Lenze EVF9323-EVV004 9300 Vector Frequency Inverter 1.5 kW

New 
On request
Refurbished   
9 available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: 9300 Vector | Series: 9300 Vector

The Lenze EVF9323-EVV004 is a 1.5 kW frequency inverter belonging to the 9300 Vector series, engineered for high-dynamic motor control and speed regulation in industrial automation installations. Designed to operate on a 3-phase mains supply between 320 V AC and 528 V AC, this AC drive delivers a rated output current of 3.9 A with an overload capacity of up to 150% (5.85 A) for 60 seconds. The V004 designation identifies a specific hardware configuration manufactured without an integrated RFI filter, making it ideal for installation in control panels that utilize dedicated external line filtering. It supports Sensorless Vector Control, Field-Oriented Control (FOC), and programmable V/f characteristic curves to regulate standard three-phase AC motors across dynamic load profiles.

Interfacing options on the EVF9323-EVV004 include an onboard CAN system bus supporting communications up to 500 kbps, alongside an integrated automation slot for modular fieldbus cards. Physical I/O terminals provide 6 parameterisable digital inputs, 1 controller enable input, 4 digital outputs, 2 bipolar analog inputs, and 2 analog outputs. Commissioning a replacement inverter into an active machine requires matching the application configuration, function block assignments, and parameter settings of the existing unit. Parameter transfer can be performed directly using the optional EMZ9371BC operating keypad or via Global Drive Control (GDC) PC software. Parameter extraction from a faulty donor unit and pre-configuration support available through ABC Industrial Parts help streamline spare-part installation and reduce unexpected machine downtime.

System diagnostic evaluation is supported through hardware status LEDs and software status monitoring. Front panel LEDs provide immediate operational status, with a green Ready LED indicating drive readiness or active running status, and a red TRIP LED signaling protective shut-off conditions. Internal status parameter C0168 logs active fault states, while the integrated fault history buffer stores recent events for diagnostic review. Issues such as overcurrent (OC1, OC2, OC5), mains phase loss (LP1), or DC bus overvoltage (OU) can often be resolved through external checks on wiring, braking modules, or ramp settings. When internal component defects or unrecoverable hardware trips occur, board-level repairs or replacing the unit with a tested exchange inverter from ABC Industrial Parts offers a swift return to full operation.

Technical Specifications

ManufacturerLenze
Part NumberEVF9323-EVV004
Model / TypeEVF9323-EV V004
Product Family9300 Vector
Component TypeFrequency Inverter
Rated Power1.5 kW
Supply Voltage Range320 - 528 V AC (3-Phase)
Rated Output Current3.9 A
Maximum Output Current (60s Overload)5.85 A
Output Frequency Range0 - 480 Hz
Switching Frequency8 kHz
Control MethodsSensorless Vector Control / Field Oriented Control / V/f Characteristic
Digital Inputs6 parameterisable (+1 controller enable)
Digital Outputs4 parameterisable
Analog Inputs2 bipolar (-10V to +10V or 0/4-20mA)
Analog Outputs2 (-10V to +10V or 0/4-20mA)
Onboard InterfaceCAN / Lenze System Bus (up to 500 kbps)
Expansion SlotAutomation Slot for Fieldbus Modules
RFI FilterWithout integrated RFI filter (V004 variant)

Programming and Configuration

Parameterization and functional programming of the Lenze EVF9323-EVV004 inverter are performed using standard Lenze software tools or plug-in keypad hardware. The drive features an open control structure using interconnectable function blocks, which allow engineers to program speed control loops, torque limits, dynamic acceleration profiles, and custom input/output mappings directly within the drive firmware.

Commissioning or replacing a drive unit requires transferring the parameter dataset from the original drive or engineering backup file. Using the optional EMZ9371BC keypad module, complete parameter profiles can be cloned directly between drive units without a PC. Alternatively, the Global Drive Control (GDC) software tool connects via system bus adapters to read, edit, transfer, or back up parameter sets. Restoring default operational conditions is accomplished by executing a factory reset via parameter C0002 (set to value 11).

Communication and System Integration

The EVF9323-EVV004 is equipped with a native CAN / Lenze system bus interface capable of communication speeds up to 500 kbps. This integrated bus allows high-speed peer-to-peer data interchange between multiple 9300 Vector drives, facilitating multi-axis synchronization and master-slave drive configurations across a shared CAN line.

