Lenze E82EV371_2B 8200 Vector Frequency Inverter 0.37 kW 230V

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze E82EV371_2B is a compact 0.37 kW frequency inverter from the 8200 Vector series, designed for controlled motor speed regulation of three-phase AC asynchronous motors. Operating on a single-phase or three-phase input supply voltage ranging from 180 V to 264 V AC, this drive delivers a continuous output current of 2.4 A and a maximum peak output current of 3.6 A for 60 seconds, representing a 150% overload capacity. Built into a book-style housing for cabinet installation, the drive incorporates an integrated Class A/B RFI radio interference filter to satisfy electromagnetic compatibility requirements and simplify panel wiring. Control functionality supports both linear or quadratic V/f characteristic curves and sensorless vector control with an output frequency range from 0 Hz up to 480 Hz.
Constructed with a modular system architecture, the E82EV371_2B power unit features plug-in slots for optional function and communication modules, allowing connection to systems using CANopen (E82ZAFC), PROFIBUS-DP (E82ZAFP), or LECOM RS-232/RS-485 interfaces. Commissioning a replacement unit requires configuring the drive parameters to match the operational motor and machine profile, as a bare replacement drive will not operate out of the box. Internal non-volatile EEPROM memory stores up to four complete parameter configuration sets, which can be programmed or uploaded using the optional XT Keypad E82ZBC or Lenze Global Drive Control (GDC) software via a PC interface. Where parameter extraction from a faulty board is achievable, ABC Industrial Parts can assist in transferring stored parameter sets to a replacement drive to reduce setup time.
Operational monitoring and troubleshooting on the E82EV371_2B are provided by front-panel status LEDs and digital diagnostic tools. A solid green operating state LED indicates normal ready or running status, while a flashing green LED indicates an active controller inhibit condition; a flashing red LED signals an active TRIP fault. Detailed error diagnostics can be viewed through the XT Keypad display or the real-time diagnostic monitor and fault history memory log in the GDC software. First-line field checks should verify mains supply voltage across terminals, motor insulation, output wiring, and the physical seating of communication option modules. Internal microcontroller or power section hardware failures, such as fault codes H10 or H11, cannot be serviced in the field, and procuring a fully tested exchange drive through ABC Industrial Parts provides a direct route to restoring production.
Technical Specifications
| Rated Power Output | 0.37 kW |
| Supply Voltage Range | 180 - 264 V AC |
| Mains Rated Input Current | 5.0 A |
| Continuous Output Current | 2.4 A |
| Maximum Output Current (60s) | 3.6 A |
| Output Frequency Range | 0 - 480 Hz |
| Default Switching Frequency | 8 kHz |
| Control Mode | V/f Characteristic, Sensorless Vector Control |
| Integrated Filter | Class A/B RFI Filter |
| Enclosure Design | Book-Style Cabinet Mounting |
Programming and Configuration
The Lenze E82EV371_2B inverter relies on parameter-driven configuration to manage motor acceleration, deceleration, thermal protection, and operating modes. Parameters can be modified directly at the drive using the plug-in XT Keypad E82ZBC or through a computer running Lenze Global Drive Control (GDC) software connected via a PC adapter. Key timing parameters include acceleration ramp time (C0012) and deceleration ramp time (C0013), which control motor dynamic response and help prevent overcurrent or overvoltage tripping during speed transitions.
The drive features internal non-volatile EEPROM memory capable of holding up to four independent parameter sets. This multi-configuration storage allows users to maintain different operating profiles or quickly restore baseline parameters. In cases of configuration corruption or parameter transfer failure, resetting the drive to factory default settings via parameter C0002 allows technicians to establish a clean configuration baseline before re-entering application specifications.
Communication and System Integration
The E82EV371_2B frequency inverter integrates into automated networks through pluggable communication modules inserted into dedicated expansion slots on the drive chassis. Depending on system requirements, the drive can be equipped with a CANopen module (E82ZAFC), a PROFIBUS-DP module (E82ZAFP), or LECOM modules for RS-232 and RS-485 serial communications. This modular interface approach keeps base hardware compact while ensuring compatibility with standard industrial fieldbus architectures.
When connected to a network, the drive receives speed setpoints, start/stop commands, and controller inhibit signals remotely while transmitting operational status, output current, and TRIP messages back to the central controller. Proper seating of the communication module and secure fieldbus wiring are required to prevent bus faults, such as communication slot trip code CE0.
Diagnostics and Status Indication
System status and active TRIP conditions on the Lenze E82EV371_2B are indicated via visual LEDs on the front panel and digital communication tools. A steady green LED indicates that the drive is powered and ready or actively driving the motor, while a flashing green LED indicates controller inhibit mode. A flashing red LED signals an active fault condition that has tripped the drive output.
For detailed diagnostic analysis, the drive maintains an integrated fault history memory log that records recent TRIP events. Technicians can read specific fault codes, operational values, and trip conditions using the XT Keypad E82ZBC display or through the real-time diagnostic monitor built into Lenze Global Drive Control (GDC) software.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Operating State LED | Green - Solid / Flashing | Steady Green = Ready/Running; Flashing Green = Controller inhibit active |
| Fault LED | Red - Flashing | Fault/TRIP condition active |
Replacement and Spare Part Considerations
When replacing a Lenze E82EV371_2B in an existing panel, exact part number matching is critical to ensure identical power ratings (0.37 kW) and input voltage compatibility (180–264 V AC). Because the 8200 Vector series uses modular plug-in function blocks, the replacement drive chassis must be fitted with the exact fieldbus or I/O module from the original drive, such as the CANopen (E82ZAFC) or PROFIBUS (E82ZAFP) module, to maintain network communication and control terminal behavior.
