Lenze 13437162 E82EV371_2C201 8200 Vector Frequency Inverter
Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze 13437162, designated by model number E82EV371_2C201, is a 0.37 kW (0.5 hp) frequency inverter belonging to the Lenze 8200 vector product family. Designed for precise speed and torque control of AC electric motors in industrial automation systems, this compact AC drive operates on a nominal 230 V AC supply across an allowable input voltage range of 180 V to 264 V AC at 45 to 65 Hz on either a 1-phase or 3-phase supply. The unit delivers a controlled 3-phase output voltage from 0 to 230 V AC, sustaining a continuous output current of 2.4 A at an 8 kHz carrier switching frequency and an output frequency range of 0 to 480 Hz. Featuring an IP20 protection class enclosure tailored for control cabinet mounting, the drive supports both standard V/f characteristic operation and sensorless vector control to maintain dynamic motor torque across varying speed requirements in conveyor systems, industrial pumps, fans, and packaging machinery.
Connecting and integrating a replacement E82EV371_2C201 unit into an existing machine requires matching the installed physical expansion hardware and drive parameters. The inverter features a modular internal expansion slot that accommodates optional plug-in function modules, including Standard I/O, Application I/O, or fieldbus communications such as CANopen (E82ZAFAC), PROFIBUS-DP (E82ZAFPC), or serial LECOM RS232/RS485 adapters. Commissioning a replacement unit is rarely a simple plug-and-run operation; parameter sets must be transferred to mirror the original drive's settings. The inverter stores up to four complete parameter sets in internal non-volatile EEPROM memory. Parameters can be cloned and uploaded using the optional Lenze XT Keypad (E82ZBC) or transferred via a PC connected to Lenze Global Drive Control (GDC) software. ABC Industrial Parts can support parameter extraction and configuration transfer when restoring replacement drives to production readiness.
System status and fault detection are managed through direct visual cues and software diagnostics. Two front-panel status LEDs provide immediate feedback: a green Operation LED indicates mains power connection and operating state, while a red Fault LED flags active error conditions. Detailed fault diagnostics are available as text descriptions on the XT Keypad display, stored in the drive's parameter C0161 fault history log, or monitored in real time via Lenze GDC software. Recorded fault codes cover specific operating issues such as overcurrent during acceleration (OC1), deceleration (OC2), or constant speed (OC5), DC bus overvoltage (OU) or undervoltage (LU), heatsink or motor overtemperature (OH, OH4, OH7), and earth faults (OC6). Initial field troubleshooting should verify input power quality, motor cable insulation resistance, motor loading, and proper seating of plug-in function modules. Internal circuit board failures, such as EEPROM memory corruption (EER) or internal hardware errors (H05), cannot be repaired in the field; obtaining a tested exchange unit or professional repair through ABC Industrial Parts provides a rapid solution to restore machine uptime.
Technical Specifications
| Rated Power | 0.37 kW |
| Supply Voltage Range | 180 - 264 V AC |
| Supply Frequency | 45 - 65 Hz |
| Output Voltage Range | 0 - 230 V AC |
| Continuous Output Current | 2.4 A |
| Maximum Overload Current | 3.6 A |
| Output Frequency Range | 0 - 480 Hz |
| Switching Frequency | 8 kHz |
| Control Method | V/f characteristic, sensorless vector control |
| Protection Rating | IP20 |
Programming and Configuration
Parameterization and programming for the Lenze 13437162 inverter are handled through dedicated hardware interface options or software tools. The drive features non-volatile EEPROM memory capable of retaining up to four distinct parameter sets simultaneously. This multi-dataset architecture allows complex machine setups or alternative operational modes to be stored directly within the inverter without loss during power interruption. Re-commissioning or resetting a drive can be performed by restoring factory default settings using parameter C0002.
For hands-on parameter access, the optional XT Keypad E82ZBC attaches directly to the front of the drive, presenting clear-text parameter menus and fault code readings. Alternatively, Lenze Global Drive Control (GDC) PC software provides a full graphical commissioning environment. GDC allows engineers to edit parameters, upload and download configuration files, monitor real-time operating parameters, and perform parameter cloning across multiple drives to ensure identical setup in multi-axis machinery.
