Lenze EVS9326-EKV004 EVS9326-EK V004 9300 Servo Cam Controller

New 
On request
Refurbished   
10+ available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: 9300 Servo | Series: 9300 Servo Cam Profiler

The Lenze EVS9326-EKV004 is an 11 kW digital AC servo controller within the 9300 Servo family, engineered for high-dynamic motion control applications requiring decentralized execution. Featuring the integrated electronic cam profiler (-EK firmware variant), this drive executes complex dynamic curves locally, offloading motion calculation requirements from central controllers. Designed with an IP20 enclosure for cabinet installation, the drive operates across a 3-phase supply voltage range of 320 V AC to 528 V AC. It provides a rated output current of 23.5 A with a 150% peak overload capacity reaching 35.2 A for up to 60 seconds, operating at an 8 kHz switching frequency across an output frequency spectrum of 0 to 480 Hz.

Connecting the replacement unit to your system involves establishing proper feedback, control, and network interfaces. System wiring includes a dedicated resolver feedback connector (X7), master encoder input (X8), and encoder simulation output (X9), along with 4 digital inputs, 2 digital outputs, 2 differential analog inputs, and 2 analog outputs for direct local signal interaction. Communication across multi-axis configurations relies on the integrated CANbus system interface, while the Automation Interface (AIF) slot accommodates fieldbus modules such as PROFIBUS-DP or CANopen. Placing a spare unit into service requires transferring parameter sets and electronic cam tables using Lenze Global Drive Control (GDC) software or the optional EMZ9371BC Keypad XT, ensuring that drive profiles, gain parameters, and option settings match the original installation before enabling operation. Technical technicians at ABC Industrial Parts can assist with extracting parameter files and backing up drive configurations during service transitions.

Real-time troubleshooting and operational state verification are facilitated by front-panel LEDs alongside detailed code history registers. Three visual status indicators provide quick diagnostics: a green DRIVE READY light for operational state or controller inhibit, a red DRIVE ERROR / FAULT light for active trips, and a yellow BUSY / WARNING indicator for task processing or limit thresholds. First-line diagnostics include evaluating supply line stability, feedback cable integrity at X7, braking chopper and resistor circuits, and CAN bus termination resistors. Critical conditions such as internal microcontroller errors (H05) or EEPROM parameter corruption (EER) indicate board-level hardware failures that cannot be serviced in the field. When internal memory or power stage components fail, obtaining a tested exchange unit or utilizing expert repair services through ABC Industrial Parts provides a rapid path to restoring machine productivity.

Technical Specifications

ManufacturerLenze
Part NumberEVS9326-EKV004
Model / TypeEVS9326-EK V004
Product Family9300 Servo
Component TypeServo Controller
Rated Power11 kW
Supply Voltage Range320 - 528 V AC
Rated Output Current23.5 A
Maximum Output Current35.2 A
Switching Frequency8 kHz
Output Frequency Range0 - 480 Hz
Protection RatingIP20
Digital Inputs4
Digital Outputs2
Analog Inputs2
Analog Outputs2
Integrated System BusCANbus

Programming and Configuration

Parameterization and cam profile management for the Lenze EVS9326-EKV004 are conducted using Lenze Global Drive Control (GDC) software along with Lenze Cam Designer. These engineering tools allow software developers and maintenance personnel to generate, calculate, and modify decentralized electronic cam tables and motion trajectories. Motion profiles are downloaded directly into non-volatile drive memory, enabling localized position control without requiring continuous motion command streams from an external controller.

Manual configuration and local parameter management can also be executed using the optional plug-in EMZ9371BC Keypad XT operating module. The keypad provides access to the parameter structure, fault memory history, and operational status parameters. When transferring configurations between units, parameter sets must be completely downloaded and verified, paying specific attention to speed loop gain settings, thermal limits, and cam interpolation table integrity to prevent profile loading errors such as code PR0.

