Lenze 13400416 E94ASHE0074 – 9400 StateLine 3kW Servo Drive
Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze 13400416, designated by model type E94ASHE0074, is a 3.0 kW single-axis servo inverter belonging to the Lenze 9400 StateLine series. Engineered for precision multi-axis motion and dynamic torque management, this panel-mounted drive operates from a 3-phase AC supply spanning 320 V to 528 V at 45 to 65 Hz. It delivers a continuous output current of 7.0 A, with peak current ratings supporting 14.0 A for 60 seconds and temporary bursts up to 21.0 A for 3 seconds. An integrated forced-air cooling system maintains continuous thermal stability during intensive operating cycles.
Connection and integration options accommodate a wide range of feedback systems and fieldbus architectures. Motor feedback connects through a dedicated resolver terminal (X7) or a universal encoder port (X8) supporting SinCos, Hiperface, EnDat 2.1/2.2, SSI, HTL, and TTL devices. Onboard communication features an integrated CANopen system bus alongside an RJ45 Ethernet diagnostic interface (X6). Two module slots allow system expansion using optional fieldbus cards such as PROFIBUS, PROFINET, EtherNet/IP, or EtherCAT. Parameter commissioning during replacement is simplified through pluggable MM200 or MM300 smart memory cards, allowing field technicians to copy stored drive settings directly without engineering software.
Front-panel visual status indication provides rapid status checks for drive operational state, system readiness, and bus communication. Diagnostic readouts and plain-text message displays can be accessed via the optional Keypad XT (E94AZKXE) module or through PC connection. If the red ERR LED stays continuously lit at power-up, an internal hardware failure is indicated that cannot be resolved in the field. For defective units experiencing internal component failures, ABC Industrial Parts provides tested replacement units and repair support to quickly restore machine operation.
Technical Specifications
| Rated Power Output | 3.0 kW |
| Rated Output Current | 7.0 A |
| Max Output Current (60s) | 14.0 A |
| Peak Output Current (3s) | 21.0 A |
| Supply Voltage Range | 320 - 528 V AC |
| Supply Frequency | 45 - 65 Hz |
| Output Frequency | 0 - 599 Hz |
| Switching Frequency | 8 kHz |
| Digital Inputs | 8 |
| Digital Outputs | 4 |
| Analog Inputs | 2 |
| Analog Outputs | 2 |
| Onboard Engineering Interface | Ethernet (RJ45, 10/100 Mbit/s) |
| Integrated System Bus | CANopen |
| Mounting Type | Panel mounting with forced air cooling |
Programming and Configuration
Drive setup, parameter adjustment, and diagnostic monitoring for the Lenze E94ASHE0074 are performed using Lenze EASY Starter or Lenze Engineer software packages. Connection to a programming PC is established through the onboard RJ45 Ethernet diagnostic connection (X6) or using an optional E94AZCUS USB diagnostic adapter.
Parameter persistence and field replacement are managed using pluggable MM200 or MM300 memory smart cards. Operational parameters stored on the memory card transfer automatically when inserted into a replacement drive, removing the requirement to perform PC-based parameter downloads during drive swaps.
Communication and System Integration
The Lenze 13400416 includes a built-in CANopen system bus interface for system control and inter-drive synchronization. Online software diagnostics and PC connections utilize the onboard 10/100 Mbit/s RJ45 Ethernet port (X6).
To enable communication with higher-level PLCs and main control networks, the drive includes two expansion module slots. Optional fieldbus modules supported include PROFIBUS-DP (E94AYCPM), PROFINET (E94AYCER), EtherNet/IP (E94AYCEO), and EtherCAT (E94AYCET).
Diagnostics and Status Indication
Operational evaluation on the Lenze E94ASHE0074 is supported by front panel LED indicators, an optional Keypad XT (E94AZKXE) text display, internal fault logbooks, and PC-based trace tools using EASY Starter software.
Four status LEDs on the front panel display the real-time operational status of the drive and CANopen bus. A continuous red ERR LED upon power application indicates an unserviceable internal hardware condition.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| CAN-RUN | Green - Flashing / Continuous | CANopen bus operational state: Green flashing = pre-operational, Green continuous = operational state |
| CAN-ERR | Red - Flashing / Continuous | CANopen communication error: Red flashing = warning level reached, Red continuous = bus off or CAN physical error |
| DRV-READY | Green - Flashing / Continuous | Drive status: Green continuous = drive ready for operation, Green flashing = drive inhibited |
| ERR | Red - Flashing / Continuous | Drive fault state: Red flashing = warning active, Red continuous = fault active requiring reset. Continuous illumination at power-up indicates internal hardware failure requiring replacement |
Replacement and Spare Part Considerations
When replacing a unit, confirm that the spare matches part number 13400416 and model type E94ASHE0074 to match the 3.0 kW power and 7.0 A continuous output current capabilities. Optional fieldbus modules installed in the expansion slots must be transferred to the replacement unit.
