Lenze 00400052 EVF8245-E 8200 Vector Frequency Inverter 15 kW
Het item werd toegevoegd aan uw offerteaanvraag
Product Information
The Lenze 00400052 EVF8245-E is a 15 kW AC frequency inverter from the 8200 vector series, engineered for precise variable speed and torque motor control in industrial automated machinery. Built for panel and control cabinet installation with an IP20 protection rating and integrated heatsink, this drive operates on a 3-phase AC supply ranging from 320 V to 528 V AC (400 V / 480 V AC nominal) with a rated mains input current of 38 A. The drive provides a continuous output current rating of 32 A across an output frequency range of 0 to 480 Hz with an 8 kHz switching frequency. Capable of handling demanding motion applications, it supports multiple control methods including sensorless vector control, V/f characteristic curve control, and direct torque control.
Integrating the EVF8245-E into an existing control system relies on plug-in Function Module slots (FIF), allowing custom physical interface and network configurations. The drive accommodates Standard I/O or Application I/O modules, as well as fieldbus interfaces such as PROFIBUS-DP (EMF2133IB) and CANopen (EMF2173IB / EMF2178IB). Commissioning a replacement unit requires restoring the machine's parameter profile, as a spare drive is not plug-and-run without parameter configuration. Parameters stored in up to 4 internal non-volatile parameter sets can be written and backed up using the Keypad XT (EMF2102IB) operating module or Lenze Global Drive Control (GDC) software. Expert technical assistance from ABC Industrial Parts can assist in parameter extraction and configuration backup transfer when replacing a failed drive.
Operating status and faults are visually indicated via front-panel LEDs, where a solid green LED indicates operational readiness, a blinking green LED signals operation inhibited, a solid red LED indicates an active trip or fault, and a blinking red LED denotes a warning. In-depth diagnostics are managed via parameter C0183 for active trip conditions and parameter C0161 for the fault history log, accessible via Keypad XT or GDC software. First-line troubleshooting for trip codes like overcurrent (OC1, OC2, OC5), overvoltage (OU), or undervoltage (LU) involves checking motor wiring, mains voltage stability, and deceleration ramp times. For internal control board failures or hardware faults such as H05 or system fault Pr1, internal components cannot be serviced on-site, making unit repair or a reconditioned replacement unit from ABC Industrial Parts the effective route to restore production.
Technical Specifications
| Manufacturer | Lenze |
| Part number | 00400052 |
| Model / Type | EVF8245-E |
| Product family | 8200 vector |
| Component type | Frequency Inverter |
| Rated power | 15 kW |
| Supply voltage | 400 / 480 V AC |
| Supply voltage range | 320 - 528 V AC |
| Mains input current | 38 A |
| Rated output current | 32 A |
| Output frequency range | 0 - 480 Hz |
| Switching frequency | 8 kHz |
| Control methods | V/f characteristic control, sensorless vector control, torque control |
| IP rating | IP20 |
| Mounting type | Cabinet / Panel Mounting |
Programming and Configuration
Programming and parameter management for the Lenze 00400052 EVF8245-E inverter are conducted using Lenze Global Drive Control (GDC) software or the plug-in Keypad XT module (EMF2102IB). The drive architecture incorporates internal EEPROM memory capable of holding up to 4 independent parameter sets. This multi-parameter structure allows operators to store alternative application profiles or maintain standard configuration sets directly within non-volatile onboard memory.
When commissioning a spare unit or adjusting machine parameters, software communication is established via the front interface. Parameter code C0002 allows technicians to reset the inverter to factory default settings when needed. In the event of parameter memory corruption indicated by fault code P12, reloading factory default settings and restoring stored parameter files via GDC software re-establishes valid drive operation.
Communication and System Integration
System integration for the EVF8245-E inverter is built around Lenze's flexible plug-in Function Module slots (FIF). The drive separates basic power electronics from interface functions, allowing maintenance teams to insert required digital, analog, or fieldbus modules directly into the front slot of the unit.
Compatible network interface options include the EMF2133IB PROFIBUS-DP module and the EMF2173IB or EMF2178IB CANopen modules, as well as modules for INTERBUS, DeviceNet, and AS-Interface. In addition to fieldbus automation modules, Standard I/O and Application I/O modules provide hardwired control terminals. If communication between the internal drive processor and an attached function module is interrupted, the inverter registers fault code CE0.
Diagnostics and Status Indication
The EVF8245-E inverter features comprehensive real-time monitoring and visual indicators on its front panel. Internal diagnostic routines continuously monitor DC bus voltage levels, output phase currents, heatsink temperatures, internal enclosure thermal thresholds, and motor I²t thermal overload calculations.
Detailed fault evaluation is supported by onboard diagnostic parameter codes. Parameter code C0183 displays current trip conditions, while parameter code C0161 maintains a fault history log. Diagnostic status and active alarms can be monitored live through the GDC software diagnostic panel or read directly from the Keypad XT display.
Status LED Indicators
| LED | Color/Status | Meaning |
|---|---|---|
| Green LED | Green - Solid / Blinking | On = Inverter ready / operation enabled; Blinking = Operation inhibited or controller disable active |
| Red LED | Red - Solid / Blinking | On = Active trip/fault present; Blinking = Active warning present |
Replacement and Spare Part Considerations
Replacing a failed 00400052 EVF8245-E frequency inverter requires matching both the main unit part number and the configuration of attached function modules. Ensure that the replacement drive matches the 15 kW power rating, 32 A output current capacity, and 320 V to 528 V AC input voltage range. Transfer the plug-in communication or I/O module from the original drive to maintain fieldbus connectivity.
