Improve enclosure ventilation, clean heatsink fins, check internal fan operation, reduce switching frequency (C0018). |
| OH4 | Motor Overtemperature (PTC) | Thermal sensor input (T1, T2) detected motor overheat condition | Motor overloaded, motor cooling fan failed, thermal sensor wiring broken | Allow motor to cool down, inspect motor cooling fan, check PTC thermistor wiring and connection on T1/T2 terminals. |
| OH7 | Inverter Interior Overtemperature | Temperature inside inverter housing exceeded maximum limit | Inadequate control cabinet cooling, ambient temperature excessive | Reduce ambient temperature inside enclosure, improve enclosure airflow. |
| OH8 | I2t Motor Overload | Motor thermal model protection calculated motor overload | Continuous operation at low speed under high torque load without forced ventilation | Check motor sizing, equip motor with separate forced-cooling fan, verify C0075 / I2t settings. |
| CE0 | System Bus / CAN Communication Timeout | Communication failure or message timeout on system bus (CAN) | Bus connection broken, termination resistors missing, bus line interference | Check CAN bus wiring, shield grounding, termination, and node address settings. |
| CE1 | Automation Module Fault Slot 1 | Communication fault or timeout on fieldbus plug-in module (slot 1) | Fieldbus master stopped, cable disconnected, module improperly seated | Check fieldbus module seating, fieldbus master status, and fieldbus cabling. |
| EEr | External TRIP Signal Triggered | Fault input triggered via configured digital input | External monitoring device (e.g. pressure switch, safety circuit) opened | Check external fault condition connected to assigned digital input. |
| LP1 | Motor Phase Failure | Missing phase on inverter output detected | Motor cable disconnected, motor winding open circuit, contactor opened on output side | Check motor cables, output connections, motor windings, and motor contactor. |
| Pr | Parameter Error / Data Corrupt | Internal EEPROM checksum error or invalid parameter set detected | Power interrupted during parameter saving, corrupted EEPROM memory | Reload factory default parameters (C0002) and re-commission. If error persists after default load, hardware failure - return unit for repair. |
| H05 | Internal Hardware Fault | Internal electronic board level or microcontroller defect detected | Power board error, internal voltage rail failure, hardware fault | Internal hardware fault — non field-serviceable, contact Lenze service or return drive for repair/replacement. |
| NMAX | Maximum Speed Exceeded | Actual motor speed exceeded maximum configured threshold (C0011) | Overhauling load driving motor, runaway feedback condition | Check load mechanics, braking circuit, and speed limit parameters. |
Frequently Asked Questions
Does the Lenze E82EV302_4C200 inverter include an internal EMC filter?
No, the E82EV302_4C200 variant is manufactured without an integrated EMC filter. It is designed for panel installations using external or central line filters.
How do I transfer parameters to a replacement E82EV302_4C200 inverter?
Parameters can be transferred without a PC by swapping the E82ZMS001 plug-in memory module from the original drive into the replacement unit. Alternatively, parameter sets can be uploaded and downloaded using Lenze Global Drive Control (GDC) software or an E82ZBC keypad module.
Which fieldbus modules fit the front slot of this drive?
The integrated front module slot supports various plug-in interfaces, including CANopen (E82ZAFCC), PROFIBUS-DP (E82ZAFPC), DeviceNet, INTERBUS, and standard or application I/O modules (E82ZAFSC / E82ZAFAC).
What does a fault code H05 indicate on the drive display?
Fault code H05 indicates an internal hardware defect, such as a power board or microcontroller rail failure. This trip cannot be serviced in the field and requires drive repair or complete replacement.
Where are motor thermal sensors connected to the inverter?
Motor PTC thermistors are connected directly to dedicated control terminals T1 and T2 on the drive, allowing direct motor overtemperature monitoring (fault code OH4).
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.