Lenze 00409933 EMF2111IB-V531 System Bus CAN Communication Module

New 
1 available for direct collection
Refurbished   
On request
Want to exchange a faulty product?
Receive a discount on your purchase when you turn in a faulty product. Upon receipt, we will check the product to determine its eligibility according to the terms and conditions.
Repair  
Available
We can repair this product for you.
 

Product Information

Product Family: 8200 Vector / 9300 Series | Series: 8200 Vector / 9300

The Lenze 00409933 EMF2111IB-V531 is an industrial System Bus communication module engineered to integrate Lenze 8200 vector frequency inverters and 9300 series servo drives into CAN networks. Mounting directly into the Function Module (FIF) slot of the host drive controller, this compact interface operates on CAN layer 2 and CANopen drive profiles to enable multi-drive synchronization, speed and torque control, and distributed parameter access. Internal power is supplied through the host drive's FIF interface, eliminating the need for an external power supply wiring harness.

Network setup and node alignment are accomplished directly on the hardware via onboard 6-pole DIP switches. These switches allow technicians to select node addresses from 1 to 63 and set transmission speeds from 10 kbit/s up to 1000 kbit/s (1 Mbit/s). Field wiring terminates at a removable pluggable screw terminal block supporting CANH, CANL, and CAN_GND connections. When commissioning a replacement spare, matching the DIP switch configuration on the new module provides direct hardware compatibility, while ABC Industrial Parts can assist in sourcing fully tested units to minimize machine downtime.

System status monitoring and field diagnostics are supported through front-panel visual indications and drive-level software access. A dual-color Red/Green CAN Status LED displays real-time bus operation, network activity, and error conditions. Detailed parameterization and diagnostic readouts, including monitoring parameters C0359 and C0361, are accessible via Lenze Global Drive Control (GDC) engineering software or connected XT and PT keypads. If communication breaks down due to wiring or hardware faults, ABC Industrial Parts offers repair and replacement options to get critical equipment operational again.

Technical Specifications

ManufacturerLenze
Part number00409933
Model / TypeEMF2111IB-V531
Component typeCommunication Module
Communication interfaceSystem Bus (CAN) / CANopen
Transmission speed range10 kbit/s to 1000 kbit/s
Addressing rangeNode 1 to 63
Connector typePluggable screw terminal block
Form factor / Slot compatibilityLenze Function Module (FIF) slot
Supply voltageInternal via host drive FIF slot

Programming and Configuration

Hardware setup for the EMF2111IB-V531 is managed through an integrated 6-pole DIP switch located on the module. This permits direct physical setting of the bus node address across a range of 1 to 63 and configuration of the transmission baud rate between 10 kbit/s and 1000 kbit/s without requiring initial software tools.

For advanced setup and system monitoring, the module communicates through the host drive controller with Lenze Global Drive Control (GDC) software. Diagnostic and system bus operational data can be verified using parameters C0359 and C0361. Drive setup can also be executed using connected Lenze XT or PT keypads, or compatible keypad modules such as the EMF2171IB and EMF2172IB.

Communication and System Integration

The EMF2111IB-V531 provides a dedicated System Bus interface based on CAN layer 2 and CANopen drive profiles. It facilitates high-speed data transmission required for inter-drive speed and torque synchronization in multi-axis machinery, packaging lines, material handling conveyors, and textile manufacturing systems.

Physical bus connections are wired through a pluggable screw terminal block accommodating CANH, CANL, and CAN_GND signal connections. The module supports data transfer rates up to 1000 kbit/s (1 Mbit/s) and integrates directly into multi-drive networks controlled by master devices or peer-to-peer drive architectures.

Diagnostics and Status Indication

Visual status indication is provided on the module faceplate via a dual-color Red/Green CAN Status LED. This indicator displays operational states, active bus communications, and error or bus-off conditions for rapid localized maintenance.

Extended system diagnostics are conducted through the host drive controller using parameters C0359 and C0361 in Lenze Global Drive Control (GDC) software or on-site via connected XT and PT keypads.

Status LED Indicators

LEDColor/StatusMeaning
CAN Status LEDRed/Green - Solid / FlashingIndicates CAN network communication state, bus-off conditions, and module operational status

Replacement and Spare Part Considerations

When replacing a Lenze 00409933 EMF2111IB-V531 module, ensure the host drive is powered down before removing or plugging the module into the integrated Function Module (FIF) slot. Power is drawn directly from the host drive, so external power wiring is not required.