Communication and System Integration
The Lenze E82EV371_2C201 frequency inverter utilizes a flexible modular architecture for network and fieldbus connectivity. Rather than using fixed built-in fieldbus ports, the inverter includes an internal expansion slot designed to accept plug-in function modules. This modular structure allows the core drive unit to integrate seamlessly into diverse industrial automation architectures without altering the underlying inverter hardware.
Supported interface options include the CANopen function module E82ZAFAC, the PROFIBUS-DP function module E82ZAFPC, and LECOM serial communication interfaces for RS232 or RS485 networks. In addition to fieldbus adapters, the expansion slot accepts Standard I/O or Application I/O modules for discrete control wiring. Communication status and protocol-level link errors, such as function module communication fault CE0, are monitored by the drive to ensure reliable real-time control across automated conveyor systems, packaging equipment, and material handling lines.
Diagnostics and Status Indication
Real-time operational feedback for the Lenze 13437162 is delivered via two visual LED indicators located on the front panel. The green Operation LED indicates that input AC power is applied and reflects the active operational state of the drive through solid or flashing patterns. The red Fault LED illuminates or flashes to alert maintenance staff of active error states or trip conditions.
For comprehensive troubleshooting, the inverter logs historical fault events in parameter C0161. When fitted with the optional XT Keypad E82ZBC, the drive displays active fault codes and plain-text diagnostic messages. System diagnostics can also be performed via Lenze Global Drive Control (GDC) PC software, which displays live operating variables, bus voltages, output currents, and active fault registers for fast root-cause identification.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Operation | Green - Solid / Flashing | Indicates operating status and mains power connected |
| Fault | Red - Solid / Flashing | Indicates fault or active error condition |
Replacement and Spare Part Considerations
When replacing a failed Lenze 13437162 (E82EV371_2C201) frequency inverter, maintenance personnel must confirm that both the core drive specifications and the installed plug-in function module match the original installation. Because the base inverter is supplied without communication modules or keypads, any existing communication modules (such as CANopen E82ZAFAC or PROFIBUS-DP E82ZAFPC) must be unclipped from the failed unit and securely mounted into the replacement drive's expansion slot, taking care to check fixing screws to avoid module communication faults (CE0).
A replacement unit must be loaded with the parameter configuration of the original drive before being placed into active service. Parameters stored in the four EEPROM memory banks of the original drive can be transferred using the XT Keypad E82ZBC memory transfer function or saved and reloaded using Lenze Global Drive Control (GDC) software. If the original parameters cannot be read due to severe drive damage, parameters must be re-entered from machine documentation or donor backups.
Although the Lenze 8200 vector series has been officially discontinued by the manufacturer, direct replacement spare units remain essential for maintaining existing production equipment without undergoing costly panel rewiring or PLC program updates. For long-term modernization strategies, a migration path exists to the modern Lenze i510 or i550 cabinet series frequency inverters.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Overcurrent Acceleration | Short circuit or excessive output current detected during acceleration phase. | Short circuit in motor cable or motor, acceleration time set too short, motor incorrectly sized. | Check motor winding resistance and insulation, check motor connection cable for short circuit, increase acceleration time (C0012). |
| OC2 | Overcurrent Deceleration | Excessive output current detected during deceleration phase. | Deceleration time set too short, braking torque requirement too high. | Increase deceleration time (C0013), fit dynamic braking resistor if required. |
| OC5 | Overcurrent Constant Operation | Excessive output current detected during constant speed operation. | Mechanical overload or blockage, motor under-dimensioned, sudden load impact. | Check mechanical drive train for binding or overload, verify motor power rating. |
| OU | DC Bus Overvoltage | Voltage on internal DC bus exceeded upper threshold limit. | Regenerative energy from motor during deceleration, mains voltage too high. | Extend deceleration time, install brake chopper/resistor module, check input mains voltage. |
