Lenze E82EV752_4C200 8200 Vector Frequency Inverter

Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze E82EV752_4C200 is a 7.5 kW frequency inverter from the 8200 Vector series designed for precise speed control and torque management of three-phase AC motors. Operating on a 3-phase mains supply voltage from 320 V AC to 528 V AC, this enclosure-mounted drive delivers a rated continuous output current of 16.5 A and provides a peak overload current of 24.8 A for up to 60 seconds. Housed in an IP20 enclosure, the unit features an integrated Class A radio interference filter that suppresses line-bound electromagnetic emissions without needing additional external panel space. It supports both sensorless vector control and V/f characteristic control across an output frequency range of 0 to 480 Hz with a default switching frequency of 8 kHz.
Putting a replacement drive into service requires matching the physical power rating and transferring any attached control hardware from the original installation. The E82EV752_4C200 utilizes a modular system architecture that cleanly separates the base power section from user control options, accommodating plug-in modules such as the Standard I/O Function Module (E82ZAFSC), CANopen (E82ZAFCC), PROFIBUS-DP (E82ZAFPC), or LECOM RS485 communication cards. Replacement units are rarely plug-and-play and require parameter setup; up to four independent parameter sets stored in internal non-volatile EEPROM memory must be loaded using either the Keypad XT (E82ZBC) handheld module or Lenze Global Drive Control (GDC) PC software. Maintenance personnel seeking support during configuration transfer or spare preparation can consult ABC Industrial Parts for operational exchange units and technical assistance.
Drive status and fault conditions are monitored through front-panel LED indicators, digital status word inspection via fieldbus connections, and active fault history code logs under parameter C0168. A solid green OK LED indicates normal enabled operation, while a flashing green LED signifies controller inhibit or standby. The red FLT LED illuminates solid during active inverter trips and flashes rapidly for active warnings; persistent illumination across power cycles indicates an internal control hardware condition. While field faults such as heatsink overtemperature (OH), line phase loss (LP1), or DC bus overvoltage (OU) can be resolved by checking cooling fans, mains supply, or braking resistors, internal board failures (H05) and persistent EEPROM corruptions (EE0) require shop repair. ABC Industrial Parts provides tested replacement drives and repair services to minimize system downtime.
Technical Specifications
| Manufacturer | Lenze |
| Part Number | E82EV752_4C200 |
| Model / Type | 8200 Vector Frequency Inverter |
| Product Family | 8200 Vector |
| Component Type | Frequency Inverter |
| Rated Power | 7.5 kW |
| Supply Voltage Range | 320 - 528 V AC |
| Supply Input Phases | 3 phase |
| Rated Continuous Current | 16.5 A |
| Maximum Output Current | 24.8 A |
| Output Frequency Range | 0 - 480 Hz |
| Default Switching Frequency | 8 kHz |
| Control Method | V/f Characteristic Control, Sensorless Vector Control |
| Protection Rating | IP20 |
| Integrated RFI Filter | Class A Integrated Interference Filter |
Programming and Configuration
Programming and parameter management for the Lenze E82EV752_4C200 inverter are performed using either Lenze Global Drive Control (GDC) PC software or the plug-in Keypad XT (E82ZBC) operating module. The inverter contains non-volatile EEPROM memory configured to hold up to four complete, independent parameter sets, enabling flexible setup changes for multi-recipe machines or varied motor operating profiles.
Commissioning a new unit involves writing motor parameters, speed ramp times (C0012 acceleration and C0013 deceleration), switching frequency parameters, and fieldbus node addresses. In instances where parameter structures become corrupted, a factory reset can be executed via parameter C0002. Parameter files saved in GDC software can be uploaded directly to a spare unit to ensure identical dynamic performance to the original drive.
Communication and System Integration
The Lenze 8200 Vector series uses a modular interface slot (FIF) that separates fieldbus hardware from the main drive control board. The E82EV752_4C200 supports a range of swap-in function modules, including the Standard I/O Function Module (E82ZAFSC) for hardwired analog and digital control schemes.
For higher-level network integration with industrial PLCs, optional communication modules can be installed into the slot. These include the CANopen Function Module (E82ZAFCC), PROFIBUS-DP Function Module (E82ZAFPC), and LECOM RS485 modules. These interfaces allow cyclic transmission of control signals, velocity setpoints, status word feedback, and direct parameter editing over the automation network.
Diagnostics and Status Indication
The E82EV752_4C200 incorporates real-time visual LED status indicators on its front panel alongside digital diagnostic routines. Diagnostic data can be evaluated via fieldbus network status words or read out as active fault history codes under parameter C0168 using GDC software or the Keypad XT module.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Red LED (FLT) | Red - Solid or Flashing | Solid lit indicates an active inverter fault or trip state requiring reset. Fast flashing indicates an active warning. Persistent illumination across power cycles suggests an internal control hardware fault. |
| Green LED (OK) | Green - Solid or Flashing | Solid green indicates drive is operational and enabled. Flashing green indicates controller inhibit (IMP) or standby state. |
Replacement and Spare Part Considerations
When replacing a failed Lenze E82EV752_4C200, verify that the replacement drive matches the required 7.5 kW power rating, 320-528 V AC 3-phase supply input, and the version C integrated Class A RFI filter suffix. The modular nature of the 8200 Vector series allows maintenance technicians to detach the existing plug-in function module (e.g., PROFIBUS-DP or CANopen) and Keypad XT from the faulty unit and transfer them directly onto the replacement base unit.
