Product Information

Product Family: 8200 vector / 8200 motec | Series: 8200

The Lenze E82ZAFD is a plug-in CANopen function module engineered for Lenze 8200 vector and 8200 motec frequency inverters. Designed to fit directly into the standardized Function Interface (FIF) slot of the drive, this communication module establishes fieldbus connectivity between the host inverter and centralized automation networks. Power for the module is supplied internally at 24 V DC through the drive interface slot, eliminating the need for external power supplies or additional panel space.

Physical bus connection is made via a 5-pole pluggable screw terminal. Operating under the standard CANopen CiA DS301 profile, the module supports Process Data Objects (PDO) for fast cyclic control and Service Data Objects (SDO) for parameter access across the bus. When commissioning a spare module, network configuration is performed using front-accessible hardware DIP switches that define node addressing from 1 to 63 and transmission speeds from 10 to 1000 kbit/s. Drive parameters can be fine-tuned or verified using Lenze Global Drive Control (GDC) software or an optional E82ZBC Keypad Module, with ABC Industrial Parts available to assist with replacement verification and unit sourcing.

Real-time operational monitoring is facilitated by two front-panel status LEDs: a green CAN-RUN indicator displaying operational states and a red CAN-ERR indicator signaling network errors, bus-off conditions, or guarding faults. Further diagnostics are accessible through host drive parameters C0091 and C0150 through C0154, displaying error conditions such as CAN timeouts (CE0), bus-off faults (CE1), receive buffer overflows (CE2), and node guarding events (CE3). Basic troubleshooting includes checking fieldbus wiring, verifying the 120 ohm line termination resistors, and checking DIP switch address settings. If internal communication error CE4 occurs, power down the drive and re-seat the module in the FIF slot; persistent internal hardware faults are not field-serviceable, making unit replacement or tested exchange units through ABC Industrial Parts the ideal path back to operation.

Technical Specifications

ManufacturerLenze
Part NumberE82ZAFD
Model / TypeFunction Module CANopen
Component TypeCommunication Module
Product Family8200 vector / 8200 motec
Supply Voltage24 V DC (via host drive FIF interface)
Communication ProtocolCANopen (CiA DS301)
Maximum Network Nodes63 (Node ID 1 - 63)
Baud Rate10 - 1000 kbit/s
Host InterfaceLenze Function Interface (FIF)
Connector Type5-pole pluggable screw terminal

Programming and Configuration

Parameterization of the Lenze E82ZAFD communication module is performed either using Lenze Global Drive Control (GDC) software connected to the host drive or through the plug-in Lenze E82ZBC Keypad Module. Hardware network settings, including node addressing (1 through 63) and baud rate selection (10 to 1000 kbit/s), are configured directly using manual DIP switches located on the front of the module.

In addition to manual DIP switch settings, host inverter parameters C0091 and C0150 through C0154 enable access to network state monitoring and error tracking. Advanced network response times, such as Node Guarding and Heartbeat monitoring intervals, are adjusted via parameters C0352 and C0353. Alignment between these parameter settings and the central CANopen PLC configuration ensures consistent control system performance.

Communication and System Integration

The E82ZAFD module integrates Lenze 8200 vector and 8200 motec variable frequency drives into CANopen networks complying with the CiA DS301 profile. Equipped with a 5-pole pluggable screw terminal, the module provides a standard physical connection interface for fieldbus topologies across factory automation systems.

Full support for Process Data Objects (PDO) enables high-speed cyclic exchange of drive control words, setpoints, and operational status feedback. Service Data Objects (SDO) permit complete access to drive parameters over the network. With configurable transmission speeds up to 1000 kbit/s and addressable node capacity up to 63 subscribers, the module enables efficient distributed drive control.

Diagnostics and Status Indication

Visual operational feedback is provided via two status LEDs on the front of the module. The green CAN-RUN LED indicates CANopen node status across Operational, Pre-Operational, and Stopped states through solid and flashing conditions. The red CAN-ERR LED illuminates or flashes to indicate bus errors, bus-off conditions, or guarding time-outs.