Communication and System Integration

Inter-drive networking on the EVS9326-EKV004 is handled via an integrated CANbus system bus interface. This protocol supports multi-axis drive synchronization, position data sharing, and cross-drive parameter transfer. Correct network integration requires installing standard 120-ohm bus termination resistors at both physical ends of the CAN network and verifying matching baud rate settings across all participating drives.

Extended fieldbus integration is accomplished using the Automation Interface (AIF) slot located on the front of the drive controller. Optional plug-in modules including the EMF2133IB for PROFIBUS-DP, EMF2175IB for CANopen, INTERBUS, or LECOM interfaces allow connection to plant-wide PLC networks. Onboard I/O connectivity consists of 4 digital inputs, 2 digital outputs, 2 differential analog inputs, and 2 analog outputs, supplemented by dedicated terminals for resolver motor feedback (X7), master encoder input (X8), and encoder simulation (X9).

Diagnostics and Status Indication

Drive state monitoring and diagnostic reporting for the EVS9326-EKV004 utilize three color-coded front panel LED indicators alongside software-based diagnostic buffers. The green DRIVE READY LED lights solid during normal operation and blinks when the drive controller is inhibited. The red DRIVE ERROR / FAULT LED indicates an active trip or registered fault requiring acknowledgment, while the yellow BUSY / WARNING LED signals active processing tasks or current and thermal warning limits.

In-depth fault analysis can be conducted by connecting a PC running Global Drive Control software using the EMF2102IB PC system bus adapter, or by querying the active fault history buffer via the EMZ9371BC Keypad XT. Diagnostic records store error histories to assist in pinpointing external issues such as motor cable short circuits, line voltage instability, feedback signal loss, or internal board-level faults.

Status LED Indicators

LEDColor/StatusMeaning
DRIVE READYGreen - Solid / BlinkingSolid: Drive operational / normal state. Blinking: Drive ready, controller inhibited / disabled.
DRIVE ERROR / FAULTRed - Solid / BlinkingTrip condition active or fault registered; requires acknowledgment / reset.
BUSY / WARNINGYellow - SolidDrive processing task active or warning limit reached (e.g. current limit, overtemperature warning).

Replacement and Spare Part Considerations

When replacing an existing Lenze EVS9326-EKV004 unit, it is essential to verify that the replacement controller matches both the exact part number and the -EK firmware variant. The -EK classification indicates built-in electronic cam profiler functionality; substituting a standard inverter or different firmware variant will result in missing motion profile execution capabilities and system communication failure.