A replacement inverter will not run without proper parameter transfer. Before placing a replacement drive into active service, restore its configuration using a Global Drive Control (GDC) software parameter backup file or transfer the parameter sets stored on the Keypad XT module. For new system designs or complete control system modernizations, the Lenze i550 cabinet drive serves as the recommended successor series.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OH | Heatsink Overtemperature | Heatsink temperature exceeds critical limit (> 90°C) | Insufficient cooling airflow, dirty heatsink, fan failure, ambient temperature too high, excessive continuous load | Clean heatsink fins, check cabinet ventilation and fan function, reduce load or switching frequency |
| OH3 | Motor Temperature Warning / Tripped | Motor PTC thermal sensor activated or motor overload threshold exceeded | Motor overload, mechanical binding, incorrect thermal sensor wiring or parameter setting | Check motor mechanical load, inspect PTC sensor connection at terminals T1/T2, verify motor rated parameters |
| OH4 | Inverter Internal Overtemperature | Internal temperature inside inverter housing exceeds trip threshold | Excessive enclosure ambient temperature, internal fan failure | Cool enclosure, replace internal fan if failed. If error persists at room temperature, indicates internal hardware failure requiring service |
| OC1 | Short Circuit / Earth Fault / Overcurrent during Acceleration | Output current exceeded peak limit during motor acceleration phase | Short circuit in motor cable, motor winding fault, ground fault, acceleration ramp time set too short | Check motor cable insulation, test motor windings for phase-to-phase and phase-to-ground short circuit, increase acceleration ramp time C0012 |
| OC2 | Overcurrent during Deceleration | Output current exceeded peak limit during motor deceleration phase | Deceleration ramp time set too short, high load inertia, missing braking resistor | Increase deceleration ramp time C0013, enable Vmax controller or install external brake chopper/resistor |
| OC3 | Overcurrent at Constant Speed | Output current exceeded peak threshold during steady-state operation | Sudden mechanical load spike, motor stalling, severe supply voltage drop | Inspect mechanical machine elements for jamming/obstruction, check motor sizing and current limits |
| OC5 | Ixt Overload | Inverter load current integral (I x t) exceeded allowable limit (150% load for > 60s) | Continuous operation above rated current, motor undersized for drive application | Reduce continuous load on motor, verify drive power sizing relative to application demand |
| OU | DC Bus Overvoltage | DC bus voltage exceeds maximum threshold (approx. 770 V DC for 400 V class) | Regenerative energy from motor during deceleration, deceleration ramp too fast, braking chopper disabled or resistor faulty | Extend deceleration time, connect external braking resistor, check mains supply voltage level |
| LU | DC Bus Undervoltage | DC bus voltage dropped below minimum operating limit | Mains supply failure, supply voltage drop, blown line fuse, defective mains contactor | Check 3-phase mains voltage, inspect fuses and wiring, verify line voltage stability under load |
| LP1 | Mains Phase Loss | Phase loss detected on incoming AC mains supply | One phase missing from incoming 3-phase mains, blown supply fuse, loose line connection | Check line supply voltage across all three phases (L1, L2, L3) at inverter input terminals |
| EE0 | EEPROM Memory Fault | Parameter data corruption in non-volatile memory or EEPROM hardware read/write failure | Internal EEPROM memory failure, power interrupted during parameter save procedure | Perform factory parameter reset (C0002). If error persists after reset, internal hardware fault — return unit for repair |
| EEr | EEPROM Read/Write Error | Checksum failure or fault reading parameter structure from internal memory | Parameter memory corrupted, control board fault | Reload parameters from backup or reset to factory defaults (C0002). Internal board fault if unresolvable |
| NMAX | Overspeed Limit Exceeded | Motor speed exceeded maximum configured speed limit | Encoder feedback fault, load driving the motor, incorrect slip compensation or motor parameter settings | Check motor control settings, feedback wiring, and mechanical overspeed condition |
| E4 | Communication Time-out / Module Error | Communication failure between inverter control board and plug-in function module or fieldbus network | Pluggable function module loose/unseated, fieldbus cable break, bus master offline | Verify function module is properly seated in FIF slot, check fieldbus cabling and baud rate settings |
| H05 | Internal Hardware Fault | Internal control board or power section failure detected during self-test | Internal electronic components damaged or unserviceable | Internal hardware fault — return unit for repair or replace inverter |
Frequently Asked Questions
What tools are required to program the Lenze E82EV752_4C200 inverter?
Programming and configuration can be completed using Lenze Global Drive Control (GDC) software connected via a PC interface or directly using the optional Keypad XT (E82ZBC) handheld module.
Does the E82EV752_4C200 require an external RFI filter?
No, the drive features an integrated Class A radio interference filter designed to meet EMC standards without requiring external footprint filter hardware inside the cabinet.
How can parameter sets be copied to a replacement unit?
Parameter sets can be transferred by saving a backup file using Global Drive Control (GDC) software and downloading it to the replacement drive, or by storing and copying parameter sets via the Keypad XT (E82ZBC) module.
What fieldbus protocols are supported by this inverter?
The drive supports CANopen and PROFIBUS-DP through optional swap-in function modules (E82ZAFCC and E82ZAFPC), as well as LECOM RS485 communications.
What does an H05 fault code indicate on the drive display?
An H05 fault code signifies an internal control board or power section hardware failure detected during internal diagnostics. This fault cannot be serviced in the field and requires unit repair or replacement.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.
Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.