A replacement unit will not operate correctly until the original machine's parameter profile is written to its internal memory. Parameter sets can be loaded directly using Lenze Global Drive Control software or transferred using the Keypad XT module. While the 8200 vector product line is discontinued, maintaining direct replacements allows plant operators to avoid immediate control redesigns. For complete system overhauls, the Lenze i550 cabinet frequency inverter series represents the official migration path.
Error Codes & Fault Codes
The following error codes may be displayed during operation or diagnostics:
| Code | Name | Description | Possible Cause | Recommended Action |
|---|---|---|---|---|
| OC1 | Short circuit / Overcurrent during acceleration | Output current exceeded peak limit during acceleration phase | Acceleration time too short; Short circuit in motor cable; Ground fault; Motor improperly connected | Increase acceleration time; Inspect motor cable and windings for short circuit or ground fault |
| OC2 | Short circuit / Overcurrent during deceleration | Output current exceeded peak limit during deceleration phase | Deceleration time too short; Short circuit in motor circuit | Increase deceleration time or install braking resistor; Check motor circuit |
| OC5 | Short circuit / Overcurrent during constant operation | Output current exceeded peak limit during steady-state operation | Abrupt load change; Motor overload; Intermittent short circuit | Check mechanical load for jam or binding; Verify motor sizing |
| OC6 | Motor overload (I²t) | Calculated motor load exceed permissible I²t thermal threshold | Continuous operation at excessive current; Incorrect motor data parameters set | Check process load; Verify motor current settings in C0088 / C0089 |
| OU | Overvoltage in DC bus | DC bus voltage exceeded upper limit (>770 V DC) | Generative energy during braking too high; Deceleration time too short; Supply voltage too high | Extend deceleration time; Connect external braking resistor; Check mains input supply voltage |
| LU | Undervoltage in DC bus | DC bus voltage dropped below lower limit (<400 V DC threshold) | Mains supply failure; Input phase missing; Supply voltage too low | Measure line input voltage; Inspect fuses and input wiring |
| OH | Heatsink overtemperature | Inverter heatsink temperature exceeded maximum threshold (>90 °C) | Inadequate cooling / restricted airflow; Ambient temperature too high; Internal fan failure | Clean heatsink cooling fins; Ensure cabinet ventilation; Check cooling fan operation |
| OH4 | Inverter inside temperature high | Internal ambient temperature inside inverter enclosure exceeded threshold | Ambient temperature too high; Control cabinet cooling insufficient | Improve control cabinet ventilation and cooling |
| OH7 | Motor overtemperature (PTC) | Thermal contact or PTC thermistor input triggered motor overtemperature fault | Motor thermal overload; Cooling fan failure on motor | Allow motor to cool; Check mechanical load and motor ventilation |
| OH8 | Motor temperature sensor error | Open circuit or short circuit detected on motor PTC / temperature sensor terminal | Sensor wiring disconnected or damaged; Broken sensor wire | Inspect temperature sensor wiring and connections |
| LP1 | Motor phase failure | Failure detected in one of the motor output phases (U, V, W) | Interrupted motor line connection; Motor winding open circuit; Unbalanced load | Inspect motor cables, terminal block, and motor windings |
| EFr | Earth fault / Ground fault | Ground fault current detected on output motor phase | Insulation breakdown in motor or motor cable to earth ground | Measure insulation resistance of motor cable and motor with a megohmmeter |
| CE0 | Communication error on Automation Module | Communication interruption between inverter processing control and attached plug-in function/communication module | Loose module plug connection; Module failure; Bus timeout | Check seating of plug-in module; Check fieldbus master connection; Replace module if defective |
| EEr | External fault input | Digital input assigned to external fault function was activated | External monitoring device triggered fault condition | Inspect external circuit connected to configured fault input |
| H05 | Internal hardware fault | Internal control board error or internal voltage supply fault detected | Hardware component defect on internal control/power board | Internal hardware fault — return unit for repair or replace inverter |
| P12 | Parameter set error | EEPROM checksum error or corrupted parameter set data | Power interruption during parameter save; Damaged internal EEPROM | Reload factory default settings (C0002) and restore configuration; Replace unit if error persists |
| Pr1 | System fault | Internal program fault or microcontroller fault | Severe electrical interference (EMC) or internal microcontroller defect | Perform power cycle; If fault persists, internal hardware error requires service or unit replacement |
Frequently Asked Questions
What software and hardware tools are used to program the Lenze EVF8245-E?
The EVF8245-E frequency inverter is programmed using Lenze Global Drive Control (GDC) software or configured directly using the optional Keypad XT (EMF2102IB) display module.
How are parameter settings transferred to a replacement EVF8245-E inverter?
Parameter settings can be backed up and restored via GDC software or transferred using the Keypad XT module. The drive supports up to 4 independent parameter sets stored in internal EEPROM memory.
What does fault code OU indicate on the Lenze 00400052 inverter?
Fault code OU indicates an overvoltage condition in the DC bus exceeding 770 V DC, caused by excessive braking energy, short deceleration times, or high supply voltage.
Which communication modules can be plugged into the EVF8245-E interface slot?
Compatible modules include the EMF2133IB for PROFIBUS-DP, the EMF2173IB or EMF2178IB for CANopen, and options for DeviceNet, INTERBUS, and AS-Interface.
What is the recommended modern successor for the discontinued Lenze 8200 vector series?
Lenze recommends migrating to the Lenze i550 cabinet frequency inverter series for new equipment installations and control panel retrofits.
Take advantage of our exchange formula
A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.
Play it safe with our warranty conditions
Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.
Data backup and recovery
Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.
Specific firmware and hardware versions
If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.