Detailed troubleshooting is supported through host drive diagnostic parameters C0091 and C0150–C0154. In the event of a fault condition, the module can also transmit standard CANopen emergency messages across the fieldbus to notify the master controller.

Status LED Indicators

LEDColor/StatusMeaning
CAN-RUNGreen - Solid / FlashingIndicates CANopen operational status (Operational, Pre-Operational, Stopped)
CAN-ERRRed - Solid / FlashingIndicates CANopen bus error state (Bus Off, Error Warning, Node Guarding / Life Time Event)

Replacement and Spare Part Considerations

Before replacing an E82ZAFD module, disconnect all primary supply power from the host 8200 vector or 8200 motec inverter. Verify that the hardware DIP switches on the new module are positioned to match the Node ID and baud rate settings of the unit being replaced prior to inserting the module into the FIF slot.

Following physical installation, reconnect the 5-pole pluggable terminal block and ensure proper bus termination is present. If the drive reports error CE4 upon power-up, ensure that the module is fully seated in the interface slot and that terminal contacts are clean.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
CE0Communication Error 0 (CAN Time-out)Communication failure or time-out on CANopen bus (PDO time-out / bus off).Bus line disconnected, incorrect wiring, incorrect baud rate, master stopped, terminating resistors missing.Check CAN cabling and 120 ohm terminating resistors. Verify baud rate setting and host controller status.
CE1CAN bus-off stateThe CAN controller on the module entered the Bus-Off state due to excessive transmission or reception error frames.Severe EMI/RFI noise, faulty cable shield connection, baud rate mismatch, wrong node ID.Check grounding and shielding of bus lines. Verify baud rate settings on all node devices. Restart module/inverter.
CE2CAN receive buffer overflowData received faster than the host inverter internal task processing capacity.Excessive PDO transmission rates or unhandled burst messages on the bus.Increase PDO transmission cycle time / inhibit time from CANopen master controller.
CE3CAN Guarding Error / Heartbeat ErrorNode guarding or heartbeat monitoring triggered a life fault event.Master stopped polling node within Guard Time, or heartbeat producer failed.Verify CANopen master state and configured Node Guarding / Heartbeat parameters (C0352/C0353).
CE4CAN internal communication errorInternal communication fault between E82ZAFD function module and host inverter CPU.Bad electrical connection at FIF interface slot, damaged connector pins, internal module hardware failure.Turn off power, remove and re-seat E82ZAFD module in FIF slot. If error persists, replace E82ZAFD module.

Frequently Asked Questions

How is the Lenze E82ZAFD communication module powered?

The module receives its required 24 V DC power directly from the host drive through the standard Function Interface (FIF) slot, eliminating the need for external power wiring.

How are the node address and baud rate configured on the E82ZAFD?

Node addresses from 1 to 63 and transmission speeds from 10 to 1000 kbit/s are configured using hardware DIP switches located on the front of the module.

Which Lenze drive series accept the E82ZAFD module?

The E82ZAFD function module is designed for direct plug-in compatibility with Lenze 8200 vector and Lenze 8200 motec frequency inverters.

What do the CAN-RUN and CAN-ERR LEDs signal during operation?

The green CAN-RUN LED indicates operational states (Operational, Pre-Operational, Stopped), while the red CAN-ERR LED signals bus error conditions, bus-off states, or guarding faults.

What tools can be used for configuration and diagnostic parameter access?

Drive parameters and network diagnostics can be accessed using Lenze Global Drive Control (GDC) software or the plug-in Lenze E82ZBC Keypad Module.

What causes fault code CE4 on a host drive?

Fault code CE4 indicates an internal communication failure between the module and host drive CPU, typically caused by a poor physical connection at the FIF slot or internal hardware damage.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.