| LU | DC Bus Undervoltage | Voltage on internal DC bus dropped below lower threshold limit. | Mains voltage line supply failure, input power phase loss, mains voltage drop under load. | Check input supply voltage, check mains fuses and supply wiring. |
| OH | Heatsink Overtemperature | Inverter heatsink temperature exceeds maximum safety limit. | Insufficient ventilation/cooling around inverter, ambient temperature too high, fan failure, dirty heatsink fins. | Clean heatsink cooling fins, check control cabinet ventilation, lower ambient temperature, reduce switching frequency. |
| OH4 | Motor Overtemperature | Motor temperature sensor or thermal contact trip active. | Motor thermal overload, PTC sensor tripped, cooling fan on motor failed or blocked. | Allow motor to cool down, check motor load, check motor ventilation fan and thermal sensor connections. |
| OH7 | Drive Internal Overtemperature | Internal temperature inside inverter housing exceeds safety limit. | Ambient cabinet temperature exceeds allowable threshold, internal airflow blocked. | Check cabinet air circulation and internal drive cooling. |
| OC6 | Earth Fault | Ground fault detected on motor connection side. | Short circuit to earth/ground in output phase cable or motor winding. | Check motor cable and motor insulation resistance to earth with megohmmeter. |
| EER | EEPROM Memory Error | Internal non-volatile EEPROM memory read/write error. | Internal hardware fault, power interruption during parameter saving operation. | Reload factory default parameters (C0002) and write parameters again. Return unit for repair if fault persists. |
| H05 | Internal Hardware Error | Internal control board or power section failure. | Hardware component failure on internal circuit board. | Internal hardware fault; non-field-serviceable. Replace the drive unit or return unit for repair. |
| CE0 | Communication Error Function Module | Communication interruption between inverter internal control board and plug-in function module. | Function module not seated correctly, loose connection, defective module or drive interface. | Power down drive, re-seat plug-in function module securely, check fixing screws. |
| LP1 | Mains Phase Failure | One of the AC input mains supply phases is missing or unbalanced. | Blown input fuse, loose input wiring terminal connection. | Check input supply lines and input power terminal connections. |
Frequently Asked Questions
How do I transfer parameters from a failed Lenze 13437162 inverter to a replacement drive?
Parameters can be transferred using the optional Lenze XT Keypad E82ZBC or via Lenze Global Drive Control (GDC) PC software. If the keypad is available, parameter sets saved in the internal EEPROM can be copied directly to the keypad and downloaded into the new unit. Alternatively, connecting a PC running GDC software allows uploading the parameter file from the original drive or backup and downloading it into the replacement inverter.
What plug-in function modules are supported by the E82EV371_2C201 inverter?
The E82EV371_2C201 features an internal expansion slot that accepts plug-in function modules including Standard I/O, Application I/O, CANopen module E82ZAFAC, PROFIBUS-DP module E82ZAFPC, and LECOM serial adapters for RS232 or RS485 communication.
What does fault code H05 indicate on the Lenze 8200 vector drive?
Fault code H05 indicates an internal hardware error within the control board or power section of the inverter. This is a non-field-serviceable fault caused by hardware component failure. The unit must be replaced or sent for professional repair.
Can the Lenze 13437162 inverter operate on both single-phase and three-phase AC supplies?
Yes, the drive operates on an input voltage range of 180 V to 264 V AC on either a 1-phase or 3-phase supply at 45 to 65 Hz, providing a controlled 3-phase output from 0 to 230 V AC to the motor.
What action should be taken if the drive trips on fault code OU (DC Bus Overvoltage)?
An OU fault occurs when regenerative energy from the motor during deceleration causes the internal DC bus voltage to exceed safety limits, or when input mains voltage is too high. Recommended actions include extending the deceleration time (parameter C0013), installing a brake chopper and braking resistor, or checking the input mains voltage.
Is the Lenze 8200 vector series still active, and what is the recommended upgrade path?
The Lenze 8200 vector series is officially discontinued. While drop-in replacement units remain available for existing installations, Lenze recommends the i510 or i550 cabinet series as the migration path for future system modernizations.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.