Lenze I5CA50030000A0000S CONTROL UNIT – i550 Frequency Inverter Control Unit

New 
On request
Refurbished   
1 available within 4 - 6 business days
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: i500

The Lenze I5CA50030000A0000S is a dedicated frequency inverter control unit belonging to the Lenze i500 product family, specifically designed for use with i550 cabinet power units. Operating within Lenze's decoupled modular architecture, this control module separates drive control logic and processing from the power section hardware, enabling independent servicing and hardware maintenance. The unit manages motor operation across multiple control modes, including linear or square V/f characteristic control, Sensorless Vector Control (SLVC), and Sensorless Synchronous Motor Control (SL-PSM), making it suitable for dynamic speed and torque regulation in material handling, packaging, textiles, and HVAC equipment.

For system integration and parameter management, the I5CA50030000A0000S features an onboard RS-485 interface for Modbus RTU fieldbus communication operating at data rates up to 115.2 kbps, alongside physical I/O including five assignable digital inputs, one 24 V DC digital output, two configurable analog inputs, one analog output, and a changeover relay contact. Replacing an operational unit requires transferring the parameter dataset to ensure matching drive characteristics. The control unit incorporates a removable plug-in memory module (EPM) that allows zero-tool parameter transfer, enabling quick swapping of existing settings into a spare without requiring software tools. When manual parameter backup, firmware verification, or parameter extraction from a faulty board is required, expert support from ABC Industrial Parts can assist in preparing replacement hardware for immediate production use.

Diagnostic status is communicated directly via the RDY (Ready) and ERR (Error) front-panel LEDs, which indicate conditions such as missing supply voltage, drive inhibition, active warnings, running state, or output trip faults. Further detailed system analysis is accessible through an optional keypad (i5MADK0000000S) or via Lenze EASY Starter software connected using a USB module (i5MADU0000000S) or WLAN adapter (i5MADW0000000S). First-line troubleshooting for common issues involves verifying line voltage, RS-485 bus connections, parameter settings, and motor wiring. When diagnostic codes such as internal hardware failure (0x6100) or short circuits occur, internal electronics faults cannot be serviced in the field, making replacement or exchange through ABC Industrial Parts the most efficient path to restore production stability.

Technical Specifications

ManufacturerLenze
Part NumberI5CA50030000A0000S
Model / TypeCONTROL UNIT
Product Familyi500
Component TypeFrequency Inverter Control Unit
Integrated Fieldbus InterfaceModbus RTU (RS-485)
RS-485 Baud Rate115.2 kbps
Digital Inputs5
Digital Outputs1 (24 V DC, 50 mA)
Analog Inputs2
Analog Outputs1
Relay Outputs1 Changeover (250 V AC / 3 A, 30 V DC / 3 A)
Control ModesV/f, SLVC, SL-PSM

Programming and Configuration

The Lenze I5CA50030000A0000S control unit utilizes Lenze EASY Starter engineering software for drive parameterization, commissioning, and detailed diagnostics. Parameter datasets dictate drive functions, motor characteristics, I/O assignments, and fieldbus communication settings. Commissioning can be performed by connecting a PC to the control unit via an optional USB module (i5MADU0000000S) or wirelessly using a WLAN module (i5MADW0000000S). Alternatively, basic parameter changes and status checks can be carried out directly using the optional plug-in keypad (i5MADK0000000S).

Application data and drive parameters are stored on a plug-in removable memory module (EPM). This physical storage architecture allows application settings to be retained independently of the control unit board hardware. During hardware maintenance or spare unit commissioning, swapping the memory chip from the old control unit into the replacement module automatically restores the complete drive parameter set without requiring a software connection or re-commissioning tools.

Communication and System Integration

Network connectivity for the I5CA50030000A0000S is provided through an integrated RS-485 serial communication port using the Modbus RTU protocol. The interface supports data transfer rates up to 115.2 kbps, enabling direct integration into fieldbus networks without requiring external gateway modules. Through Modbus RTU, higher-level controllers can issue control commands, monitor operational parameters, adjust setpoints, and query real-time drive status.

The control unit also provides local signal interfaces to interface directly with external sensors, switches, and supervisory hardware. Onboard connectivity includes five digital inputs, one 24 V DC digital output rated for up to 50 mA, two configurable analog inputs, one analog output, and a changeover relay contact rated at 250 V AC / 3 A or 30 V DC / 3 A. Network diagnostics and status monitoring can be conducted over Modbus diagnostic registers or via fieldbus monitoring tools in EASY Starter.

Diagnostics and Status Indication

Real-time diagnostic states are displayed on the front face of the I5CA50030000A0000S via two primary LED indicators labeled RDY (Ready) and ERR (Error). The multi-state RDY LED signals supply voltage presence, drive inhibition, active output operation, or warning conditions. The ERR LED provides instant notification of fault conditions, turning solid red when an operational fault disables the drive output.

Comprehensive diagnostic routines can be conducted by connecting the unit to Lenze EASY Starter software, which provides access to a detailed internal diagnostic logbook. Operational parameters, fault logs, and real-time register states are also accessible through the optional plug-in keypad (i5MADK0000000S) or via Modbus RTU diagnostic registers across the fieldbus network.