For integration into broader plant networks, the drive includes a dedicated automation slot that accepts modular fieldbus communication cards. Supported modules include the EMF2133IB PROFIBUS-DP card, EMF2102IB or EMF2103IB LECOM interfaces (RS232/RS485), and EMF2171IB or EMF2172IB PC system bus adapters, allowing connection to higher-level programmable logic controllers.

Diagnostics and Status Indication

Visual status indication on the Lenze EVF9323-EVV004 inverter is provided by front-mounted diagnostic LEDs. The Ready LED indicates the general operating state, while the TRIP LED alerts operators to protective drive shutdowns caused by overcurrent, overvoltage, motor overtemperature, or system communications errors.

Detailed diagnostic analysis is available through drive software parameters. Active errors are displayed in parameter C0168, and historical error events are stored within an internal fault history buffer. These diagnostic registers can be queried via the EMZ9371BC keypad or through real-time diagnostic monitoring in the Global Drive Control (GDC) software suite.

Status LED Indicators

LEDColor/StatusMeaning
TRIP LEDRed - Solid or FlashingInverter TRIP error state / Fault condition active. Indicates drive shut down due to protective fault function.
Ready LEDGreen - Flashing = Ready; Solid = RunningInverter operational status indicator. Flashing indicates drive is ready/operational; solid green indicates drive is enabled/running.

Replacement and Spare Part Considerations

When replacing an existing drive with a Lenze EVF9323-EVV004, ensure that the part number and variant matches the installation requirement. The V004 model is built without an integrated RFI filter; replacing an unfiltered drive with a unit containing an internal filter (or vice versa) can alter cabinet EMC performance or physical wiring clearance.

A replacement EVF9323-EVV004 will not run directly out of the box without configuration. Machine parameter values, motor nameplate data, I/O functions, and fieldbus communication settings must be transferred from the original inverter or restored from a software backup before enabling the drive.