Before restoring power, copy the 6-pole DIP switch settings from the failed module to the replacement unit to ensure identical node addressing (1 to 63) and baud rate (10 to 1000 kbit/s). Verify that 120 Ohm termination resistors are correctly positioned at both physical ends of the CAN bus line to prevent signal reflection errors.

Error Codes & Fault Codes

The following error codes may be displayed during operation or diagnostics:

CodeNameDescriptionPossible CauseRecommended Action
CE0Communication Error 0 (System Bus Fault)Interruption or telegram failure on System Bus (CAN).CAN bus cable broken or disconnected, incorrect baud rate, wrong node address, missing bus termination resistor.Check CAN wiring, verify DIP switch settings for address/baud rate, check termination resistor (120 Ohm at bus ends).
CE1Process Data Object 1 Timeout (CAN Error 1)Time-out during reception of CAN Process Data Object 1 (CAN-IN1).Master or sender stopped sending process data, bus overload, line interference.Check transmitter node, verify fieldbus scan time, check CAN cable shielding.
CE2Process Data Object 2 Timeout (CAN Error 2)Time-out during reception of CAN Process Data Object 2 (CAN-IN2).Transmitter node offline or message response delayed.Check sender node status and network traffic load.
CE3Process Data Object 3 Timeout (CAN Error 3)Time-out during reception of CAN Process Data Object 3 (CAN-IN3).Transmitter node offline or message response delayed.Check sender node status and CAN cyclic communication setup.
ECESystem Bus Hardware / Bus-Off FaultCAN controller bus-off state caused by excessive transmit/receive error counters or module failure.Severe EMC noise on line, short circuit in CAN bus, defective transceiver, internal hardware failure.Check shield connection and grounding; cycle power. If error persists with clean wiring, internal module hardware fault exists — replace the unit.

Frequently Asked Questions

Which drive series are compatible with the Lenze 00409933 EMF2111IB-V531 module?

The EMF2111IB-V531 is designed to plug directly into the integrated Function Module (FIF) slot of Lenze 8200 vector frequency inverters and Lenze 9300 series servo drives.

How are the node address and transmission baud rate configured on this module?

Address and baud rate settings are set using the onboard 6-pole DIP switches. Node addressing can be set from 1 to 63, and transmission speeds can be configured between 10 kbit/s and 1000 kbit/s (1 Mbit/s).

Does the EMF2111IB-V531 require an external 24V power supply?

No, the module receives operational power directly through its plug-in connection in the host drive's FIF slot.

What does an ECE fault code indicate on this system?

An ECE fault signifies a System Bus Hardware or Bus-Off fault. It occurs due to severe EMC noise, short circuits on the CAN bus, or an internal hardware failure in the module. If shielding and wiring are intact and cycling power does not clear the error, the module hardware requires replacement.

What software tools can be used to monitor diagnostics on the EMF2111IB-V531?

System parameters C0359 and C0361 can be monitored using Lenze Global Drive Control (GDC) software or directly via XT and PT keypads attached to the host drive controller.

Take advantage of our exchange formula

A defective product does not have to be worthless. At ABC Industrial Parts, you can hand in defective products and immediately benefit from a discount on your new purchase. This is a smart way to save money while contributing to a circular economy.

Play it safe with our warranty conditions

Industrial plants prefer to keep running invariably, no matter what. Therefore, it is essential that you can rely on high-quality products and/or sustainable repairs. With our warranty conditions, you can count on certainty, whether you choose new, used or repaired products.​​​​​​​

Data backup and recovery

Have you lost valuable parameters or data due to a malfunction while the manufacturer no longer provides support? At ABC Industrial Parts, we help you secure this data, both for common and specific products.

Specific firmware and hardware versions

If you are working with specific hardware or firmware versions that are no longer available from the manufacturer, ABC Industrial Parts is your partner. When making your enquiry, clearly state which versions you need, we will then look at the possibilities of supplying those versions, so that your installations continue to function optimally.


Disclaimer:
We are not an authorised distributor of Lenze.
Product photos are for illustration purposes only and may differ from the actual product delivered.
Some of the content on this page was created with the help of AI. While we strive to provide accurate and up-to-date information, errors may occur.