Status LED Indicators

LEDColor/StatusMeaning
RDY (Ready)Multi-stateOff: Supply voltage missing. Blinking slow (1 Hz): Inverter ready / inhibited. On steady: Inverter enabled and running. Blinking fast (4 Hz): Warning or error state active.
ERR (Error)Multi-stateOff: Normal operation / no error active. Blinking: Warning active. On steady: Fault active, drive output disabled.

Replacement and Spare Part Considerations

The modular structure of the Lenze i500 series decouples the I5CA50030000A0000S control unit from the underlying power section. When servicing a machine, technicians can replace the control unit without demounting the cabinet power hardware or disconnecting main supply wiring. Compatibility is maintained across Lenze i550 cabinet power units.

To avoid re-commissioning delays, the parameter dataset stored on the plug-in memory module must be inserted into the replacement control unit prior to powering on. If the memory module is missing, unreadable, or throwing error 0x6280, parameters must be loaded into the unit using EASY Starter via USB (i5MADU0000000S), WLAN (i5MADW0000000S), or keypad (i5MADK0000000S). Ensure all RS-485 Modbus RTU termination resistors and communication addresses are verified before restoring fieldbus control.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
0x2220Earth faultGround fault detected on motor side / output phase to ground.Motor cable insulation damaged, ground fault in motor windings, excessive cable capacitance.Check motor and motor cable insulation resistance. Check max motor cable length.
0x2310Overcurrent peak currentOutput current exceeded maximum instantaneous threshold.Acceleration time too short, short circuit at output, motor overload, incorrect motor data.Check acceleration ramp times, motor wiring, and motor nameplate parameter settings.
0x2320Short circuitShort circuit detected between output phases.Short circuit in motor cable or terminal box, power section transistor failure.Inspect motor cabling and motor terminals. If fault persists with motor disconnected, internal hardware fault requires unit return for repair.
0x3210DC-bus overvoltageDC-bus voltage exceeded maximum allowable threshold.Excessive regenerative energy from motor during deceleration, deceleration ramp too short, mains voltage too high.Increase deceleration ramp time, install braking resistor if applicable, check line supply voltage.
0x3220DC-bus undervoltageDC-bus voltage dropped below minimum operating limit.Mains supply failure, supply voltage too low, temporary voltage drop under load.Check supply mains voltage and line supply fuses/fusing.
0x3230Mains phase failureMissing AC input line phase detected.Input phase blown fuse, disconnected line phase, unstable AC mains supply.Inspect input mains wiring and upstream line supply fuses.
0x4210Heatsink overtemperatureHeatsink temperature exceeded safety limit.Inadequate cooling / restricted airflow, ambient temperature too high, fan failure.Clean heatsink, check cabinet ventilation, verify operation of cooling fan.
0x4310Motor overtemperatureMotor temperature sensor trip or i2t thermal model trip.Motor overload, inadequate motor cooling, defective thermal sensor.Check mechanical load on motor, verify motor thermal sensor connection and evaluation setting.
0x6100Internal hardware failureControl electronics or processor hardware error.Faulty internal component, corrupted internal flash memory, hardware failure.Perform power cycle. If fault persists, non-field-serviceable internal hardware fault — replace the Control Unit.
0x6280Memory module errorMemory module missing, damaged, or unreadable.Memory module not fully seated, corrupted parameter dataset, incompatible memory module.Re-insert memory module firmly into slot; replace memory module or re-write parameter set via EASY Starter.
0x7121Motor overload (i2t)Calculated thermal load on motor exceeded limit.Continuous operation above rated current, load block or mechanical binding.Check drive sizing and motor load; verify motor current limits in parameter settings.
0x8130Modbus communication timeoutLoss of Modbus RTU fieldbus communication within configured timeout interval.Damaged RS-485 cable, incorrect baud rate/parity setting, master controller stopped transmitting.Check RS-485 wiring, polarity, termination resistors, and Modbus master communication state.

Frequently Asked Questions

How do I transfer parameters when replacing the Lenze I5CA50030000A0000S control unit?

The control unit includes a removable plug-in memory module (EPM). To transfer parameters to a new unit, simply remove the memory module from the original control unit and plug it firmly into the replacement unit before powering up. This restores all parameter settings without software tools.

What power units are compatible with the I5CA50030000A0000S control unit?

The I5CA50030000A0000S control unit is designed to mount directly onto Lenze i550 cabinet power units within the i500 modular frequency inverter family.

Which communication protocols are supported natively on this module?

The I5CA50030000A0000S features an integrated RS-485 serial interface supporting Modbus RTU fieldbus communication at baud rates up to 115.2 kbps.

What engineering software is required to configure the unit?

Lenze EASY Starter engineering software is used to configure parameters, view the diagnostic logbook, and back up parameters. Connection to a PC requires an optional USB module (i5MADU0000000S) or WLAN module (i5MADW0000000S).

What does a solid red ERR LED indicate on the front panel?

A solid red ERR LED indicates that an operational fault is active, which disables the drive output. Specific fault details can be determined via the keypad, EASY Starter diagnostic logbook, or Modbus registers.

What should I do if fault code 0x6100 appears?

Fault code 0x6100 indicates an internal hardware failure in the control electronics. First, attempt a power cycle. If the fault persists, the internal hardware is non-field-serviceable and the control unit must be replaced or sent for repair.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.