A replacement E82EV371_2B drive cannot operate directly out of the box without transferring the original drive's parameter configuration. Parameters stored in the non-volatile EEPROM must be uploaded via GDC software or copied using the XT Keypad E82ZBC to the new unit. If migration to current technology is preferred, Lenze designates the i510 and i550 cabinet series as the recommended successor series for 8200 Vector drives, though retrofitting requires reviewing physical mounting dimensions, terminal wiring, and fieldbus configuration.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Short Circuit | Short circuit at the output terminals or severe motor current surge. | Short circuit in motor cable or motor winding; ground fault; acceleration ramp too short. | Check motor cable and motor insulation; check output wiring; increase acceleration time. |
| OC2 | Earth Fault | Earth/ground fault detected at drive output. | Earth fault in output motor cable or motor insulation failure. | Check motor and cable for insulation breakdown to ground. |
| OC3 | Overload during Acceleration | Excessive motor current during acceleration phase. | Acceleration time too short; mechanical overload or stuck motor shaft. | Increase acceleration time (parameter C0012); check motor sizing and mechanical load. |
| OC4 | Overload at Constant Speed | Excessive continuous motor current during steady state operation. | Mechanical overload; motor undersized for load. | Check mechanical drive train for blockages; verify motor current rating. |
| OC5 | I x t Overload | Inverter thermal overload (I x t protection activated). | Continuous current requirement exceeding continuous inverter rating. | Reduce continuous motor load; check duty cycle; verify drive rating. |
| OU | Overvoltage in DC Bus | DC bus voltage exceeded upper limit threshold. | Deceleration time too short; regenerative energy from motor load too high. | Increase deceleration time (parameter C0013); connect external braking module/resistor if supported. |
| LU | Undervoltage in DC Bus | DC bus voltage dropped below minimum allowed operating limit. | Mains supply voltage too low; supply phase failure; power line interruption. | Check input mains voltage supply and fuses. |
| OH | Heatsink Overtemperature | Drive heat sink temperature exceeded maximum threshold. | Insufficient ambient cooling; fan failure or clogged heat sink fins; excessive ambient temperature. | Clean heat sink cooling fins; improve control cabinet ventilation; check ambient operating temperature. |
| OH4 | Motor Overtemperature (PTC/TK) | Motor temperature sensor input triggered fault. | Motor overheated; motor PTC or thermal contact switch opened; sensor connection broken. | Allow motor to cool down; check motor thermal protection wiring and sensor. |
| LP | Mains Phase Failure | Phase loss detected on AC supply mains. | Asymmetric supply mains; failure of one supply phase or line fuse. | Check mains voltage across all supply terminals and inspect input fuses. |
| CE0 | Communication Failure Slot | Communication failure with installed function module. | Plug-in communication module disconnected or faulty; fieldbus network cable interruption. | Check fieldbus cable connections and communication module seated properly. |
| EEr | External Fault | External fault condition signalled via digital input trip assignment. | External fault contact or sensor opened. | Inspect connected external protective devices and digital input signals. |
| P13 | Parameter Error | Parameter data set checksum or parameter transfer error. | Incomplete or corrupt parameter transfer; internal memory fault. | Reload factory default parameter set (C0002) and reconfigure drive parameters. Internal fault if persistent — return unit for repair. |
| H10 | Hardware Fault Internal | Internal electronic hardware fault detected by micro-controller system. | Internal circuit board or component failure. | Internal hardware fault — non-field serviceable; replace unit or return unit for repair. |
| H11 | Control Board Error | Internal power section or control board hardware fault. | Internal hardware component failure. | Internal hardware fault — non-field serviceable; replace unit or return unit for repair. |
| NMAX | Speed Limit Exceeded | Actual motor speed exceeded maximum configured speed parameter threshold. | Overhauling load; improper motor parameter calibration or encoder feedback error. | Check speed feedback configuration and mechanical load condition. |
Frequently Asked Questions
What tools are required to configure the Lenze E82EV371_2B inverter?
The inverter can be configured using the optional XT Keypad E82ZBC attached directly to the front interface slot or via a PC running Lenze Global Drive Control (GDC) software connected through a communication adapter.
Can a replacement Lenze E82EV371_2B drive be installed directly out of the box?
No, a replacement drive requires parameter configuration before operation. Motor parameters, speed ramps, and communication settings stored in the original drive's EEPROM must be transferred using the XT Keypad E82ZBC or GDC software.
What do the front panel status LEDs on the E82EV371_2B indicate?
A steady green LED indicates normal ready or running state, while a flashing green LED indicates controller inhibit active. A flashing red LED indicates an active fault or TRIP condition.
How are communication protocols such as PROFIBUS or CANopen integrated into this inverter?
The drive features a modular expansion slot that accepts pluggable function modules, including the CANopen module E82ZAFC, PROFIBUS module E82ZAFP, or LECOM RS-232/RS-485 modules.
What action should be taken if the inverter displays fault code H10 or H11?
Fault codes H10 and H11 indicate internal electronic hardware or control board failures. These internal hardware faults are not field-serviceable, requiring drive replacement or repair.
What is the recommended successor series for the Lenze 8200 Vector inverter family?
Lenze recommends the i510 or i550 cabinet series as successor drive models for replacing legacy 8200 Vector frequency inverters in panel installations.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.