If the original drive hardware is damaged or unresponsive, parameter sets can be written using GDC software over the system bus interface or cloned using the plug-in EMZ9371BC keypad from a matching donor unit on the same machine line.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
OC1Short Circuit / Overcurrent AccelerationShort circuit or extreme overload during motor acceleration.Short circuit in motor cable, inter-turn fault in motor, acceleration ramp time too short.Check motor and motor cable for short circuit or ground fault; increase acceleration time.
OC2Short Circuit / Overcurrent DecelerationShort circuit or extreme overload during motor deceleration.Deceleration ramp time too short, short circuit in motor output.Increase deceleration time; check motor output connection; verify braking module function.
OC5Short Circuit / Overcurrent Constant SpeedOvercurrent detected during constant speed operation.Sudden load change, motor stalled, mechanical jam, motor cable fault.Inspect mechanical load for jams or binding; check motor wiring.
OUOvervoltage DC BusDC bus voltage exceeds maximum limit.Regenerative energy from motor during deceleration too high, mains supply voltage too high.Increase deceleration ramp time; connect or inspect external brake resistor / brake chopper.
LUUndervoltage DC BusDC bus voltage falls below operational threshold.Mains supply voltage too low, supply phase loss, power supply failure.Check supply voltage mains supply and fuse connections.
OHHeatsink OverheatingInverter heatsink temperature exceeded maximum safety threshold.Cooling fan clogged or failed, ambient temperature too high, ventilation restricted, continuous high load.Clean heatsink, ensure adequate cabinet ventilation, verify fan function.
OH3Motor Overheating (PTC)Motor thermistor (PTC / sensor on T1/T2 terminals) triggered overheating threshold.Motor overloaded, cooling fan on motor defective, ambient temperature at motor high.Allow motor to cool; check mechanical load; verify motor PTC sensor connection.
OH4Inverter Inside OverheatingInternal air temperature inside inverter casing is too high.Cabinet ambient temperature excessive, fan failure.Improve enclosure cooling and air circulation.
OH7Motor Temperature Sensor Wire BreakOpen circuit detected on motor thermistor input (T1/T2).Broken wire, disconnected motor PTC sensor.Inspect wire connection to motor PTC terminals T1 and T2.
OH8Motor Temperature Sensor Short CircuitShort circuit detected on motor temperature sensor connection.Short circuit in sensor wiring or defective sensor.Check sensor wire insulation and replace PTC sensor if defective.
CE0Communication Error Module SlotCommunication fault with expansion module in automation slot.Fieldbus module loose, defective module, bus line interruption.Check seating of module in automation slot; check fieldbus connection.
CE1System Bus (CAN) Communication Error Channel 1System bus CAN communication time-out or bus-off state on channel 1.CAN cable disconnected, incorrect baud rate, missing bus termination resistor.Check CAN wiring, shield grounding, and termination resistors (120 Ohm).
CE2System Bus (CAN) Communication Error Channel 2System bus CAN communication fault on process data channel 2.Master device lost or communication time-out.Verify master CAN controller activity and frame cycle timing.
CE3System Bus (CAN) Communication Error Channel 3System bus CAN communication fault on process data channel 3.Interrupted message transfer on system bus.Inspect CAN node parameters and bus topology.
CE4System Bus CAN Transmit ErrorCAN controller bus-off or transmit overload.Excessive bus traffic, wiring short circuit on CAN_H / CAN_L.Inspect physical CAN line and check baud rate configuration across all nodes.
EERInternal Memory Fault (EEPROM Error)Non-volatile EEPROM memory read/write error. Internal board-level component fault.EEPROM memory corruption or hardware component failure.Internal hardware fault — execute factory reset (C0002 = 11); if error persists, return unit for repair or replace inverter.
FUEFrequency Input Signal ErrorFault detected in frequency input or encoder feedback signal.Encoder wire break, missing pulse feedback.Check encoder cable connection and signal levels.
LP1Mains Phase FailureFailure or high imbalance of one input phase on mains power lines.Blown main fuse, loose supply cable phase, line unbalance.Check supply mains voltages at input terminals L1, L2, L3.
NMAXMotor OverspeedMotor speed exceeded maximum limit set in parameter C0596.Overhauling load, wrong encoder scale, control loop instability.Verify speed limit parameter C0596; check encoder feedback and load parameters.
P12Controller Internal Hardware ErrorInternal monitoring hardware fault detected on control PCB.Defective internal control board, power supply monitoring fault.Internal hardware fault — turn off power and restart; if persistent, unit requires repair or replacement.
P13Motor Phase FailurePhase interruption detected in motor output lines (U, V, W).Disconnected motor cable, open motor winding, output contactor open during operation.Check cabling between inverter terminals U, V, W and motor terminals; check motor windings.
PR0Program Error / Internal System FaultInternal firmware execution fault or watchdog timeout.Firmware fault or severe electromagnetic disturbance.Internal hardware/firmware fault — power cycle drive; replace drive unit if problem persists.
PR1System Program ErrorSystem micro-controller memory or operating program crash.Internal CPU fault or board-level failure.Internal fault — perform power restart; return unit for factory service or replacement if recurring.
H05Internal Hardware ErrorHardware diagnostic failed during self-test.Defective internal gate driver or power stage measurement circuit.Internal hardware failure — non-field-serviceable; repair or replace inverter unit.

Frequently Asked Questions

How do I clone parameters to a replacement Lenze EVF9323-EVV004 inverter?

Parameters can be cloned using the optional EMZ9371BC keypad module by transferring saved memory profiles between units, or electronically via Global Drive Control (GDC) PC software connected to the drive interface.

What does the V004 designation in the model number indicate?

The V004 variant indicates that the frequency inverter is manufactured without an integrated RFI filter, making it suitable for systems utilizing external line filters.

Which fieldbus expansion modules can be installed on the EVF9323-EVV004?

The onboard automation slot supports fieldbus cards including the EMF2133IB PROFIBUS-DP module, EMF2102IB or EMF2103IB LECOM cards, and InterBus communication modules.

What does a flashing green Ready LED indicate?

A flashing green Ready LED indicates that the drive power supply and operational status are ready, while a solid green LED indicates that the inverter is enabled and actively running.

How can I resolve an EER fault code on the inverter?

An EER fault indicates an internal EEPROM memory error. You can attempt to clear it by resetting the inverter to factory defaults via parameter C0002 (value 11). If the fault persists, internal memory corruption or hardware damage requires unit repair or replacement.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.