Parameter configuration can be completed tool-free by transferring the existing MM200 or MM300 memory smart card to the spare unit. ABC Industrial Parts offers support for acquiring replacement units and repairing failed drives from the Lenze 9400 series.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| 0x00110001 | Heatsink overtemperature | Temperature of the power section heatsink exceeded allowable limit | Excessive ambient temperature, fan blocked or defective, insufficient ventilation space | Clean heatsink cooling fins, check fan operation, lower ambient temperature |
| 0x00110002 | Motor overtemperature | Motor temperature sensor triggered overtemperature warning/fault | Motor overloaded, PTC or KTY thermal sensor circuit open or miswired | Check motor load, verify motor cooling, check temperature sensor wiring |
| 0x00210001 | DC bus overvoltage | DC bus voltage exceeded upper limit | Deceleration ramp too short, regenerative energy too high, braking resistor not connected or defective | Increase deceleration ramp time, check braking resistor connection and chopper settings |
| 0x00210002 | DC bus undervoltage | DC bus voltage dropped below minimum operating limit | Mains supply failure, voltage sag, blown mains fuse | Verify AC supply mains voltage and fuses, check line input connections |
| 0x00310001 | Short circuit / Overcurrent | Instantaneous output current threshold exceeded | Short circuit in motor cable, earth fault in motor winding, acceleration time too short | Check motor cable and motor winding insulation resistance, check acceleration ramp parameters |
| 0x00410001 | Motor I2t overload | Motor load integral exceeded I2t thermal limit | Motor operated above continuous current rating for prolonged duration | Reduce continuous load, check mechanical system for binding |
| 0x00410002 | Drive I2t overload | Power section load integral exceeded I2t thermal limit | High overload cycle maintained beyond specified duration | Reduce drive load cycle or select a higher capacity drive unit |
| 0x00510001 | Mains phase failure | Missing AC supply phase detected on power input | One or two input phases missing, main contactor open, fuse blown | Check three-phase AC mains voltage on input terminals L1, L2, L3 |
| 0x00610001 | Encoder feedback fault | Loss of feedback signal from encoder or resolver | Encoder cable disconnected, broken wire, missing encoder supply, defective sensor | Check feedback cable, shield connection, pinout, and encoder voltage supply |
| 0x00710001 | Fieldbus communication error | Communication failure or watchdog timeout on fieldbus option module | Disconnected fieldbus cable, network master fault, incorrect baud rate or station address | Check network wiring, termination resistors, PLC master status, and bus settings |
| 0x00810001 | System hardware fault | Internal electronic hardware fault or internal component failure detected | Board hardware error, corrupt flash memory, damaged power section | Internal board failure — restart power. If error persists, unit must be returned for repair or replaced |
Frequently Asked Questions
How do I transfer drive parameters to a replacement Lenze E94ASHE0074?
Parameters are transferred by moving the pluggable MM200 or MM300 memory card from the original drive into the replacement unit. The drive automatically loads the saved parameter set when powered up.
Which motor feedback types are compatible with the E94ASHE0074?
The drive includes a dedicated resolver input (X7) and a multi-encoder connector (X8) supporting SinCos, Hiperface, EnDat 2.1/2.2, SSI, HTL, and TTL encoder types.
What does a solid red ERR LED mean upon power-up?
A continuous red ERR LED at power-up indicates an internal electronic hardware failure. If power cycling does not clear the error, the unit contains an unserviceable board fault and requires repair or replacement.
What engineering software is used to connect to the drive?
The drive is configured using Lenze EASY Starter or Lenze Engineer software over the onboard RJ45 Ethernet diagnostic connection (X6) or using an E94AZCUS USB adapter.
Can the E94ASHE0074 drive communicate over PROFINET or PROFIBUS?
Yes. While CANopen is built into the base drive, PROFINET (E94AYCER) and PROFIBUS-DP (E94AYCPM) communications can be established by installing the corresponding expansion module into the drive's option slots.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.