Prior to applying power to the replacement drive, all configuration data, motor parameters, and electronic cam tables must be restored from a known good backup using GDC software or transferred via the EMZ9371BC keypad. Physical option modules, such as AIF fieldbus cards (EMF2133IB or EMF2175IB), must be carefully transferred from the original drive, ensuring secure seating in the expansion slot before commissioning the machine.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
OC1Short circuit / Earth faultOvercurrent trip during acceleration or short circuit at output terminalsShort circuit in motor winding, grounded motor cable, dynamic overcurrent threshold exceededCheck motor and motor wiring for insulation fault or short circuit; check acceleration time settings.
OC2Overcurrent during decelerationOvercurrent trip during braking phaseBraking ramp too short, motor regenerated power excessiveExtend deceleration time, verify brake chopper and braking resistor function.
OC5I x t OverloadDrive overloaded continuously beyond thermal integration limitDrive undersized for mechanical load, mechanical jamming/stickingCheck mechanical drive train for stiffness/jamming, check current limit settings and duty cycle.
OUOvervoltage DC busDC bus voltage exceeded upper trip limitExcessive braking energy returned from motor, missing or damaged braking resistor, braking chopper failureVerify mains voltage, inspect brake resistor connection and value, check brake chopper.
LUUndervoltage DC busDC bus voltage fell below lower trip limitMains supply failure, supply phase loss, supply voltage dropped under loadCheck input line voltage and fuses, verify mains supply stability.
OHHeatsink OvertemperaturePower section heatsink temperature exceeded maximum permissible limitVentilation fan blocked/failed, ambient temperature too high, heatsink clogged with dustClean heat sink, inspect cabinet fan and drive fan operation, improve panel cooling.
OH4Heatsink Overtemperature Limit ExceededCritical heatsink temperature reachedSevere cooling airflow blockage or internal fan failureAllow drive to cool down; inspect cooling system and internal fan.
OH7Motor Overtemperature (PTC/NTC)Motor temperature sensor trip triggered via control terminal X10Motor thermal overload, cooling fan failure on motor, broken sensor wireCheck motor thermal load, check motor external cooling fan, verify PTC/NTC sensor and cable connections.
OH8Motor I2t OverloadCalculated motor thermal load model exceeded maximum thresholdContinuous low-speed high-torque operation without forced motor coolingReduce continuous motor load or fit forced-ventilation fan to motor.
CE0CAN Communication ErrorSystem bus (CAN) communication faultBus cable broken, missing bus termination resistor, noise interference on CAN lineCheck CAN bus wiring, 120 ohm line termination, and baud rate parameters.
CE1AIF Communication FaultCommunication failure between drive control board and plug-in AIF fieldbus moduleAIF module loose, defective option module, internal interface errorRe-seat AIF module; if fault persists, replace plug-in fieldbus module or unit.
NMAXMaximum Speed ExceededMotor speed exceeded configured maximum speed limit by more than allowable thresholdUnstable speed controller tuning, encoder feedback issue, runaway loadCheck speed feedback sensor/resolver wiring, verify gain parameters in drive speed loop.
LPMains Phase FailureMissing AC input phase detectedOne input line fuse blown, loose terminal connection, asymmetric mains supplyCheck line supply fuses, mains cables, and terminal connections.
P12Resolver Signal ErrorResolver feedback signal loss or track error on terminal X7Resolver cable broken or disconnected, damaged resolver, electrical noise on feedback cableInspect feedback cable, shielding, and connector at X7; verify resolver coil resistance.
H05Internal Hardware ErrorInternal micro-controller hardware fault or memory corruption detected during self-testBoard-level component failure, power interruption during flash writeInternal hardware fault — power cycle drive; if fault recurs, return unit for repair or replace unit.
EEREEPROM FaultError during reading or writing non-volatile parameter memory EEPROMInternal parameter memory corrupted or worn outReload factory default parameters; if error persists, internal memory hardware fault requires unit replacement or repair.
PR0Cam Profile Error / Program ErrorInvalid or incomplete cam profile data loadedCam table calculation error, missing interpolation node pointsRe-download cam tables from Lenze Cam Designer / GDC software.

Frequently Asked Questions

What software is required to configure the Lenze EVS9326-EKV004?

Configuration and cam profile programming are performed using Lenze Global Drive Control (GDC) software combined with Lenze Cam Designer software. Parameter changes can also be performed locally using the optional EMZ9371BC Keypad XT.

What does a blinking Green LED on the EVS9326-EKV004 indicate?

A blinking Green DRIVE READY LED indicates that the drive controller is powered and ready for operation, but the controller inhibit / disable function is currently active.

How are electronic cam tables loaded onto a replacement EVS9326-EKV004 drive?

Cam tables are loaded into non-volatile drive memory by downloading saved project files from Lenze Cam Designer or GDC software via a PC connected through an EMF2102IB PC system bus adapter, or by cloning parameters via the EMZ9371BC keypad module.

What does fault code H05 mean on this drive?

Fault code H05 indicates an internal hardware error or micro-controller memory fault detected during self-test. If power cycling the drive does not clear the error, internal hardware component failure requires repairing or replacing the unit.

Can fieldbus communications such as PROFIBUS-DP be added to the EVS9326-EKV004?

Yes, fieldbus support is expanded via the Automation Interface (AIF) slot, which accepts plug-in communication modules such as the EMF2133IB for PROFIBUS-DP or EMF2175IB for CANopen.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.